Accessories for stand-alone gird inverter
SMART LOAD
6000
Technical Description
SL6000-TEN081820 | 98-2001320 | Version 2.0
EN
Страница 1: ...Accessories for stand alone gird inverter SMART LOAD 6000 Technical Description SL6000 TEN081820 98 2001320 Version 2 0 EN...
Страница 2: ......
Страница 3: ...Packing List 9 3 2 Checking for Transport Damage 10 3 3 Identification of the Smart Load 10 4 Mounting 11 4 1 Dimensions and Weight 11 4 2 Selecting the Mounting Location 11 4 2 1 Ambient Conditions 1...
Страница 4: ...he Grid Frequency 28 7 Commissioning 29 8 Opening and Closing 30 8 1 Opening the Smart Load 30 8 2 Closing the Smart Load 30 9 Maintenance and Cleaning 31 9 1 Cleaning the Cooling Fins 31 10 Parameter...
Страница 5: ...he Smart Load 1 1 Validity This manual applies to firmware version FwVer 2 03 and higher You can access the firmware version of the Smart Load 6000 SL 6000 using a communication connection 1 2 Target...
Страница 6: ...ot avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous sit...
Страница 7: ...r of 6 kW The single or three phase AC input voltage is 230 V or 3 x 230 V One load resistor with a power consumption of 6 kW or 3 load resistors with a power consumption of 2 kW can be connected to t...
Страница 8: ...on 2 2 General Safety Instructions DANGER Danger to life due to high voltages in the Smart Load All work on the Smart Load must be carried out by a qualified electrician CAUTION Danger of burn injurie...
Страница 9: ...cking List Object Number Description A 1 Smart Load B 1 wall mounting bracket C 1 technical Description D 1 EC Declaration of Conformity E 1 silicone tube F 3 large bridging strips for AC and resistor...
Страница 10: ...ed in the delivery Carefully check the packaging and the Smart Load for any signs of damage If something is missing or the Smart Load has been damaged during transport contact your dealer immediately...
Страница 11: ...Despite careful construction a fire can occur with electrical devices Do not install the Smart Load on flammable construction materials in areas where highly flammable materials are stored in potentia...
Страница 12: ...Smart Load Mount the device on solid surfaces only 4 2 2 Safety Clearances When mounting the Smart Load make sure to observe the following safety clearances to ensure sufficient heat dissipation st D...
Страница 13: ...ver install the device with a forward tilt Do not install horizontally 4 3 Mounting the Smart Load 1 Use the wall mounting bracket as a drilling template and mark the position of the drill holes 2 Use...
Страница 14: ...SL6000 TEN081820 Technical Description 4 Tighten the Smart Load using the provided M6 screw on the underside of the housing The screw secures the Smart Load against being raised 5 Ensure that the Sma...
Страница 15: ...the Connection Area NOTICE Electrostatic discharges can damage the Smart Load Ground yourself before touching a component inside the Smart Load Touching the inside of the Smart Load s housing Object D...
Страница 16: ...interface port J floating input for operation display K jumper slot for switching the grid frequency L connection terminal for resistor M connection terminal for resistor N PE connection terminal for...
Страница 17: ...AC cable 3 Thread the AC cable through the cable screw connection and connect PE to the PE connection terminal 4 Tighten the lock nut on the cable screw connection DANGER Danger to life caused by volt...
Страница 18: ...MA Solar Technology AG 18 SL6000 TEN081820 Technical Description DANGER Danger to life due to high voltages in the Smart Load Only start the stand alone grid system after all work has been completed A...
Страница 19: ...kW can be purchased from SMA If Then Three phase operation Connect 3 load resistors with a power consumption of 2 kW see Connection procedure for three load resistors Page 20 Single phase operation Co...
Страница 20: ...or by connecting it to the PE connection terminal 5 Connect the first load resistor to X51 and X61 Connect the second load resistor to X52 and X62 Connect the third load resistor to X53 and X63 6 Tigh...
Страница 21: ...necting it to the PE connection terminal 6 Connect the cables to X52 and X62 7 Bridge the X51 X52 and X53 terminals using the bridging strip provided large bridging strip 8 Bridge the X61 X62 and X63...
Страница 22: ...inal B1 7 Ground the communication cable with the PC connection C1 8 9 Note down the conductor color coding for the respective pin numbers Pin 2 color ______________________ Pin 3 color ______________...
Страница 23: ...gy AG ElectricalConnection Technical Description SL6000 TEN081820 23 DANGER Danger to life due to high voltages in the Smart Load Only start the stand alone grid system after all work has been complet...
Страница 24: ...ew fitting A and slide it over the cable of the load 2 Remove the dummy plug from the cable screw connection 3 Pull the cable of the load through the cable screw connection into the inside of the Smar...
Страница 25: ...oad 2 Remove the dummy plug from the cable screw connection 3 Thread the contact cable through the cable screw connection and connect the cables to the connection terminal X80 B 4 Tighten the lock nut...
Страница 26: ...l of the power to be regulated using an external DC source The control range is 1 V 9 V 1 V 0 power output 9 V 100 power output Connection Procedure 1 Reconnect jumper A from 200 V slot to 150 V slot...
Страница 27: ...plug from the cable screw connection 4 Thread the cable of the voltage source through the cable screw connection and connect the cables to the connection terminal X90 C Ensure the polarity of the cabl...
Страница 28: ...20 Technical Description 6 Switching the Grid Frequency In order to operate the Smart Load in Sunny Island systems with a 60 Hz grid the jumper must be disconnected from jumper slot ENS 2 and be conne...
Страница 29: ...mounting bracket Correct connection of the AC cable grid Connection of DC cable load resistor any additional connections is complete All housing openings are sealed All screw fittings are tight The li...
Страница 30: ...lid 6 Remove the lid and set it aside 8 2 Closing the Smart Load 1 Establish the PE connection to the lid 2 Fasten the lid to the housing using four screws 3 Commission the Smart Load as described in...
Страница 31: ...echnical Description SL6000 TEN081820 31 9 Maintenance and Cleaning 9 1 Cleaning the Cooling Fins It is only necessary to clean the cooling fins if the Smart Load s heat dissipation is restricted by d...
Страница 32: ...50 290 180 volt minimum effective input voltage value 7 MaxACVtg 150 290 270 volt Maximum effective input voltage value Frequency power curve 10 ChrPwrPosLo 0 10000 0 watt P f defined curve P at point...
Страница 33: ...een activation and deactivation of the operating message 21 dFreqNg 1 5 5 hertz The measured frequency may only be a maximum of delta below the nominal frequency 50 60 Hz 22 dFreqPs 1 5 5 hertz The me...
Страница 34: ...rPosLoHi Vtg 0 10000 6000 watt P U analog curve P at point 1 28 ChrVtgPosLo 5 100 10 volt a P U analog curve U at point 0 29 ChrVtgPosHi 5 100 90 volta P U analog curve U at point 1 30 FrqFilCnst 7 15...
Страница 35: ...s illuminated initialization is illuminated ready for operation no power output flashes operating power output is illuminated device fault Contact SMA Technical Service Line see section 14 Contact Pag...
Страница 36: ...Smart Load using four screws 7 Remove the Smart Load 12 2 Packaging If possible pack the Smart Load in the original packaging If this is no longer available you can also use an equivalent box that fu...
Страница 37: ...Input voltage range 3 x 180 270 V DC output Output voltage 3 x 0 230 V Output power 3 x 0 2 kW Connections for 3 resistors with a power consumption of 2 kW or 1 resistor with a power consumption of 6...
Страница 38: ...the SMA Technical Service Line We require the following information in order to provide you with the necessary assistance Serial number of the Smart Load Number of additional Smart Loads Communication...
Страница 39: ...nd instructions contained in all documents relevant to the product Operating the product under incorrect safety or protection conditions Altering the product or supplied software without authority The...
Страница 40: ...SMA Solar Technology AG Sonnenallee 1 34266 Niestetal Germany Tel 49 561 9522 4000 Fax 49 561 9522 4040 E Mail Vertrieb SMA de Freecall 0800 SUNNYBOY Freecall 0800 78669269 www SMA de...