Ambient conditions for stationary application
Class 4S2
Class 4S4
c) Dust (deposited) [mg/m
2
h]
20
80
Installation sites in sparsely populated areas, not close to sand
sources.
x
x
Installation sites in areas with sand- or dust sources, including densely
populated areas
x
x
Installation sites where sand- or dust generating processes exist, or in-
stallation sites located in geographic areas in which the wind nor-
mally bears sand or dust.
‒
x
Installation sites where the air can regularly contain high levels of
sand or dust - either due to geographical or process-related circum-
stances.
‒
x
The air quality must comply with the following classification of air quality for chemically active substances:
Ambient conditions for stationary appli-
cation
Class 4C1
Class 4C2
Mean value
Threshold value
Threshold value
a) Sea salt
‒
Occurrence of salt spray
b) Sulfur dioxide [mg/m
3
]
0.1
0.3
1.0
c) Hydrogen sulfide [mg/m
3
]
0.01
0.1
0.5
d) Chlorine [mg/m
3
]
0.1
0.1
0.3
e) Hydrogen chloride [mg/m
3
]
0.1
0.1
0.5
f) Hydrogen fluoride [mg/m
3
]
0.003
0.01
0.03
g) Ammonia [mg/m
3
]
0.03
1.0
3.0
h) Ozone [mg/m
3
]
0.01
0.05
0.1
i) Nitrogen oxides [mg/m
3
]
0.1
0.5
1.0
Installation sites in rural or densely populated
areas with little industry and moderate traffic
volume
x
x
Installation sites in densely populated areas
with industry and high traffic volume
‒
x
4.3
Installation
4.3.1
Design of the System with MV Power Station
Closed electrical operating area
For safety reasons, the system with the MV Power Station must be installed in a closed electrical operating area in
accordance with IEC 61936-1.
• Ensure that unauthorized persons have no access to the MV Power Station.
• Only appropriately trained and qualified persons may operate inverters and perform MV switchgear
switching operations.
4 Information for Installation
SMA Solar Technology AG
Transportation and Installation Requirements
21
MVPS22JP-TA-en-20
Содержание MEDIUM VOLTAGE POWER STATION 1000-1SC-JP
Страница 38: ...www SMA Solar com...