Sunny Boy 2000
Technical Description
SB2000-11:EE
- 64 -
SMA Regelsysteme GmbH
MPP-Such
PV setpoint voltage is determined and set
MPP
Sunny Boy is in MPP mode
U-Konst.
Sunny Boy is in constant voltage mode
Stoer.
failure
Error messages
Bfr-Srr
communication between microcontrollers is failing
EEPROM
EEPROM cannot be read or written in
Fac-Bfr
BFR-frequency measurement - value out of tolerable range
Fac-Srr
SSR-frequency measurement - value out of tolerable range
Dl
BFR-sudden change of differential current,
value out of tolerable range (30 mA/s)
dl-Srr
SRR-sudden change of differential current leap,
value out of tolerable range (30 mA/s)
dl-Mess
Acquisition of differential or fault current defective
dZac-Bfr
BFR-sudden change of impedance - value out of tolerable range
dZac-Srr
SSR-sudden change of impedance - value out of tolerable range
Imax
internal
overcurrent
K1-Schliess
Relay K1 does not close correctly
K1-Trenn
Relay K1 does not separate correctly
K2-Trenn
Relay K2 does not separate correctly
NUW-UAC
different values between BFR and SRR for grid voltage
NUW-dl
different values between BFR and SRR for differential current
NUW-FAC
different values between BFR and SRR for grid frequency
NUW-Mess
different values between BFR and SRR for dI, Fac, Uac or Zac
NUW-REL
Relay test failed
NUW-ZAC
different values between BFR and SRR for grid impedance
Offset
Offset check for grid voltage measurement failed
Rechner
BFR or SSR controller failure
Riso
isolation resistance out of tolerable range
Uac-Bfr
BFR-grid voltage measurement - value out of tolerable range
Uac-Srr
SSR-grid voltage measurement - value out of tolerable range
UpvMax
PV input voltage above the tolerable maximum value
Uzwk
Internal voltage out of tolerable range
Zac-Bfr
BFR-grid impedance measurement - value out of tolerable range
Zac-Srr
SSR-grid impedance measurement - value out of tolerable range
Watchdog
Watchdog for operation control triggered