4 Mounting Instructions
10 –
Fasten the nuts to fix the positioner
bracket to the yoke.
If the actuator is pillar type, fasten the U-
clamp nuts.
11 –
Mount the positioner to the plate and
tighten the hex screws. You can take the
back plate apart to facilitate the assembling.
12 –
Move the positioner as to adjust the
Hall sensor tip in the center of the magnet.
Tighten the nuts after the adjustment.
2
m
m
t
o
4
m
m
ATTENTION:
A minimum distance of 2mm and a maximum
distance of 4mm is recommended between the
magnet external face and the positioner face.
For that, a centralizer device (linear or rotary)
must be used. The centralizer device is in the
positioner packing.
Содержание FY301
Страница 8: ...H 523 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK...
Страница 24: ...FY301 Operation Maintenance and Instructions Manual 1 16...
Страница 54: ...H 523 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn 7038...
Страница 64: ...H 523 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C08 CEPEL Centro de Pesquisa de Energia El trica...
Страница 65: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Eqpvtqn Ftcykpi FM Approvals Factory Mutual...
Страница 66: ...H 523 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 CSA Canadian Standards Association...
Страница 82: ...6 Mounting Instructions...