3  Product Description

User Manual

SCCP-JP-BA-A4-en-12

23

3.7.2.2  Remote GFDI

Depending on the order option, ground-fault monitoring in the Sunny Central can be carried out via ground-fault detection 

and interruption with motor drive, in short "Remote GFDI". This grounds one terminal of the PV array. Remote GFDI also 

enables automatic error processing. This reduces downtimes and avoids service calls due to temporary insulation errors 

such as when condensation occurs on the PV modules.
Remote GFDI is performed via a K-type circuit breaker with adjustable operating current. The Remote GFDI is integrated 

in the Sunny Central and connected between an input busbar and the grounding busbar.

Figure 7: Remote GFDI in the Sunny Central

If the Remote GFDI triggers, initially a temporary error will be assumed and a motor drive will close the Remote GFDI 

after a defined delay. No external switch command is required to close the triggered Remote GFDI. The Sunny Central 

will switch back to feed-in operation after a defined delay. 
In the default setting of the Sunny Central, the software will attempt to start the Remote GFDI up to three times per day. 
If the Remote GFDI triggers on several consecutive days, the software will assume that a permanent insulation error has 

occurred, and the Sunny Central will no longer revert to operation. In this case, a qualified person will need to check and, 

if necessary, repair the insulation and then acknowledge the error.

Содержание Sunny Central 500CP-JP

Страница 1: ...SCCP JP BA A4 en 12 98 103200 02 Version 1 2 ENGLISH User Manual SUNNY CENTRAL 500CP JP 630CP JP 800CP JP...

Страница 2: ...cognized even if not explicitly identified as such A lack of identification does not mean that a product or symbol is not trademarked The Bluetooth word mark and logos are registered trademarks owned...

Страница 3: ...onitoring in Grounded PV Arrays 22 3 7 2 1 Ground Fault Detection and Interruption GFDI 22 3 7 2 2 Remote GFDI 23 3 7 2 3 Soft Grounding 24 3 7 3 Insulation Monitoring 25 3 7 3 1 Insulation Monitoring...

Страница 4: ...ance 44 6 5 Configuring the Remote Shutdown 44 6 6 Deactivating the Fully Hermetic Transformer Protection 44 7 Grid Monitoring 45 7 1 How Grid Monitoring Works 45 7 2 Setting Line Voltage Monitoring 4...

Страница 5: ...int 63 8 3 Q at Night 63 8 3 1 Selecting Parameter QoDQ VarMod 63 8 3 2 No Q at Night Off Mode 65 8 3 3 Q at Night with Setpoint Command via Modbus Protocol VArCtlCom Mode 65 8 3 4 Q at Night with Abs...

Страница 6: ...umber 34xx to 40xx Disturbance on PV Array 79 10 4 5 Error Numbers 60xx to 90xx Disturbance on the Sunny Central 81 11 Instantaneous Values 85 11 1 Sunny Central 85 11 1 1 Power Limitation 85 11 1 2 E...

Страница 7: ...ion for SUNNY CENTRAL 500CP JP 630CP JP 800CP JP Technical Information Important Requirements for Medium Voltage Transformers and Transformers for Auxiliary Power Supply for SUNNY CENTRAL Inverters of...

Страница 8: ...m Detect Button Key Button or key to be selected or pressed Select Start detection Complete designation Designation in this document Sunny Central Inverter Sunny Central Communication Controller SC CO...

Страница 9: ...further information in the Technical Information Medium Voltage Transformer Important Requirements for Medium Voltage Transformers and Transformers for Auxiliary Power Supply for SUNNY CENTRAL Invert...

Страница 10: ...Internal power supply DC voltage from the PV array Additional external voltages e g control signals from a control room Ensure that no disconnected components can be reconnected After disconnecting t...

Страница 11: ...erters located opposite each other blocks the escape route It is imperative that the escape route is freely accessible at all times An escape route with a passage width of at least 500 mm must be avai...

Страница 12: ...When working on the Sunny Central and handling assemblies observe all ESD safety regulations Wear suitable personal protective equipment for all work on the device Discharge electrostatic charge by t...

Страница 13: ...proof soles and steel toe caps During precipitation or on moist ground safety boots of category S5 with perforation proof soles and steel toe caps Tight fitting work clothes made of 100 cotton Suitabl...

Страница 14: ...ral The Sunny Central is controlled via the Sunny Central Communication Controller SC COM The grid management service specifications from the grid operator can be implemented via a Power Reducer Box o...

Страница 15: ...rom the touch display Reading off the firmware version You can read off the version number of the Sunny Central and touch display firmware via the user interface You can also read off the version numb...

Страница 16: ...3 Operating Modes The Sunny Central cycles through various states during operation Figure 3 Principle overview of the operating states of the Sunny Central in normal operation Observe the documentatio...

Страница 17: ...lay If the input voltage VPV is higher than the start voltage PvVtgStrLevMin the Sunny Central waits until the time specified in the parameter PvStrT has elapsed If the input voltage VPV does not fall...

Страница 18: ...state Stop If the key switch is turned to Stop while the Sunny Central is in the operating state MPP load operation the Sunny Central switches to the operating state Shutdown Once the shutdown is comp...

Страница 19: ...diagnosis Control network This network is used by the Power Reducer Box or Power Plant Controller to transmit grid management specifications issued by the grid operator to the Sunny Central The use o...

Страница 20: ...the remote shutdown is similar to the stop function of the key switch If the remote shutdown function is activated from the control room while the Sunny Central is in the operating state Grid monitor...

Страница 21: ...When the switch is closed the all or nothing relay is activated and the Sunny Central feeds into the grid If the fast stop is tripped the switch opens and the relay is deactivated The Sunny Central is...

Страница 22: ...sonal hazard due to leakage currents or system failure If the insulation resistance falls below the configured warning threshold the system may be switched off Use the parameter IsoErrIgn to activate...

Страница 23: ...ny Central and connected between an input busbar and the grounding busbar Figure 7 Remote GFDI in the Sunny Central If the Remote GFDI triggers initially a temporary error will be assumed and a motor...

Страница 24: ...idual current will occur through the Soft Grounding resistor The residual current increases the voltage of the grounded terminal against ground potential This enables monitoring of insulation with Sof...

Страница 25: ...sulation monitoring device activates the relay with changeover contact This relay is integrated in the Sunny Central If the insulation resistance falls below the error threshold 1 k an insulation erro...

Страница 26: ...tes one of the errors 3501 Insulation error 3504 Insulation error ignored or 3601 Warning insulation error is displayed the insulation is defective In this case a qualified person will need to check a...

Страница 27: ...h back to feed in operation after a defined delay In the default setting the Sunny Central software will attempt to start the Remote Soft Grounding up to three times per day If the Remote Soft Groundi...

Страница 28: ...rters quickly and reliably for implementation The following figure shows how the specifications of the grid operator are implemented The Power Reducer Box or Power Plant Controller sends the specifica...

Страница 29: ...eive any updated default values it will utilize the specified proxy values for active power limitation reactive power setpoint and displacement power factor In this case different proxy values can be...

Страница 30: ...al after a signal from the grid operator or the safety system for the grid transfer point Ratio VGrid V Behavior of the Sunny Central 90 to 100 The ratio of line voltage VGrid to nominal voltage V is...

Страница 31: ...n Q at Night operation for one hour or the DC current falls below 60 A the DC switchgear opens The inverter continues to feed in reactive power If reactive power feed in is interrupted after a grid fa...

Страница 32: ...of stand alone grids and disconnects the Sunny Central from the utility grid Islanding can occur when at the time of utility grid failure the load in the shut down sub grid is roughly equivalent to t...

Страница 33: ...stantaneous values and parameter settings The functions are activated by tapping on the appropriate symbols on the touch display The touch display is divided into three areas Figure 13 Touch display a...

Страница 34: ...he type of string current monitoring DC currents of the individual Sunny String Monitors This symbol appears once you have selected the symbol Switch on DC or AC side closed If you see this symbol bet...

Страница 35: ...pe of the displacement power factor Actual reactive power in VAr Actual displacement power factor cos Actual excitation type of the displacement power factor Symbol Designation Explanation Language se...

Страница 36: ...his symbol to see the following information OS version of the operating system App version of the application software Language selected language Ser No Serial number of the Sunny Central Error This s...

Страница 37: ...hour format 5 Select the number format 6 Confirm your entry by selecting 4 6 Setting the Brightness 1 Select 2 Select 3 Set the display brightness Select for a darker screen or for a lighter screen 4...

Страница 38: ...rated in the same network the SC COM of each Sunny Central must be assigned a unique network address Figure 15 Example of a plant network with two Sunny Central inverters Procedure Setting the IP addr...

Страница 39: ...1 Subnet mask 255 0 0 0 8 In the Local Area Connection Properties window select OK The settings are now applied 9 Select OK in the Network Connections window This closes the window The computer is now...

Страница 40: ...ter the installer password in the appropriate field on the homepage and confirm with Login 3 Select PV system Devices 4 Select A list of the existing device types appears 5 Select the desired device t...

Страница 41: ...ting Sunny String Monitors via the Sunny Central String Monitor Controller Procedure 1 Select the Parameters tab 2 Set the parameter DevFunc to AutoDetect_SSMU 3 Confirm the entry with Save 4 Select t...

Страница 42: ...10 00 a m to 3 00 p m by default Procedure 1 Select the parameter MoniTmComOn and set the start of the communication period see Section 6 2 page 40 2 Select the parameter MoniTmComOff and set the end...

Страница 43: ...entral String Monitor Controller the PV string data is continuously monitored and the group data compared so that potential errors are detected immediately It is therefore advisable to split the PV st...

Страница 44: ...switched with 24 V see Sunny Central installation manual To use this function the associated parameter must be activated Procedure 1 Ensure that the Sunny Central is in the operating state Stop 2 Log...

Страница 45: ...ing before the Sunny Central disconnects from the utility grid 7 2 Setting Line Voltage Monitoring You can specify the thresholds and tripping time manually For voltage monitoring you can set two limi...

Страница 46: ...level 2 is breached timer for A starts counting 6 Grid limit level 2 is breached for delay time level 2 grid disconnection 7 Grid limit level 1 is breached for delay time level 1 grid disconnection h...

Страница 47: ...e Sunny Central it will only switch back on once the line voltage has met certain conditions The line voltage and the power frequency must remain within the set thresholds for grid connection for the...

Страница 48: ...nny Central has switched off due to grid limit infringement you can prevent an automatic restart of the Sunny Central The Sunny Central will not switch back on until the error has been acknowledged Yo...

Страница 49: ...r indicates the percentage of the saved power Pcur by which the power per Hz will be reduced if the power frequency continues to rise If the power frequency decreases again as shown in point B the las...

Страница 50: ...2 page 40 4 Change any parameters associated with the selected mode Example A 500 kW Sunny Central is feeding 350 kW Pcur into the utility grid The frequency rises to 51 2 Hz The difference between t...

Страница 51: ...If the Sunny Central has not received any signal for five minutes the error message will be displayed in the instantaneous value P WModFailStt 8 1 2 4 Active Power Limitation with Absolute Value WCns...

Страница 52: ...face see Section 6 1 page 40 8 1 4 Displaying Error Messages and Warnings for Active Power Limitation The instantaneous value P WModFailStt displays errors or warnings associated with active power lim...

Страница 53: ...cabling between the Sunny Central and Power Reducer Box or the Power Plant Controller is OK AnInFail The WCnstNomAnIn mode has been selected and the value measured at the analog input is less than 2...

Страница 54: ...helps perform voltage stabilizing measures in the event of overvoltage or undervoltage The parameterization is carried out by means of a reactive power voltage characteristic curve VArCtlVolHysDbA The...

Страница 55: ...VArNom refers to Pmax If the calculated amount of reactive power exceeds the predefined value of Qmax the power will be limited to Qmax If the calculated amount of reactive power falls below the prede...

Страница 56: ...itation 8 2 1 9 Displacement Power Factor cos via Standard Signal PFCnstAnIn Mode The reactive power setpoint is set via an analog signal at the input terminals for setpoint specification see Sunny Ce...

Страница 57: ...e can be configured as rising or falling The start and end points of the characteristic curve can be set via parameters Figure 20 Characteristic curve for reducing reactive power as a function of acti...

Страница 58: ...ic curve for reducing reactive power as a function of the line voltage If the line voltage is changed by the configurable voltage difference Q VDif for the configurable duration of Q VDifTm the reacti...

Страница 59: ...age or undervoltage The parameterization is carried out by means of a reactive power voltage characteristic curve The characteristic curve can be flexibly configured by parameterizing the slope a type...

Страница 60: ...trol SMA Solar Technology AG 60 SCCP JP BA A4 en 12 User Manual Figure 23 Characteristic curve for reducing reactive power with deadband Figure 24 Characteristic curve for reducing reactive power with...

Страница 61: ...t is actively used In order to prevent several systems with this function from interfering with each other the parameter Q VArTmsVtg can be used to set a delay time This delay time defines how long a...

Страница 62: ...r setpoint is actively used In order to prevent mutual interference of several systems with this function the parameter Q VArTmsVtg can be used to set a delay time This delay time defines how long a v...

Страница 63: ...er Box or Power Plant Controller can be accessed via the Internet Ensure that the Sunny Central and the Power Reducer Box or the Power Plant Controller are connected correctly Ensure that the cabling...

Страница 64: ...power setpoint is imported via an analog input The analog value is converted into a reactive power setpoint VArCtlVol The reactive power is set as a function of the line voltage VArCtlVolHystDb The pr...

Страница 65: ...e of QoDQmax the power will be limited to QoDQmax 8 3 6 Q at Night via Standard Signal VArCnstNomAnIn Mode The reactive power setpoint is set via an analog signal at the input terminals for setpoint s...

Страница 66: ...x the characteristic curve will be limited to QoDQmax at the value QQoDmax and the reactive power value will remain constant at QoDQmax in the range from QQoDmax to Pmax If the value of Pmax falls bel...

Страница 67: ...curve for reducing reactive power as a function of the line voltage If the line voltage is changed by the configurable voltage difference Q VDif for the configurable duration of Q VDifTm the reactive...

Страница 68: ...of overvoltage or undervoltage The parameterization is carried out by means of a reactive power voltage characteristic curve The characteristic curve can be flexibly configured by parameterizing the s...

Страница 69: ...echnology AG 8 Power Control User Manual SCCP JP BA A4 en 12 69 Figure 30 Characteristic curve for reducing reactive power with deadband Figure 31 Characteristic curve for reducing reactive power with...

Страница 70: ...t is actively used In order to prevent several systems with this function from interfering with each other the parameter Q VArTmsVtg can be used to set a delay time This delay time defines how long a...

Страница 71: ...setpoint is actively used In order to prevent mutual interference of several systems with this function the parameter Q VArTmsVtg can be used to set a delay time This delay time defines how long a vo...

Страница 72: ...p 2 Wait 15 minutes before opening the Sunny Central This will ensure that the capacitors are discharged 3 Open the Sunny Central 4 Manually switch the GFDI circuit breaker off 5 Close the Sunny Centr...

Страница 73: ...device checks each terminal of the PV array for potential insulation errors Switching to insulated operation is useful for performing maintenance or service work on or near the PV array e g cutting th...

Страница 74: ...r performing maintenance or service work on or near the PV array e g cutting the grass or for checking the status of the insulation at regular intervals 9 3 2 Switching to Insulated Operation 1 Set th...

Страница 75: ...value view 5 To display the corrective measure select the instantaneous value Dsc in the instantaneous value view 10 3 Acknowledging Disturbance Messages Once the error has been remedied you can ackn...

Страница 76: ...isturbance is no longer shown on the touch display The Sunny Central then checks whether the cause of the error has been rectified If the cause of the disturbance still exists after the waiting time h...

Страница 77: ...it is deleted from the fault memory To view previous disturbances after they have been deleted from the fault memory an event report is filed on the SD memory card The event report logs the time and...

Страница 78: ...ervoltage detected by redundant monitoring 30 s 30 s Check line voltage Check grid connections Check stability of the utility grid Make sure the external fuses function properly Make sure the AC cable...

Страница 79: ...ge may have to be acknowledged manually Error no Explanation Behavior of the Sunny Central Corrective measures S 1 S 2 R 3403 Voltage of PV array is too high 15 min 30 min Check DC input voltage Check...

Страница 80: ...oCtlWarn has been reached W W Check grounding and equipotential bonding Check module wiring and PV system design Check the RisoCtlWarn parameter 3803 Current of PV array is too high 1 min D x Check DC...

Страница 81: ...and digital signal processor invalid 5 min 5 min x 6120 Watchdog tripping error 30 s W 6121 No response from watchdog 30 s W 6122 Ten internal monitoring errors have occurred in succession W 5 min 61...

Страница 82: ...7 Capacitor self test failed Q Q 6461 Insulation monitoring device has not adopted threshold 15 min 15 min x Ensure that insulation monitoring device and wiring OK 6501 Internal temperature in Sunny C...

Страница 83: ...l Contact the SMA Service Line 7706 AC circuit breaker has tripped 30 s Q Contact the SMA Service Line 7707 Faulty switching state of AC contactor 30 s Q 7708 Faulty switching state of Remote GFDI W W...

Страница 84: ...e been opened during operation 30 s 1 min x 9009 Fast stop has been manually tripped 30 s 30 s Eliminate error and switch fast stop back on 9013 This is a grid stability shutdown see Section 3 8 7 The...

Страница 85: ...tpoint information Name Display Description P WModStt Off No mode for active power limitation has been selected WMax Active power is limited by specification of an upper limit This limit is relative t...

Страница 86: ...ErrNo Error number ErrNoFirst Error number of the first error Error Localization of error GriSwStt State of AC contactor Mode Operating state of inverter Msg Error message Prio Priority of error mess...

Страница 87: ...f interior fan 1 in h CntFanCab2 Operating hours of interior fan 2 in h CntFanHs These instantaneous values are only visible after entering the installer password Operating hours of heat sink fan in h...

Страница 88: ...ware 6 CRC SvmMode Name Description MeanCurGr1 Mean current for group 1 mean value exists for all 6 groups SSMUWrnCode String failure detection SSMUNoOf Number of Sunny String Monitors found Name Desc...

Страница 89: ...value of string 1 over the last 30 seconds mean value exists for all eight measuring channels Name Description Alarm contact 1 Status of alarm contact 1 Alarm contact 2 Status of alarm contact 2 Netwo...

Страница 90: ...WCnst Manual limitation of active power in kW P W via communication devices such as the SC COM WCnstNom Manual limitation of active power in P WNom via communication devices such as the SC COM WCnstN...

Страница 91: ...mit is defined by the parameter PFAbsMin 0 5 to 1 The parameter should not fall below 0 8 in normal operation 0 9 PF PFExtStr Excitation of the displacement power factor cos at characteristic curve po...

Страница 92: ...to 1 000 kW SC 500CP JP 500 kW SC 630CP JP 700 kW SC 800CP JP 880 kW PF PFSubVal Proxy value for cos outside of normal feed in operation in the event of communication failure 0 5 to 1 The value 0 5 c...

Страница 93: ...on downtime until proxy values are used 1 s to 999 s 300 s Q EnaTmsVtg Activation of line voltage delay in the parameter Q VarTmsVtg Off Off On Q VLockInW Voltage value from which the Q V characterist...

Страница 94: ...power factor via an external control unit such as the Power Reducer Box VArCnst Specification of reactive power in kVAr via the parameter Q VAr VArCnstNom Specification of reactive power in via the pa...

Страница 95: ...0CP JP 385 kVAr to 385 kVAr SC 800CP JP Q VDif Definition of voltage change leading to a change in reactive power 0 1 to 10 The value refers to the nominal voltage VRtg 1 Q VArGra Definition of the re...

Страница 96: ...to 700 kVAr SC 630CP JP 210 kVAr 0 kVAr to 880 kVAr SC 800CP JP 264 kVAr QoDQ VArMod Specification of the mode of reactive power specification in the operating state Q at Night Off Sets reactive powe...

Страница 97: ...perating state Q at Night 0 s to 86 400 s 3 600 s SDLimComSrc Selection of the SDELimit source CAN SC COM interface UART UART Via SMA Net WCtlHzMod Activation of frequency dependent active power limit...

Страница 98: ...s 600 ms HzCtlhLim Threshold for overfrequency level 1 50 Hz to 55 Hz For 50 Hz grid 51 Hz 60 Hz to 66 Hz For 60 Hz grid 61 2 Hz HzCtlhLimTm Tripping time for overfrequency level 1 0 ms to 1 000 000 m...

Страница 99: ...120 to 150 134 VCtlPeakMaxTm Tripping time for overvoltage 0 ms to 20 ms 1 ms VCtlOpMinNom Minimum connection voltage 0 to 100 90 VCtlOpMaxNom Maximum connection voltage 100 to 200 110 VRtg Nominal li...

Страница 100: ...d 100 to 0 10 FRTEna To view or change this parameter you must enter the installer password Enables dynamic grid support Off Deactivated On On Activated FRTMod You can only view this parameter after e...

Страница 101: ...ge of insulation measurement 0 V to 1 200 V SC 500CP JP 410 V SC 630CP JP 610 V SC 800CP JP 760 V PvVtgRisoDif Differential voltage to PvVtgStrLevMin for switching from insulation measurement to feed...

Страница 102: ...C 0 5 to 1 0 8 Ofs_h On Offset for operating hours 0 h to 2 147 482 h 0 Ofs_h Total Offset for feed in hours 0 h to 2 147 482 h 0 Ofs_E Total Offset for total supplied energy 0 kWh to 214 748 367 kWh...

Страница 103: ...iewed To change this parameter you must enter the installer password Name Description Value range Explanation Default value Serial number Display of serial number Value cannot be changed Firmware Firm...

Страница 104: ...32 Insensitive 35 min 16 64 Sensitive 15 min 7 64 Regular 15 min 9 64 Insensitive 15 min 10 ComBaud Baud rate 1 200 Bd Parameter can only be changed in the operating state Stop 19 200 Bd 4 800 Bd 9 6...

Страница 105: ...nnected strings in the respective group 1 to 4 Parameter exists for all eight groups Contact the SMA Service Line if you wish to use this function No of Strings All groups 1 to 4 Monitoring1 On Start...

Страница 106: ...nitor Active high Contact activated when voltage present 0 Active low Contact activated when no voltage present Deactivated Contact deactivated Surge arrester2 Alarm contact Active high Contact activa...

Страница 107: ...ou have technical problems concerning our products contact the SMA Service Line We require the following information in order to provide you with the necessary assistance Device type Serial number Typ...

Страница 108: ...www SMA Solar com SMA Solar Technology...

Отзывы: