6 Troubleshooting instructions
Remember to shut the fan off at the power supply isolator prior to troubleshooting.
Troubleshooting flap system
Fault symptom
Status LED
Error
Solution
Inlet flap will not close/
open
Quick flash
Flap touches the ventilation
duct (obstructed).
Remedy the damage.
Actuator blocked.
Replace defective parts.
Normal flash
ON/OFF signal from controller /
manual operation is lacking.
Actuator not running
No flash
Lacking 24 V DC supply volt-
age
Check 24 V DC supply voltage.
Check assembly according to the
connection and circuit diagram.
Troubleshooting fan motor
Fault symptom
Status LED
Error
Solution
Abnormal noise coming
from fan.
-
Faulty mounting.
Check in accordance with the docu-
ment. Retighten if required.
Bearing noise.
Replace the motor.
Vibrating fan.
Check whether fan blades are de-
fective, correctly assembled or dirty.
Replace or clean.
Fan motor is not run-
ning.
-
AC motor: Motor protection
switches off
Check the size of the protective mo-
tor switch see
.
Replace motor protection, change
to correct size.
Check whether the fan motor is
blocked.
Remove the blocking.
Too high negative pressure in the
livestock house,
check the air inlets.
AC motor:
Control voltage to motor con-
tactor
Check signal to contactor.
AC motor:
Power supply to the motor
Measure the voltage going to the
motor.
LPC motor:
-