background image

V

ICTORY

BURNERS FAIL TO OPERATE
CAUSE

REMEDY

1. Gas supply valve shut off

1. Open gas valve

2. No power, main electric switch open

2. Close switch

3. No power, blown or defective line fuse

3. Replace fuse

4. Pilot flame too low

4. Adjust pilot flame

5. Ignition system control switch is on “OFF” position

5. Move switch to “ON” position

6. Harnesses plug-in connectors are not

6. Check connectors

securely connected

7. HSI element damaged or broken (does not glow red)

7. Replace element

8. Flame sensor contaminated

8. Clean sensor

9. Roll-out switch open

9. Replace roll-out switch (inspect flue passages prior to 

replacement) 

10. Defective air flow switch, restriction or obstruction in 

10. Check air flow switch hose connections. Check for obstruc tion

venting system (motor run for 30 seconds)

or restriction in venting system. Replace defective switch.

11. Defective blower motor

11. Check voltage (120V) at motor connector. Replace 

defective motor.

12. Defective transformer

12. Remove connector marked C, R on Aquastat. Check 

transformer connector terminals for 24V. Replace
defective transformer.

13. Defective Smart Valve

13. Set thermostat and Aquastat to call heat. Remove connector

marked B2, B1, R on Aquastat. Check terminal B2, B1 for 24V. 
Follow Smart Valve system troubleshooting in Smart Valve 
(Honeywell) Instruction Manual to find out if Smar t Valve must 
be replaced.

14. Defective electronic Aquastat

14. Set thermostat and Aquastat to call heat. Remove connector 

marked B2, B1, R. Check voltage at B1, B2 (24V nominal). 
Remove thermostat connections from T or TV terminal.  No 
voltage between B1 and B2. If Aquastat fails above tests, 
replace Aquastat.

BURNERS WILL NOT SHUT-OFF
CAUSE

REMEDY

1. Defective Aquastat

1. Test Aquastat as 14 on page 25, replace def ective Aquastat.

2. Aquastat sensor is not properly inside Aquastat well.

2. Insert the senser into the well. Make sure the sensor fits 

securely against the bottom of the well. Secure sensor and
lead wire with mounting clamp.

FLASH BACK-BURNING AT ORIFICES
CAUSE

REMEDY

1. Manifold gas pressure too low

1. Adjust to proper manifold pressure

2. Improper primary air adjustment

2. Adjust air to produce soft, clean flame

3. Gas regulator bleed too slow

3. Adjust bleed opening

4. Burrs on orifices

4. Remove burrs

5. Improper orifice

5. Install proper orifice size

6. Adverse draft condition in boiler room

6. Check air supply and venting system

7. Low main gas pressure

7. Contact utility

General Troubleshooting Guide For Servicepeople

25

Содержание victory II VH series

Страница 1: ...is boiler is under positive pres sure when it is connected to the outdoors with 3 diameter pipe Leakage from this system can be hazardous and if not avoided can result in death or ser ious injury In a...

Страница 2: ...0 3000 4000 5000 6000 7000 8000 9000 10000 Orifice Size for Sea Level Orifice Sizes for High Altitudes Includes 4 Reduction for Each 1000 Feet Elevation Feet Orifice sizes indicated for sea level abov...

Страница 3: ...fueled shall not be installed in an abo ve grade under floor space or basement unless such loca tion is provided with an approved means for removal of unburned gas Consult Chapter 5 of the 1994 UNIFOR...

Страница 4: ...ith a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances input IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT THE AREA OF FREE OPENINGS MUST BE APPROPR...

Страница 5: ...ght run would be 20 2 x 3 14 ft 3 Installation A Horizontal Venting Figures 5 and 6 show typical horizontal venting For combustible wall passage of vent piping a U L listed thimble must be used See Fi...

Страница 6: ...ltitudes 5500 to 7000 Ft Altitudes 7000 to 10 000 Ft Altitudes Equivalent Length of each 90 Elbow Ft Max Equivalent Length Ft VH 30 30 30 30 6 2 60 90 and 120 VH 150 30 30 15 6 2 VH 180 30 15 15 6 2 F...

Страница 7: ...VICTORY II 7 Figure 6 Figure 5 VICTORY II HORIZONTAL VENTING All joints must be liquid and pressure tight Use U L listed single wall 3 dia AL29 4C S S venting materials See page 5...

Страница 8: ...VICTORY 8 Figure 7...

Страница 9: ...VICTORY Figure 8 9...

Страница 10: ...lined masonry chimney If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exposed chimney it must be re lined with a UL listed metallic liner system See Table 2 in...

Страница 11: ...height and connector 11 9 VH 180 length restrictions 2 Connector may have to be upsized to 6 diameter to meet requirement of 11 9 Additional National Fuel Gas Code Boiler Gas Appliance Reference Tabl...

Страница 12: ...VICTORY 12 Figure 9...

Страница 13: ...VICTORY Figure 10 13...

Страница 14: ...ional Fuel Gas Code ANSI Z223 1 latest edition C The boiler and its gas connection must be leak tested before placing the boiler in operation Use liquid soap solution for all gas leak testing DO NOT u...

Страница 15: ...g arrangement 1 Supply and Return For tapping sizes see dimensions on page 2 Shut off valves are recommended 2 Circulating Systems Victory II boilers are equipped with a water circulating pump mounted...

Страница 16: ...VICTORY 16...

Страница 17: ...VICTORY Figure 14 Figure 15 Piping Arrangement 17...

Страница 18: ...quipment PIPING A HEATING COOLING SYSTEM TO A WATER BOILER AND CHILLER Figure 16 illustrates a method of piping a heating cooling sys tem to a water boiler and a chiller Hand valves shown or automatic...

Страница 19: ...sired setting 10 If appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service or gas supplier To Turn Off Gas to Appliance 1 Set thermostat to lowest settin...

Страница 20: ...op of main burner tube C Main Burner Ignition Checkout and Pilot Adjustment 1 The pilot flame must not smother or snuff out when tested as follows a Main burner ignition from cold start repeat b Conti...

Страница 21: ...m meter to burner including gas valve gas piping manifold and pilot burner DO NOT use open flame CARE AND MAINTENANCE This section must be brought to the attention of the o wner by the installer so th...

Страница 22: ...ers are not firing 3 Annual Inspection and Cleaning The following must be done by a competent serviceperson to help insure safe and reliable operation A Flue passage cleaning See Figure 23 It is sugge...

Страница 23: ...LVE OPENS IGNITOR OFF BOILER HEATING PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN NO NO NO PILOT AND MAIN VALVE CLOSE NO YES YES YES YES YES NO NO Victory II Boiler Sequence of Operations BOILER WATER T...

Страница 24: ...2 High limit of electronic Aquastat open nor mal condition 3 No power 4 Defective Aquastat 5 Defective transformer 6 Harnesses plug in connector is not securely connected at both ends 7 Damaged harne...

Страница 25: ...at to call heat Remove connector marked B2 B1 R on Aquastat Check terminal B2 B1 for 24V Follow Smart Valve system troubleshooting in Smart Valve Honeywell Instruction Manual to find out if Smart Valv...

Страница 26: ...nting system 4 Condensation trap is not full of water 4 Check and fill with water 5 Venting system is physically damaged 5 Check carefully and repair Also see Venting System Regular Inspection 6 Over...

Страница 27: ...Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe conditi...

Страница 28: ...VICTORY SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com...

Отзывы: