11 Troubleshooting
SMA Solar Technology AG
Operating manual
SBxx-1AV-41-BE-en-12
80
Event number
Message, cause and corrective measures
3701
Resid.curr.too.high > Check generator
The inverter has detected a residual current due to temporary grounding of the
PV array.
Corrective measures:
• Check the PV system for ground faults.
3801
3802
DC overcurrent > Check generator
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:
• If this message is displayed frequently, ensure that the PV array has been
correctly rated and wired.
3901
3902
Waiting for DC start conditions > Start cond. not met
The feed-in conditions for the utility grid are not yet fulfilled.
Corrective measures:
• Ensure that the PV array is not covered by snow or otherwise shaded.
• Wait for higher irradiation.
• If this message is displayed frequently in the morning, increase the
voltage limit for starting grid feed-in. Change the parameter
Critical
voltage to start feed-in
.
• If this message is displayed frequently with medium irradiation, ensure
that the PV array is correctly rated.
4011
Bridged strings detected
The DC inputs A and B are connected in parallel.
4012
No bridged strings detected
The DC inputs A and B are not connected in parallel.
6001-6412
Self diagnosis > Interference device
The cause must be determined by the Service.
Corrective measures:
• Contact the service.