13 Technical Data
SMA Solar Technology AG
Operating manual
SBxx-1AV-41-BE-en-12
101
AC Output
SB3.0-1AV-41
SB3.6-1AV-41
SB4.0-1AV-41
Rated power at 230 V,
50 Hz
3000 W
3680 W
4000 W
Maximum apparent
AC power at cos φ = 1
3000 VA
3680 VA
4000 VA
Rated grid voltage
230 V
230 V
230 V
Nominal AC voltage
220 V / 230 V / 240
V
220 V / 230 V / 240
V
220 V / 230 V / 240
V
AC voltage range*
180 V to 280 V
180 V to 280 V
180 V to 280 V
Nominal AC current at
220 V
13.7 A
16 A
18.2 A
Nominal AC current at
230 V
13.1 A
16 A
17.4 A
Nominal AC current at
240 V
12.5 A
15.4 A
16.7 A
Maximum output cur-
rent
13.7 A
16 A
18.2 A
Total harmonic distor-
tion of the output cur-
rent with total harmonic
distortion of the AC
voltage <2%, and AC
power >50% of the
rated power
≤3 %
≤3 %
≤3 %
Maximum output cur-
rent under fault condi-
tions
29 A
29 A
29 A
Inrush current
< 20% of the nominal
AC current for a
maximum of 10 ms
< 20% of the nominal
AC current for a
maximum of 10 ms
< 20% of the nominal
AC current for a
maximum of 10 ms
Rated power frequency
50 Hz
50 Hz
50 Hz
AC power frequency*
50 Hz / 60 Hz
50 Hz / 60 Hz
50 Hz / 60 Hz
Operating range at AC
power frequency
50 Hz
45 Hz to 55 Hz
45 Hz to 55 Hz
45 Hz to 55 Hz
Operating range at AC
power frequency
60 Hz
55 Hz to 65 Hz
55 Hz to 65 Hz
55 Hz to 65 Hz