cian or gas supplier

To Turn Off Gas To Appliance

1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be

performed.

3. Remove control access panel.
4. Turn gas control knob clockwise 

until knob stops,

then continue to "OFF". DO NOT force.

5. Replace control access panel.

III. BURNER ADJUSTMENT

A. Adjust gas input rate:

1. Consult gas supplier for higher* heating value of gas –

W/m

3

(Btu/cu.ft.)

2. Set thermostat high enough so that boiler will remain on

while checking rate.

3. Measure manifold pressure at 1/8" tapping. Cor rect

manifold pressure for gas used is printed on boiler rat-
ing plate. NOTE: Gas pressure may be adjusted by turn -
ing pressure regulator screw on combination gas valve
(turn clockwise to increase pressure, counterclockwise
to decrease pressure).
a. Input for PROPANE is approximately at rating shown

on rating plate when manifold pressure is 241 mm
(9

1

/

2

") water column.

b. Input for NATURAL GAS is approximately at rating

when manifold pressure is 89 mm (3

1

/

2

") water col-

umn, but should be checked on the gas meter:
Input = W/m

× m

metered in 3 minutes × 20

(Input = Btu/cu. ft. x cu. ft. metered in 3 minutes x
20)

Sentinel

15

Example #1:
For 8.29 W/m

3

gas, this becomes:

Input = m

3

metered in 3 minutes × 8.29 × 20 

(For 1000 Btu/cu.ft. gas, this becomes:
Input = cu. ft. metered in 3 minutes × 1000 × 20)

Example #2:

For 8.70 W/m

3

gas this becomes:

Input = m

3

metered in 3 minutes × 8.70 × 20

(For 1050 Btu/cu.ft. gas, this becomes: 
Input = cu. ft. metered in 3 minutes × 1050 × 20)

4. The higher heating value* of gas varies substantially for

different localities. Consult with Slant/Fin’s Technical
 Service Dept. for re-orificing procedures if any of the
 following apply:
a. Boiler (burner) is overfiring. CAUTION! National Fuel

Gas Code ANSI Z223.1-latest edition or CSA 
B149.1-00 for natural gas and propane, does NOT
permit firing at a higher input rate than the input rate
indicated on the boiler rating plate in order to avoid
hazardous conditions such as explosion or carbon
monoxide  poisoning.

b. Poor higher heating value* of gas is causing the

 actual input to be substantially lower than the rating
plate indication.

* “Higher heating value” of gas is commonly known as a “heating value.”

The gas metered in 3 minutes to obtain rated input for each
boiler model, using 8.29 W/m

3

(1000 Btu/cu.ft.) gas is tabu lated

below:

B. Main Burners
1. Fire the boiler continuously for at least 15 minutes, to reach

burner operating temperature.

2. Observe the flames, all burners. The base of all flame jets

should be blue. The tips should be blue shading to orange.
NOTE: Dust, disturbed by any movement, will cause bright
orange flames. Wait for dust to settle.

3. For one burner, close the air shutter until some of its flame jet

tips turn yellow-white, indicating insufficient primary air. Then
open shutter until whitish tips disappear completely. Set all
burner shutters to the same opening. Observe to make sure
that no yellow-white tips appear over any portion of the
flame. Small yellow tips at the pilot location are  permitted.
NOTE: This adjustment method gives MINIMUM primary air
setting for safe combustion. DO NOT attempt to make this
adjustment unless burners are at operating temperature.
Adjustment should be made with burner access panel in
final operating position. Use of a mirror may be helpful to
observe flames. Note that burner ports are on top of main
burner tube.

Figure 11. Valve VR8204 or VR8304

Figure 12.

m

3

/hr

cu.ft./hr.

m

3

cu.ft.

1.98

70

0.099

3.50

2.97

105

0.149

5.25

3.96

140

0.198

7.00

4.95

175

0.248

8.75

5.94

210

0.297

10.50

6.93

245

0.347

12.25

BOILER RATED INPUT

8.29 W/m

3

(1000 Btu/cu. ft.)

Natural Gas

GAS CONSUMPTION

8.29 W/m

3

(1000 Btu/cu. ft.)

in 3 minutes, at rated input

Содержание SENTINEL

Страница 1: ... READING THE INSTALLATION INSTRUCTIONS The installation must conform to the requirements of the authority having jurisdiction or in the absence of such requirements to the National Fuel Gas Code ANSI Z2231 latest edition or CSA B 149 1 latest edition for natural gas and propane The installation must also conform to the additional requirements in this Slant Fin Instruction Book In addition where re...

Страница 2: ...ther appliance are vented to a single chimney Orifice indicated for sea level above are factory installed in boiler unless otherwise specified by the local authority See Section III on page 15 for burner input adjustment 1 1 2 FPT Supply 419 mm 16 1 2 552 mm 21 3 4 3 4 to air eliminating system by others Vent Damper shown vertically Vent Damper shown horizontally Sediment Trap required High Limit ...

Страница 3: ... etc during appliance operation and service circulator replace ment condensate trap control replacement etc BOILER FOUNDATION A Provide a solid level foundation capable of supporting the weight of the boiler filled with water and extending at least 51 mm 2 past the jacket on all sides See dimensions of boiler page 2 B For installation on non combustible floors only The Com bustible Floor Kit part ...

Страница 4: ...s utility local building codes and other authorities having jurisdiction If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exterior chimney ONE of the following options apply 1 Chimney must be re lined with an approved metallic liner When this is done the chimney will be considered NOT exposed to the outdoors and the requirements for NON exposed chimneys and ...

Страница 5: ...od outlet and the connec tor to the outdoor chimney or vent as close to the draft hood as practicable and without modification of the draft hood or the damper See figures 1 and 2 6 The inlet size of the vent damper must be the same nominal trade size as the outlet of the draft hood 7 This device must be located in a venting system or section of a venting system so that it serves only the single ap...

Страница 6: ...ther end of the flexible metal conduit has a small molex plug and a 90 degree metal conduit connector Route the molex receptacle through the conduit bracket on the vent damper Place the harness receptacle into the damper plug Securely fasten the harness conduit con nector to the conduit bracket by carefully pushing it into the hole in the bracket 4 Restore electrical power and turn on gas supply C...

Страница 7: ...electrical source is utilized the boiler when installed must be electrically grounded in accordance with the requirements of the authority having jurisdiction or in absence of such requirements with the Cana dian Electric Code CSA C22 1 Part 1 latest edition C Basic control wiring diagrams are supplied Other control systems may be factory sup plied see User s Information Manual and Instructions pa...

Страница 8: ...8 Sentinel Figure 8 Multizoning of Sentinel boilers pump zoning system using R845A relay Figure 9 Multizoning of Sentinel boiler 2 zone system pump zoning system using R882A B relays ...

Страница 9: ... same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITONS IS TRUE r e t a w r e l i o b e h t s e c u d e r t a h t d e l l a t s n i s i m e t s y s t n e m e g a n a m y g r e n e l a n r e t x e n A temperature as the heating load decreases g n i t a e h e c a p s y n a r o f d e s u t o n s i r e l i o b s i h T r e t a e r g r o H B M 0 0 3 w k 8 8 f o t u p...

Страница 10: ...AIN BURNERS OFF VENT DAMPER CLOSES CIRCULATOR OFF SYSTEM GOES TO STANDBY SPARK GENERATOR MODULE POWERED S8600F OR S8600M IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS S8670E IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR 30 70 SECONDS L P PROPANE GAS S8600M and S8670E IGNITION TRIAL CONTINUES FOR 90 SECONDS AFTER TRIAL FOR IGNITION SYSTEM SHUTS OFF AFTER 5 MINUTES MODULE RE INSTATES TR...

Страница 11: ... push and hold the but ton a second time for 20 seconds The display will read Pur OFF SETTING THE CONTROL At initial start up with the Economy Feature active the control establishes a 63 C 145 F target temperature To test the high limit shut off function the Economy Dial must be turned to OFF Once tested restore the Economy setting If the heating demand is high the target will increase over time t...

Страница 12: ...l Targeting Works on page 4 for more information zECONOMY TARGET When the Economy feature is active the Fuel Smart HydroStat continually sets target temperatures below the high limit setting to maximize fuel efficiency When the boiler water reaches the target temperature the LED illuminates and the burner will shut down The boiler water will continue to cir culate and heat the house as long as the...

Страница 13: ...nd should be provided If the boiler is not near an outside wall air may be ducted to it from outside wall openings Provisions for combustion and ventilation air must be made in accordance with section 5 3 Air for Combustion and Ventila tion of the National Fuel Gas Code ANSI Z2231 latest edition or CSA B 149 1 latest edition for natural gas and propane or applicable provisions of the local buildin...

Страница 14: ...ER PIPING I CIRCULATING SYSTEMS A Hot water heating systems include a water circulating pump which may be mounted on the supply or return side of the boiler based on system design See figure 5 II AIR CONTROL SYSTEM A DIAPHRAGM EXPANSION TANKS are used to control system pressure in an AIR ELIMINATING SYSTEM an automatic air vent is used to REMOVE air from the sys tem water See figure 9 If system pr...

Страница 15: ...NSI Z223 1 latest edition or CSA B149 1 00 for natural gas and propane does NOT permit firing at a higher input rate than the input rate indicated on the boiler rating plate in order to avoid hazardous conditions such as explosion or carbon monoxide poisoning b Poor higher heating value of gas is causing the actual input to be substantially lower than the rating plate indication Higher heating val...

Страница 16: ... gauge 2 Air control system noise and air binding in system should be corrected 3 Water lines slightest leaks should be corrected 4 Low water cutoff for operation see instructions fur nished with unit 2 WATER LEVEL CHECK DURING HEATING SEASON A Check water pressure regularly and add water slowly to system when needed If much water is added venting may be necessary B Regular loss of water from wate...

Страница 17: ...hen system water glycol solution is in contact with a potable water vessel as with a tankless heater PROPYLENE GLYCOL is used in the quick freeze food industry it is practically non toxic Its use may be permitted when tankless heaters are used When anti freeze must be used inhibited propylene glycol is recommended Useful information on the characteristics mixing proportions etc of glycol in heatin...

Страница 18: ...zontal run of smokepipe 4 Inadequate chimney or venting system REMEDY 1 Check clean re light See instructions 2 Open gas valve s 3 Close switch 4 Replace fuse 5 Check control Clean contacts or replace control 6 Repair or replace 7 Replace transformer 8 Check clean and reinstall 9 Check with test light and correct 10 Check and correct in accordance with wiring diagrams included with appliance instr...

Страница 19: ...t so appliance will operate continuously e Test for spillage at the draft hood relief opening after 5 min utes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe f After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlined above return doors win dows exhaust fans fireplac...

Страница 20: ...ed from a well This accumulation creates an insulating layer that drastically affects boiler efficiency by reducing the transmission of heat through this primary transfer surface and causes extreme metal temperatures that eventually crack the heat exchanger RECOMMENDATIONS On all installations in hard water areas 1 The system should be thoroughly inspected for leaks which must be repaired however ...

Отзывы: