10 Troubleshooting
SMA Solar Technology AG
64
SI80H-BE-BEN120810
Operating Manual
Charging the Battery
1. Switch off all loads.
2. Activate or deactivate all miniature circuit-breakers and/or fuse-switch-disconnectors for energy
sources.
3. Quickly connect the switch-disconnector of the BatFuse and close the BatFuse
(see the installation manual of the BatFuse).
4. Start the generator.
5. Switch the off-grid inverter on (see Section 5.1).
6. If the Sunny Remote Control shows
<Init System>
, press and hold the button.
☑ The Sunny Remote Control shows the QCG.
7. Select menu
Emerg Charge
and press the button.
8. Confirm with
Y
.
☑ The Sunny Remote Control shows the
ExtCurMax
parameter.
9. Set the AC current of the connected generator and press the button.
10. Confirm the AC current with
Y
.
11. Turn the button to the right and confirm the message
Emerg. Charg Mode Start?
.
Содержание SUNNY ISLAND 6.0H