background image

V

ICTORY

22

3. Perform “Venting System Regular Inspection” on

Page 14.

C. Piping

Check the following:
1. Water piping and accessories for leaks. Slightest

leaks should be corrected.

2. System to be full of water and pressure to remain

stable at correct setting on gauge.

3. Air-control system. Noise and air binding in r adia-

tion should not occur.

4. Low water cutoff for operation (see instructions fur-

nished with unit).

D. Boiler Room Air Supply

Check air vents for continued positive supply of air as
required. Air needs are greatest in cold weather. Air
vents must be open and free of obstr uction.

WARNING: The flow of combustion and ventilating air to
the boiler should not be obstructed.

2. Inspection During Heating Season

A.  Check water pressure regularly and add water slowly

to system when needed. If much water is added, vent-
ing may be necessary. Regular loss of water from boil-
er system may indicate either a system leak, or a
faulty air control system, or a faulty automatic fill valve.

B. Check venting system. See “Venting System Regular

Inspection” on Page 14.

C. Check condensation drain trap to be full of water.

Check for deterioration of the tubing. Check that the
trap is not plugged.

D. With main burners firing, the diagnostic indicator light

status must be “bright-dim” indicating normal opera-
tion, it is “off” when main burners are not firing.

3. Annual Inspection and Cleaning

The following must be done by a competent serviceperson
to help insure safe and reliable operation:
A. Flue passage cleaning

See Figure 23. It is suggested that paper be placed on
burners to collect any foreign material in cleaning
flues.
1. Remove control box (see instruction under “Safety

Check”. See Figure 20).

2. Remove jacket top.
3. Remove inducer assembly.
4. Remove flue collector.
5. Use wire brush to clean flue passages.
6. Replace flue collector and re-seal with fur nace

cement.

7. Replace inducer assembly, jacket top and control

box.

8. Remove and dispose of paper and accum ulated

material.

B. Cleaning of burners

If burners surfaces are not clean, or uneven flame
indicates plugged burner parts, remove and clean
burners.
1. Disconnect sensor and ignitor wires by removing

plug-in wires from C2 connector on the Smar t Valve
(see Figures 17 and 21).

2. Remove pilot gas line at gas valve.
3. Disconnect pilot burner assembly from pilot bracket.
4. Lift burner and remove burner from orifice.
5. Clean burners. To clean burners, run a clean flue

brush up the tube until all foreign matter is
removed.

6. Replace burners, pilot assembly, ignitor and sensor

wires.

7. Adjust burners and pilot assembly.

C. Re-check of input gas rate of burners. See “Burner

Adjustment” on Page 19.

D. Re-adjusting for best flame characteristics of main

flame and pilot burner flame. See “Burner Adjustment”
on Page 19.

E. To prolong the life of inducer motor, lubricate with 

6 drops of Anderol 465 annually.

Figure 23.

Содержание victory II VH series

Страница 1: ...is boiler is under positive pres sure when it is connected to the outdoors with 3 diameter pipe Leakage from this system can be hazardous and if not avoided can result in death or ser ious injury In a...

Страница 2: ...0 3000 4000 5000 6000 7000 8000 9000 10000 Orifice Size for Sea Level Orifice Sizes for High Altitudes Includes 4 Reduction for Each 1000 Feet Elevation Feet Orifice sizes indicated for sea level abov...

Страница 3: ...fueled shall not be installed in an abo ve grade under floor space or basement unless such loca tion is provided with an approved means for removal of unburned gas Consult Chapter 5 of the 1994 UNIFOR...

Страница 4: ...ith a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances input IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT THE AREA OF FREE OPENINGS MUST BE APPROPR...

Страница 5: ...ght run would be 20 2 x 3 14 ft 3 Installation A Horizontal Venting Figures 5 and 6 show typical horizontal venting For combustible wall passage of vent piping a U L listed thimble must be used See Fi...

Страница 6: ...ltitudes 5500 to 7000 Ft Altitudes 7000 to 10 000 Ft Altitudes Equivalent Length of each 90 Elbow Ft Max Equivalent Length Ft VH 30 30 30 30 6 2 60 90 and 120 VH 150 30 30 15 6 2 VH 180 30 15 15 6 2 F...

Страница 7: ...VICTORY II 7 Figure 6 Figure 5 VICTORY II HORIZONTAL VENTING All joints must be liquid and pressure tight Use U L listed single wall 3 dia AL29 4C S S venting materials See page 5...

Страница 8: ...VICTORY 8 Figure 7...

Страница 9: ...VICTORY Figure 8 9...

Страница 10: ...lined masonry chimney If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exposed chimney it must be re lined with a UL listed metallic liner system See Table 2 in...

Страница 11: ...height and connector 11 9 VH 180 length restrictions 2 Connector may have to be upsized to 6 diameter to meet requirement of 11 9 Additional National Fuel Gas Code Boiler Gas Appliance Reference Tabl...

Страница 12: ...VICTORY 12 Figure 9...

Страница 13: ...VICTORY Figure 10 13...

Страница 14: ...ional Fuel Gas Code ANSI Z223 1 latest edition C The boiler and its gas connection must be leak tested before placing the boiler in operation Use liquid soap solution for all gas leak testing DO NOT u...

Страница 15: ...g arrangement 1 Supply and Return For tapping sizes see dimensions on page 2 Shut off valves are recommended 2 Circulating Systems Victory II boilers are equipped with a water circulating pump mounted...

Страница 16: ...VICTORY 16...

Страница 17: ...VICTORY Figure 14 Figure 15 Piping Arrangement 17...

Страница 18: ...quipment PIPING A HEATING COOLING SYSTEM TO A WATER BOILER AND CHILLER Figure 16 illustrates a method of piping a heating cooling sys tem to a water boiler and a chiller Hand valves shown or automatic...

Страница 19: ...sired setting 10 If appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service or gas supplier To Turn Off Gas to Appliance 1 Set thermostat to lowest settin...

Страница 20: ...op of main burner tube C Main Burner Ignition Checkout and Pilot Adjustment 1 The pilot flame must not smother or snuff out when tested as follows a Main burner ignition from cold start repeat b Conti...

Страница 21: ...m meter to burner including gas valve gas piping manifold and pilot burner DO NOT use open flame CARE AND MAINTENANCE This section must be brought to the attention of the o wner by the installer so th...

Страница 22: ...ers are not firing 3 Annual Inspection and Cleaning The following must be done by a competent serviceperson to help insure safe and reliable operation A Flue passage cleaning See Figure 23 It is sugge...

Страница 23: ...LVE OPENS IGNITOR OFF BOILER HEATING PERIOD WAIT FOR AIR PROVING SWITCH TO OPEN NO NO NO PILOT AND MAIN VALVE CLOSE NO YES YES YES YES YES NO NO Victory II Boiler Sequence of Operations BOILER WATER T...

Страница 24: ...2 High limit of electronic Aquastat open nor mal condition 3 No power 4 Defective Aquastat 5 Defective transformer 6 Harnesses plug in connector is not securely connected at both ends 7 Damaged harne...

Страница 25: ...at to call heat Remove connector marked B2 B1 R on Aquastat Check terminal B2 B1 for 24V Follow Smart Valve system troubleshooting in Smart Valve Honeywell Instruction Manual to find out if Smart Valv...

Страница 26: ...nting system 4 Condensation trap is not full of water 4 Check and fill with water 5 Venting system is physically damaged 5 Check carefully and repair Also see Venting System Regular Inspection 6 Over...

Страница 27: ...Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe conditi...

Страница 28: ...VICTORY SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com...

Отзывы: