11 Troubleshooting
SMA Solar Technology AG
Operating manual
SBS25-1VL-10-BE-en-13
94
Event number
Message, cause and corrective measures
10340
Webconnect disabled
The Webconnect function has been switched off. This means that the inverter
can not communicate with Sunny Portal without an additional SMA communi-
cations product (e.g. Sunny Home Manager).
• If the inverter is to communicate with Sunny Portal without an additional
SMA communication product, switch the Webconnect function on.
10420
Internal consumption control was started
The battery is automatically charged or discharged depending on the pur-
chased electricity or the grid feed-in.
10421
Internal consumption control was stopped
The automatic charging or discharging of the battery stopped due to an exter-
nal control command.
10422
Only charging operation in internal consumption mode
The battery is charged only when increased self-consumption is active. The
battery is only charged again once there is sufficient PV power in the system.
10425
The device switches off
The battery is switched off in order to protect against deep discharge. The in-
verter can only be recommissioned once it has been disconnected from the
utility grid.
10517
Dynamic active power limitation started.
The inverter limits the active power of the PV inverters to the set limit.
10518
Dynamic active power limitation terminated.
The inverter terminated the active power limitation of the PV inverters.
10520
Supplied power: [xx] W (permitted value: [xx] W)
The set active power limitation cannot be met.
Corrective measures:
• Ensure that the correct active power limitation has been configured.
• Ensure that the PV inverters have been configured correctly.
• Ensure that the communication between battery inverter and PV inverter
functions perfectly.
• Ensure that no external feeders are in the system.
10521
Active power was limited today for [xx] minutes.
The active power limitation of the PV inverters was limited for the specified
time.
27103
Set parameter
The parameter change has been adopted.