DA 1700 dual actuator
Technical User Guide
63
7.2 DA 1700-7 ACT 3x400 V
435370 DA 1700-7 ACT 3x400 V
Electrical
Rated voltage
V AC
400 +/-10%
Operating voltage
V AC
360 – 440
Frequency
Hz
50
Max. current consump-
tion
At 400 V AC supply
A
5.9
Max. input power (P1)
W
2260
Max. power (P2) shaft
W
2200
Efficiency motor [η]
%
78
CosPhi [Φ]
Factor
0.7
Motor protection thermal
cutout (PTO)
Thermik S01 120.05 in separate cable
Mechanical
Cable length
m
4
Impeller diameter
mm
1400
Number of fan blades
pcs.
3
Fan blade pitch
°
45
Fan output
Revolutions (rated cur-
rent) per minute
RPM
700
Air output at -0 Pa
m
3
/h
59600
Air output at -10 Pa
m
3
/h
58000
Air output at -20 Pa
m
3
/h
56300
Air output at -30 Pa
m
3
/h
54300
Air output at -40 Pa
m
3
/h
52400
Air output at -50 Pa
m
3
/h
50500
Air output at -60 Pa
m
3
/h
48200
Air output at -70 Pa
m
3
/h
45900
Air output at -80 Pa
m
3
/h
43700
Air output at -90 Pa
m
3
/h
41500
Air output at -100 Pa
m
3
/h
39200
Power consumption at
-10 Pa
W
1712
Specific output at -10 Pa
m
3
/kWh
33900
Specific energy at -10 Pa Watt/100
0 m
3
/h
30
Testing body
SKOV A/S
Environment
Temperature, operation
°C
÷ 40 to + 40
Start temperature
°C
÷ 40 to + 50
Storage temperature
°C
÷ 40 to + 70