Insert the smaller end of the black plastic water deflector into the threaded end of the elbow fitting. The flat end of the 
elbow fitting will face outward from the vacuum breaker.

Place several drops of thread sealant on the threads of the elbow fitting. Insert the elbow fitting and water deflector into 
the threaded hole of the vacuum breaker tube. Screw the fitting into place. DO NOT overtighten this connection. The 
final position of the elbow should allow water flow from the vacuum breaker in a downward direction.

Figure 1

Figure 2

Figure 3

Slide the spud coupling, nylon slip gasket,  
rubber gasket and spud flange (all supplied with 
a standard flushometer vacuum breaker) over the 
vacuum breaker tube and insert the tube into the 
fixture spud. Tighten the spud coupling onto the 
fixture spud by hand.

VACUUM BREAKER 

OUTLET TUBE

WATER DEFLECTOR

¼” I.P.S.

ELBOW FITTING

INSTALL 

FITTING 

IN THIS 

RANGE

90°

1½” 

(38 mm)

WATER 

DEFLECTOR

CENTERLINE 

OF TRAP 

PRIMER

WATER 

FLOW

VACUUM BREAKER 

OUTLET TUBE

ELBOW FITTING

WALL FLANGE

½” (13 mm) NPT MALE PIPE 

FOR TRAP PRIMER OUTLET

½” (13 mm) NPT 

FEMALE TUBE FITTING

1” 

(25 mm)

TO 

TRAP

FINISHED WALL

VACUUM 

BREAKER TUBE

RUBBER 

GASKET

SPUD 

FLANGE

SPUD 

COUPLING

NYLON SLIP 

GASKET

1 - INSTALL WATER DEFLECTOR AND ELBOW (FIG. 1)

2 - INSTALL WALL FLANGE (FIG. 2)

3 - INSTALL VACUUM BREAKER FLUSH CONNECTION 
      (FIG. 3)

Place wall flange over the ½” (13 mm) NPT male pipe used as the trap primer outlet. Push wall flange until it is flush 
against the wall. Connect the ½” (13 mm) NPT female tube fitting to the pipe. The fitting will help keep the wall flange 
in position.