Configuration
3.13
Table of Points - Linearization
The output signal follows a curve determined by 16 points freely configurable.
TABLE OF POINTS - LINEARIZATION
Points
%
Actual Value
(process Out)
X(%)
Desired position
value (of the
process ) Y(%)
1
0 0
5 Points
(See figure: Position graphic of the
magnet)
2
26.4 25
3
48.6 50
4
74.2 75
5
100 100
6
- -
Not used
.
.
.
.
.
.
.
.
.
16
- -
Table function
(Linearization)
Depending on the application and according with the process, the transmitter output or PV is shown
in one linear characteristic curve (position, level, opening etc.). TP also has the option for adjust this
curve of linear output, to that the value in percentage can be linearized, you have to uses a table 16
points at maximum and minimum points 2. The output is calculated by interpolating these points.
The user can set the total of points desired.
To configure the feature table:
The user must choose the item "function" to "table" option.
Select the number of points, according to you need, 2-16 points.
Create the table and indicate the current position value in the "X" (%) column and the
desired position value in the "Y" (%) column. Once created the table, send the points for
the position transmitter.
Done, this configured.
Position Graphic of the Magnet
Exemple:
0 %
25 %
50 %
75 %
100 %
Desired position
value (of the
process) Y(%)
0 %
26,4 %
48,6 %
74,2 %
100 %
Actual Value
(process Out)
X(%)
NOTE:
If the table is enabled there will be an indication on the Display LCD with the F(X) icon.
Figure 3.13 - Position Graphic of the Magnet
Содержание TP302
Страница 15: ...Installation 1 9 Figure 1 9 Bus Topology Figure 1 10 Tree Topology ...
Страница 34: ...TP302 Operation Maintenance and Instructions Manual 3 14 ...
Страница 42: ...TP302 Operation Maintenance and Instructions Manual 4 8 ...
Страница 50: ...VR524 Qrgtcvkqp cpf Ockpvgpcpeg Kpuvtwevkqp Ocpwcn C08 CEPEL Centro de Pesquisa de Energia Elétrica ...
Страница 51: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Eqpvtqn Ftcykpi Canadian Standards Association CSA ...