12 Parameters
SMA Solar Technology AG
96
SCCP-JP-BA-A4-en-12
User Manual
Q-VArTmsSpnt**
Time setting of the
characteristic curve
point
0.2 s to 20 s
‒
10 s
Q-VArTmsVtg**
Delay of line voltage
0.2 s to 20 s
‒
10 s
Qlimit*
Reactive power of
device
0 kVAr to 500 kVAr
SC 500CP-JP
220 kVAr
0 kVAr to 700 kVAr
SC 630CP-JP
310 kVAr
0 kVAr to 880 kVAr
SC 800CP-JP
385 kVAr
Qmax**
Limitation of the reactive
power of the
Sunny Central
0 kVAr to 220 kVAr
SC 500CP-JP
220 kVAr
0 kVAr to 310 kVAr
SC 630CP-JP
310 kVAr
0 kVAr to 385 kVAr
SC 800CP-JP
385 kVAr
QoDQmax*
Limitation of the reactive
power of the Sunny
Central in the operating
state"Q at Night"
The reactive power
cannot exceed
Qlimit
.
0 kVAr to 500 kVAr
SC 500CP-JP
150 kVAr
0 kVAr to 700 kVAr
SC 630CP-JP
210 kVAr
0 kVAr to 880 kVAr
SC 800CP-JP
264 kVAr
QoDQ-VArMod** Specification of the
mode of reactive power
specification in the
operating state
"Q at Night"
Off
Sets reactive power to
0 kVAr and displacement
power factor cos φ to 1
Off
VArCtlCom
Specification of reactive
power via external control
unit, such as the Power
Reducer Box
VArCnst
Specification of reactive
power in kVAr via the
parameter
QoDQ-VAr
VArCnstNom
Specification of reactive
power in % via the
parameter
QoDQ-VArNom
VArCnstNomAnIn
The reactive power setpoint
is imported via an analog
input.
VArCtlVol
Specification of reactive
power as a function of the
line voltage
VArCtlVolHystDb
Specification of reactive
power as a function of the
line voltage (Q = f(V)
characteristic curve)
VArCtlVolHysDbA
Specification of reactive
power as a function of line
voltage with activation
power
Name
Description
Value/range
Explanation
Default
value
Содержание Sunny Central 500CP-JP