RHP303 – User’s Manual
11
BAUD RATE
SW1.1
SW1.2
SW1.3
SW1.4
SW1.5
SW1.6
SW1.7
SW1.8
AUTO
OFF
X
X
X
X
X
X
X
M
ANUAL
9.6 Kbps
ON
ON
OFF
OFF
OFF
X
X
X
19.2 Kbps
ON
OFF
ON
OFF
OFF
X
X
X
45.45 Kbps
ON
ON
ON
OFF
OFF
X
X
X
93.75 Kbps
ON
OFF
OFF
ON
OFF
X
X
X
187.5 Kbps
ON
ON
OFF
ON
OFF
X
X
X
500 Kbps
ON
OFF
ON
ON
OFF
X
X
X
1.5 Mbps
ON
ON
ON
ON
OFF
X
X
X
3.0 Mbps
ON
OFF
OFF
OFF
ON
X
X
X
6.0 Mbps
ON
ON
OFF
OFF
ON
X
X
X
12 Mbps
ON
OFF
ON
OFF
ON
X
X
X
Note: The “X” on the table means “The switch position is irrelevant”.
To adjust the transmission speed, use a screwdriver.
NOTE
For the Modbus protocol, the available rates must be adjusted in “Manual”: 9.6 Kbps and 19.2
Kbps.
Technical Specifications
POWER SUPPLY
Power connector
3-pin terminal block
Voltage
12 to 30 Vdc (24 Vdc nominal)
Maximum current
270 mA @ 24 Vdc
Protection against reverse polarity
Yes
Cabling
< 2.5 mm
2
FUNCTION SPECIFICATIONS
Supported Protocols
Modbus, DP-V0, DP- V1, DP-V2, FDL, MPI,
FMS, PROFIsafe, PROFIdrive and any other
FDL-based protocol
Communication Rates (kbps)
9.6; 19.2; 45.45; 93.75; 187.5; 500; 1500;
3000; 6000 and 12000
Communication Rate detection
Self-detectable by default or switch
configurable
Communication rate selection switch
0 = Self-detectable by default
Communication rate detection time
< 5 s (if self-detection selected)
Data delay time
1 Tbit for all rates
Jitter delay time
±0.1 Tbit for all rates
Terminators
One on each spur
ENVIRONMENT CONDITIONS
Operation temperature
0 to 60 ºC
Protection degree
IP 20
DIMENSIONS AND WEIGHT
Dimensions (LxWxH)
296 x 125.4 x 65 mm
Weight
612 g
MOUNTING
Support
DIN rail