Technical Data
SMA Solar Technology AG
58
SB16_21TL-IA-IEN112351
Installation Guide
11 Technical Data
11.1 Sunny Boy 1600TL
DC Input
* The maximum open-circuit voltage, which can occur at a cell temperature of − 10 °C, must not exceed the maximum input
voltage.
AC Output
Maximum DC power at cos φ = 1
1 700 W
Maximum input voltage*
600 V
MPP voltage range
155 V … 480 V
Rated input voltage
400 V
Minimum input voltage
125 V
Start input voltage
150 V
Maximum input current
11 A
Maximum input current per string
11 A
Number of independent MPP inputs
1
Strings per MPP input
1
Rated power at 230 V, 50 Hz
1 600 W
Maximum AC apparent power
1 600 VA
Rated grid voltage
230 V
AC nominal voltage
220 V/230 V/240 V
AC voltage range
180 V … 260 V
Nominal AC current at 220 V
7.3 A
AC nominal current at 230 V
7.0 A
AC nominal current at 240 V
6.7 A
Maximum output current
8.9 A
Harmonic distortion of output current at
AC THD voltage < 2 %,
AC power > 0.5 rated power
≤ 3 %
Rated grid frequency
50 Hz
AC grid frequency
50 Hz
Operating range at AC grid frequency 50 Hz
45.5 Hz … 54.5 Hz
Power factor at rated power
1
Feed-in phases
1
Connection phases
1
Overvoltage category according to IEC 60664-1
III