Longo programmable controller LPC-2.DP1

3.3 Parameters

If parameter is set to logical “1”,   is considered to be active, enabled or set. If parameter has
logical value “0” is considered to be inactive, disabled, or cleared.

Parameter can be status, command or both. When parameter is marked as status this means that
module is sending information to controller. On the other hand, command represents request from
main module to module.

Communication

: Normal state is  “1”.  If off, there is communication error or no communication

established.

Normal/Economic

: When set Economic mode is enabled. Default value is “0” therefore normal mode

is selected.

Local/Remote

: When “0”, Local mode is selected. In this mode CP uses set point set by TB.

In remote mode, “1”, CP uses set point received from other devices (HMI, Touch Panel, OT1,
..) through communication channel.

Heat valve

: When valve is opened “1” is reported, while “0” stands for closed valve

Cool valve

: When valve is opened “1” is reported, while “0” stands for closed valve

System On/Off

: If parameter is set to “0” CP functions are executing in normal mode. If set to “1”

Fan speed and all valves are OFF (closed).

Winter/Summer: 

Used only for t

wo-pipe system

 to change calculation for Hot valve and Fan speed;

Winter – heating (“0”) to Summer – cooling (“1”)

4/2 pipe

: Four-pipe system manages hot and cold water pipes simultaneously. Two-pipe system 

manages only one pair of pipes (one valve, pump). Operation in two-pipe system is therefore
dependent on 

Winter/Summer (Change-over)

 parameter.

“0” = Four pipe system
“1” = Two pipe system

Fan speed I.

: When this parameter is “1”, actual fan speed is I. 

Fan speed II.

: When this parameter is “1”, actual fan speed is II.

Fan speed III.

: When this parameter is “1”, actual fan speed is III.

Fan speed mode 

: This parameter determines fan speed adjustment mode:

“0”: Manual  
“1”: Auto

Balcony door En.

: When switch for detecting opened balcony door is connected to the system, this

function should be enabled (“1”). 

Balcony door switch

: Parameter reports whether door are closed or opened

“1”: closed
“0”: opened

Window En.

: When switch for detecting opened window is connected to the system, this function

should be enabled (“1”).

Window switch

:  Parameter reports whether window is closed or opened

“1”: closed
“0”: opened

Max. temp.

:  denotes max. SP temp. which is scaled to top of LCD temperature bar

Min. temp.

: denotes min. SP temp. which is scaled to bottom of LCD temperature bar

P regulation par.

: Proportional parameter for PI calculation algorithm on CP

5

Содержание LPC-2.DP1

Страница 1: ...USER MANUAL Longo programmable controller LPC 2 DP1 Temperature Control panel Version 4 SMARTEH d o o Poljubinj 114 5220 Tolmin Slovenia Tel 386 0 5 388 44 00 e mail info smarteh si www smarteh si...

Страница 2: ...Longo programmable controller LPC 2 DP1 Written by SMARTEH d o o Copyright 2016 SMARTEH d o o User Manual Document Version 4 March 2016 i...

Страница 3: ...ot include damage due to transport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection s...

Страница 4: ...1 2 FEATURES 2 3 OPERATION 3 3 1 Operational modes 3 3 2 Functions 4 3 3 Parameters 5 4 INSTALLATION 7 4 1 Connection scheme 7 4 2 Mounting frame selection 9 4 3 Mounting instructions 10 4 4 Module l...

Страница 5: ...eed I speed II speed III AUTO or OFF modes of operation can be selected Fan mode is represented with left blue LCD bar graph With ECO economy OFF and ERR error signs on LCD CP status is represented Co...

Страница 6: ...controller off 10 position LCD bar graph for temperature set point 4 position LCD bar graph for manual fan speed auto and controller off Light intensity measurement LCD intensity control Step less or...

Страница 7: ...led Display will return to stand by mode if touch buttons are not pressed for a while 5 seconds Changing operation modes Request for switching between CP normal and economic operating mode is done wit...

Страница 8: ...re and temperature set point is 1 C the PI output value will increase every second by 1 On the other hand if the difference is 1 C the PI output value will decrease every second by 1 2 4 pipe system s...

Страница 9: ...sed Winter Summer Used only for two pipe system to change calculation for Hot valve and Fan speed Winter heating 0 to Summer cooling 1 4 2 pipe Four pipe system manages hot and cold water pipes simult...

Страница 10: ...into PI calculation algorithm as SP Fan mode set Fan mode on CP panel can be remotely changed by main module 0 1 2 3 4 Off I II III auto The change is made by setting the Fan Remote Cmd command bit Re...

Страница 11: ...Longo programmable controller LPC 2 DP1 4 INSTALLATION 4 1 Connection scheme Figure 2 Connection scheme 7...

Страница 12: ...cted II middle speed selected III maximum speed selected AUTO auto speed selection OFF module functions switched off TB1 Up left Fan mode Increase Mode speed selection TB2 Down left Fan mode Decrease...

Страница 13: ...were not verified by Smarteh Before installation verify compatibility of non listed frames Module housing has a fin on each side which can be easily removed with knife cutter or pliers This adaptation...

Страница 14: ...connected to the main power supply Module should be positioned in the wall inside of the room Avoid direct sunlight or positioning near heating cooling source object Usage of cover frames and holders...

Страница 15: ...DP1 with cover plate LPC 2 DP1 is connected to the main module with interconnection cable e g SSK ICM 7 which must be ordered together with LPC 2 DP1 module When more modules e g LPC 2 CR1 LPC 2 CH1...

Страница 16: ...ounting module 01 derivation code 001 version code reserved for future HW and or SW firmware upgrades D C 01 10 is the date code 01 week and 10 year of production Label 2 description S N DP1 S9 090000...

Страница 17: ...Longo programmable controller LPC 2 DP1 5 REGULATION DIAGRAM 13...

Страница 18: ...main module Interconnection connector type RJ 12 6 6 Power consumption 1 W Dimensions W x H x D 75 x 49 x 29 mm Weight 50 g Maximum altitude 2000 m Mounting position horizontal Ambient temperature 0 t...

Страница 19: ...scribes all the changes to the document Date V Description 30 03 16 4 Added sentence about sealing junction box and pipes on page 10 01 07 12 3 CGP General update 20 07 10 2 Updated regulation diagram...

Страница 20: ...Longo programmable controller LPC 2 DP1 8 NOTES 16...

Отзывы: