Sentinel

u

TEMP   

ACTIVE

Indicates that the

Fuel Smart HydroStat control is powered
and that the temperature function is
active.

v

TEMP   

HIGH TEMP

Illuminates

when the boiler water temperature reach-
es the high limit setting. It will remain lit
until the water temperature falls 5.5°C
(10°F) (see High Limit Differential on page
4). The Fuel Smart HydroStat prevents
burner operation while this LED is on.

w

LWCO  

ACTIVE

Indicates that the low water cut-off (LWCO)

function of the Fuel Smart HydroStat is active. When the control is
installed with a Hydrolevel Electro-Well, this LED will be on at all
times when the control is powered.

IMPORTANT:

If the control is installed with a well other than the

Electro-Well, this LED will not illuminate indicating that the control is
not providing low water cut-off functionality.

x

LWCO  

LOW WATER

Illuminates if the boiler is in a low water

condition. The Fuel Smart HydroStat will prevent burner operation
during this condition. 

IMPORTANT:

The system must be checked

by a qualified heating professional prior to resuming operation.

WARNING: DO NOT ADD WATER UNTIL THE BOILER
HAS FULLY COOLED.

y

ECONOMY  

ACTIVE

Indicates that the Thermal Targeting func-

tion is active and the Fuel Smart HydroStat will reduce boiler tem-
perature to conserve fuel. The Economy feature is activated using
the ECONOMY dial. (See “How Thermal Targeting Works” on page
4 for more information).

z

ECONOMY  

TARGET

When the Economy feature is active, the

Fuel Smart HydroStat continually sets target temperatures below
the high limit setting to maximize fuel efficiency. When the boiler

water reaches the target temperature, the
LED illuminates and the burner will shut
down. The boiler water will continue to cir-
culate and heat the house as long as the
thermostat call continues. The LED will
stay lit until the boiler temperature drops
to the differential set point (see Target
Temp Differential on page 4) at which
point the boiler will be allowed to fire
again. NOTE: This LED illuminates regu-
larly during normal boiler operation.

{

TEST/SETTINGS

Button

To Test Low Water Cut-Off

: Press and hold the Test/Settings button

for 5 seconds. The display will read LCO.

LWCO TEST

LCO

The red Low Water light should illuminate and the burner circuit (B1
and B2) should de-energize. NOTE: The control must be installed
with a Hydrolevel Electro-Well for low water cut-off functionality (see
page 2 for more details).

To View Current Settings: Press and release the Test/Settings Button in
short intervals to sequentially display the following settings:

HIGH LIMIT SETTING   HL

q

LOW LIMIT SETTING   LL

q

ECONOMY SETTING   ECO

q

CURRENT TARGET TEMPERATURE   

ooo

q

PRE-PURGE SETTING   Pur

The display will return to boiler temperature (default) if

Test/Settings Button in not pressed for 5 seconds.

ACTIVE

HI TEMP

ACTIVE

LOW WA

TER

ACTIVE

TARGET

TARGET SET

TINGS

u v w x y z {

TEMP   LWCO   ECONOMY

LED LEGEND and TEST/SETTINGS BUTTON

Содержание SENTINEL

Страница 1: ... READING THE INSTALLATION INSTRUCTIONS The installation must conform to the requirements of the authority having jurisdiction or in the absence of such requirements to the National Fuel Gas Code ANSI Z2231 latest edition or CSA B 149 1 latest edition for natural gas and propane The installation must also conform to the additional requirements in this Slant Fin Instruction Book In addition where re...

Страница 2: ...ther appliance are vented to a single chimney Orifice indicated for sea level above are factory installed in boiler unless otherwise specified by the local authority See Section III on page 15 for burner input adjustment 1 1 2 FPT Supply 419 mm 16 1 2 552 mm 21 3 4 3 4 to air eliminating system by others Vent Damper shown vertically Vent Damper shown horizontally Sediment Trap required High Limit ...

Страница 3: ... etc during appliance operation and service circulator replace ment condensate trap control replacement etc BOILER FOUNDATION A Provide a solid level foundation capable of supporting the weight of the boiler filled with water and extending at least 51 mm 2 past the jacket on all sides See dimensions of boiler page 2 B For installation on non combustible floors only The Com bustible Floor Kit part ...

Страница 4: ...s utility local building codes and other authorities having jurisdiction If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exterior chimney ONE of the following options apply 1 Chimney must be re lined with an approved metallic liner When this is done the chimney will be considered NOT exposed to the outdoors and the requirements for NON exposed chimneys and ...

Страница 5: ...od outlet and the connec tor to the outdoor chimney or vent as close to the draft hood as practicable and without modification of the draft hood or the damper See figures 1 and 2 6 The inlet size of the vent damper must be the same nominal trade size as the outlet of the draft hood 7 This device must be located in a venting system or section of a venting system so that it serves only the single ap...

Страница 6: ...ther end of the flexible metal conduit has a small molex plug and a 90 degree metal conduit connector Route the molex receptacle through the conduit bracket on the vent damper Place the harness receptacle into the damper plug Securely fasten the harness conduit con nector to the conduit bracket by carefully pushing it into the hole in the bracket 4 Restore electrical power and turn on gas supply C...

Страница 7: ...electrical source is utilized the boiler when installed must be electrically grounded in accordance with the requirements of the authority having jurisdiction or in absence of such requirements with the Cana dian Electric Code CSA C22 1 Part 1 latest edition C Basic control wiring diagrams are supplied Other control systems may be factory sup plied see User s Information Manual and Instructions pa...

Страница 8: ...8 Sentinel Figure 8 Multizoning of Sentinel boilers pump zoning system using R845A relay Figure 9 Multizoning of Sentinel boiler 2 zone system pump zoning system using R882A B relays ...

Страница 9: ... same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITONS IS TRUE r e t a w r e l i o b e h t s e c u d e r t a h t d e l l a t s n i s i m e t s y s t n e m e g a n a m y g r e n e l a n r e t x e n A temperature as the heating load decreases g n i t a e h e c a p s y n a r o f d e s u t o n s i r e l i o b s i h T r e t a e r g r o H B M 0 0 3 w k 8 8 f o t u p...

Страница 10: ...AIN BURNERS OFF VENT DAMPER CLOSES CIRCULATOR OFF SYSTEM GOES TO STANDBY SPARK GENERATOR MODULE POWERED S8600F OR S8600M IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS S8670E IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR 30 70 SECONDS L P PROPANE GAS S8600M and S8670E IGNITION TRIAL CONTINUES FOR 90 SECONDS AFTER TRIAL FOR IGNITION SYSTEM SHUTS OFF AFTER 5 MINUTES MODULE RE INSTATES TR...

Страница 11: ... push and hold the but ton a second time for 20 seconds The display will read Pur OFF SETTING THE CONTROL At initial start up with the Economy Feature active the control establishes a 63 C 145 F target temperature To test the high limit shut off function the Economy Dial must be turned to OFF Once tested restore the Economy setting If the heating demand is high the target will increase over time t...

Страница 12: ...l Targeting Works on page 4 for more information zECONOMY TARGET When the Economy feature is active the Fuel Smart HydroStat continually sets target temperatures below the high limit setting to maximize fuel efficiency When the boiler water reaches the target temperature the LED illuminates and the burner will shut down The boiler water will continue to cir culate and heat the house as long as the...

Страница 13: ...nd should be provided If the boiler is not near an outside wall air may be ducted to it from outside wall openings Provisions for combustion and ventilation air must be made in accordance with section 5 3 Air for Combustion and Ventila tion of the National Fuel Gas Code ANSI Z2231 latest edition or CSA B 149 1 latest edition for natural gas and propane or applicable provisions of the local buildin...

Страница 14: ...ER PIPING I CIRCULATING SYSTEMS A Hot water heating systems include a water circulating pump which may be mounted on the supply or return side of the boiler based on system design See figure 5 II AIR CONTROL SYSTEM A DIAPHRAGM EXPANSION TANKS are used to control system pressure in an AIR ELIMINATING SYSTEM an automatic air vent is used to REMOVE air from the sys tem water See figure 9 If system pr...

Страница 15: ...NSI Z223 1 latest edition or CSA B149 1 00 for natural gas and propane does NOT permit firing at a higher input rate than the input rate indicated on the boiler rating plate in order to avoid hazardous conditions such as explosion or carbon monoxide poisoning b Poor higher heating value of gas is causing the actual input to be substantially lower than the rating plate indication Higher heating val...

Страница 16: ... gauge 2 Air control system noise and air binding in system should be corrected 3 Water lines slightest leaks should be corrected 4 Low water cutoff for operation see instructions fur nished with unit 2 WATER LEVEL CHECK DURING HEATING SEASON A Check water pressure regularly and add water slowly to system when needed If much water is added venting may be necessary B Regular loss of water from wate...

Страница 17: ...hen system water glycol solution is in contact with a potable water vessel as with a tankless heater PROPYLENE GLYCOL is used in the quick freeze food industry it is practically non toxic Its use may be permitted when tankless heaters are used When anti freeze must be used inhibited propylene glycol is recommended Useful information on the characteristics mixing proportions etc of glycol in heatin...

Страница 18: ...zontal run of smokepipe 4 Inadequate chimney or venting system REMEDY 1 Check clean re light See instructions 2 Open gas valve s 3 Close switch 4 Replace fuse 5 Check control Clean contacts or replace control 6 Repair or replace 7 Replace transformer 8 Check clean and reinstall 9 Check with test light and correct 10 Check and correct in accordance with wiring diagrams included with appliance instr...

Страница 19: ...t so appliance will operate continuously e Test for spillage at the draft hood relief opening after 5 min utes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe f After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlined above return doors win dows exhaust fans fireplac...

Страница 20: ...ed from a well This accumulation creates an insulating layer that drastically affects boiler efficiency by reducing the transmission of heat through this primary transfer surface and causes extreme metal temperatures that eventually crack the heat exchanger RECOMMENDATIONS On all installations in hard water areas 1 The system should be thoroughly inspected for leaks which must be repaired however ...

Отзывы: