20
6
Maintenance
In order to ensure maximal and durable service, we strongly recommend that your product be maintained
clean and ensure that it is installed in a dry and ventilated location. We shall in no case be liable for damages
associated with improper use or incorrect maintenance of the equipment.
7
Fuse protections
28V 8A
56V 4A
F1 (mains): rating - type
Size - breaking capacity
6,3A T
5x20 - 1500A
F7, F8 (load):
rating - type - size
8A F
5x20
4A F
5x20
FBat (battery):
rating - type - size
10A F
5x20
8A F
5x20
8
Troubleshooting procedure
If the AES does not deliver voltage
•
Check mains presence on the mains terminal strip
•
Check the fuses
•
Check the voltage value on terminals load1 and/or load2
=
floating voltage (see 1.2.2)
•
The voltage on the battery cables must be identical to that of the load
•
Check that each 12 Vdc battery has a voltage greater than or equal to 11.5 Vdc
•
Repeat the measurement after having disconnected the load and the battery
•
Recheck the signalling of the indicator lights (see chapter 5, AES Operation)
•
If all the steps are validated, check the compatibility of your load
If the battery does not take over after a mains fault
•
Check the voltage on the battery terminals
•
Check the battery fuse
•
Check the voltage on terminals load1 and/or load2
If the indicator lights are not illuminated
•
Check mains presence on the mains terminal strip
•
Check the battery connection (and the battery fuse)
•
Check that the wire ribbon is properly connected
•
Check the voltage on terminals load1 and/or load2
For additional technical assistance, contact the SLAT hotline
+ 33 (0) 4 78 66 63 70
For return requests, visit our website
http://www.slat.com/en/services/assistance/maintenance-and-product-returns/#formulaire
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorisation) number.
Returns are not accepted without an RMA number.