Installation
1.7
Installation in Hazardous Areas
WARNING
Explosions could result in death or serious injury, besides financial damage. Installation of this
transmitter in explosive areas
must be carried out in accordance with the local standards and the
protection type adopted .Before continuing the installation make sure the certificate parameters are I n
accordance with the classified area where the equipment will be installed.
The instrument modification or parts replacement supplied by other than authorized representative of
Smar is prohibited and will void the certification.
The transmitters are marked with options of the protection type. The certification is valid only when the
protection type is indicated by the user. Once a particular type of protection is selected, any other type
of protection can not be used.
Explosion/Flame Proof
WARNING
Only use Explosion Proof/Flameproof certified Plugs, Adapters and Cable glands.
In Explosion-Proof installations the cable entries must be connected or closed using metal cable gland
and metal blanking plug, both with at least IP66 and Ex-d certification.
The standard plugs provided by Smar are certified according to CEPEL certificate. If the plug needs to
be replaced, a certified plug must be used.
The electrical connection with NPT thread must use waterproofing sealant. A non-hardening silicone
sealant is recommended.
For NEMKO ATEX certificate please to follow the installation guidelines in hazardous locations below:
Group II Category 2G, Ex d, Group IIC, Temperature Class T6, EPL Gb U = 28VDC
Ambient Temperature: -20 to 60ºC for T6
Environmental Protection: IP66/687 or IP66W/687W
The electrical connection available are ½ - 14NPT and M20x1,5.
Cable entries must be connected or closed using metal cable gland and metal blanking plug, both with
at least IP66 and Ex-d certification or any appropriate ATEX approved metal cable gland and metal
blanking plug. Do not remove the transmitter covers when power is ON.
Intrinsically Safe
WARNING
In hazardous zones with intrinsically safe or non-incendive requirements, the circuit entity parameters
and applicable installation procedures must be observed.
To protect the application the transmitter
must be connected to a barrier
. Match the parameters
between barrier and the equipment (Consider the cable parameters). Associated apparatus ground
bus shall be insulated from panels and mounting enclosures. Shield is optional. If used, be sure to
insulate the end not grounded. Cable capacitance and inductance plus C
i
and L
i
must be smaller than
Co and Lo of the associated Apparatus.
For free access to the Hart bus in the explosive environment, ensure the instruments in the loop are
installed in accordance with intrinsically safe or non-incendive field wiring practices. Use only Ex Hart
communicator approved according to the type of protection Ex-i (IS) or Ex-n (NI).
It is not recommended to remove the transmitter cover when the power is ON.
Содержание TT301
Страница 2: ...www el scada ru...
Страница 8: ...TT301 Operation Maintenance Instruction Manual VIII...
Страница 16: ...TT301 Operation Maintenance Instruction Manual 1 8...
Страница 25: ...Operation 2 9 ALARM 1 ALARM 2 Figure 2 9 Typical Alarm Condition Display...
Страница 26: ...TT301 Operation and Maintenance Instruction Manual 2 10...
Страница 28: ...TT301 Operation Maintence Instruction Manual 3 2 Figure 3 1 Configurator Figure 3 2 CONF401 Screen...
Страница 47: ...Programming Using Local Adjustment 4 9 Configuration CONF Figure 4 7 Local Adjustment Configuration Tree...
Страница 58: ...TT301 Operation and Maintenance Instruction Manual 5 6 Figure 5 2 Four Possible Positions of the Display...
Страница 60: ...TT301 Operation and Maintenance Instruction Manual 5 8...
Страница 67: ...Certifications Information A 3 CSA NEMKO and DMT CEPEL...
Страница 69: ...Certifications Information A 5 CEPEL...
Страница 70: ...Operation and Maintenance Instruction Manual TT301 A 6 Control Drawing Factory Mutual FM...
Страница 71: ...Certifications Information A 7 NEMKO...
Страница 72: ...Operation and Maintenance Instruction Manual TT301 A 8 Canadian Standards Association CSA...
Страница 74: ...SRF Service Request Form B 2...