SMA Solar Technology AG
Electrical Connection
Technical Description
SL6000-TEN081820
19
5.3 Connecting the Resistor
Cabling notes
The load resistor should be connected using a cable with the following properties:
•
Shielded
•
Cable length: maximum 20 m
•
Cross section: at least 1.5 mm
2
Load resistor
•
The resistance value must be between 19
Ω
and 26
Ω
.
•
The load resistor must be suitable for 230 V DC voltage.
•
Only use resistors that are suitable for pulsed DC voltages.
Load resistors with a power consumption of 6 kW can be purchased from SMA.
If...
Then...
Three-phase operation...
•
Connect 3 load resistors with a power consumption of 2
kW, see "Connection procedure for three load resistors"
(Page 20).
Single-phase operation...
•
Connect 1 load resistor with a power consumption of 6 kW,
see "Connection procedure for one load resistor" (Page
21).
or
•
Connect 3 load resistors with a power consumption of 2
kW, see "Connection procedure for three load resistors"
(Page 20).
Exceeding the resistance value
If the resistance value of 26
Ω
is exceeded, achieving the nominal power of the
Smart Load can no longer be ensured.
NOTICE!
An incorrect resistance value will irreparably damage the Smart Load.
•
Ensure that the resistance value is never below 19
Ω
.