Sunny Island
Installation & Operating Instructions
BWRI33-12:EE
- 71 -
SMA Regelsysteme GmbH
7.2 Menu “GENSET” (2-2), Operation of Generator
Fig. 7.4: Menu “GENSET“ (2-2)
The menu ”GENSET” (2-2) comprises functions concerning a connected generator.
Such a generator can e. g. be started or stopped manually via this menu or can be
set to automatic operation controlled by the Sunny Island.
The menu item “ACKNOWLEDGE” enables the operator to easily confirm error
states of the generator. At the next start-up attempt the complete starting sequence
is run again. This function can be useful e. g. to solve start-up difficulties by the gen-
erator.
In addition ”ACKNOWLEDGE” removes the lock-out that normally prevents another
generator start for 6 hours after a configurable number of failed start-up attempts
(see chapter 8.6).
The upper lines show behind ”State” and “Fail” whether a generator has been con-
figured (see also chapter 8.6), in which operating phase it currently is and whether
an error has occurred.