Manufactured by:

Warranty void if panel is modified.

Call factory with servicing questions:

1-800-RHOMBUS

(1-800-746-6287)

This control panel must be installed and serviced by a licensed 

electrician in accordance with the National Electric Code NFPA-70, state 

and local electrical codes. 

All conduit running from the sump or tank to the control panel must be 

sealed with conduit sealant to prevent moisture or gases from entering the panel. 

NEMA 4X enclosures are for indoor or outdoor use,

 primarily to provide a 

degree of protection against corrosion, windblown dust and rain, splashing water 

and hose-directed water. 

Cable connectors must be liquid-tight in NEMA 4X 

enclosures.

The EZ Series

®  

Type EZS control panels are designed to control single phase 

pump(s). The controller records pump status, number of cycles, elapsed run 

time, alarm counter, and float error counts. 

Mounting the Control Panel

Note:

 The control panel should not be mounted in a location that may be subject 

to submersion.

1.

 

Determine mounting location for panel. If distance exceeds the length of 

either the float cables or the pump power cables, splicing will be required. 

For outdoor or wet installation, we recommend the use of an SJE-Rhombus

®

 

liquid-tight junction box with liquid-tight connectors to make required con

-

nections.  

You must use conduit sealant to prevent moisture or gases 

from entering the panel.

2. 

Mount control panel with mounting devices furnished.

3.

  Determine conduit entrance locations on control panel.  Check local codes 

and  schematic  for  the  number  of  power  circuits  required. 

(Float cables 

require separate conduit from power and pump cables.)

Note:

 Be sure the proper power supply voltage, amperage, and phase meet the 

requirements of the pump motor(s) being installed.  If in doubt, see the pump 

identification plate for voltage/phase requirements.

4.

  Drill proper size holes for type of connectors being used.

Note:

 If using conduit, be sure that it is of adequate size to pull the pump cable(s) 

through.  

5.

  Attach cable connectors and/or conduit connectors to control panel.

 FOR INSTALLATION REQUIRING 

A SPLICE, FOLLOW STEPS 6-10;

FOR INSTALLATION WITHOUT A 

SPLICE, GO TO STEP 11.

6.

  Determine location for mounting junction box according to local code 

requirements. 

Do not

 mount the junction box inside the sump or basin.

7.

  Mount junction box to proper support.

8.

  Run conduit to junction box. Drill proper size holes for the type of conduit 

used.

Installation

EZ Series

®

SJE Rhombus

®

 Type EZS

Installation Instructions and Operation/Troubleshooting Manual

Instl. Instr. PN 1023074E 07/18

© 2018 SJE, Inc. All Rights Reserved.

SJE RHOMBUS is a trademark of SJE, Inc.

Содержание EZS

Страница 1: ...g will be required For outdoor or wet installation we recommend the use of an SJE Rhombus liquid tight junction box with liquid tight connectors to make required con nections You must use conduit sealant to prevent moisture or gases from entering the panel 2 Mount control panel with mounting devices furnished 3 Determine conduit entrance locations on control panel Check local codes and schematic f...

Страница 2: ...mber Failure to do so could result in serious or fatal electrical shock 1 Determine your normal operating level and desired float configuration as illustrated in Figures 2 5 2 Mount float switches at appropriate levels Be sure that floats have free range of motion without touching each other or other equipment in the basin 3 For mounting clamp installation place the cord into the clamp as shown in...

Страница 3: ... status closed open Elapsed Time Count the display shows then alternates showing hours hh then minutes mm Cycle Count the display shows then the count High Level Power Fail Alarms the display shows then the count Float Error Count the display shows then the count Auxiliary Alarm Input Counts the display shows then the count TIMED DOSE DISPLAY ONLY Timer Override Count the display shows then the co...

Страница 4: ...CONSEQUENTIAL DAMAGES AS A RESULT OF A BREACH OF THIS WRITTEN WARRANTY OR ANY IMPLIED WARRANTY SJE Rhombus Five Year Limited Warranty Float Controls 1 Check the floats during their entire range of operation Clean adjust replace and repair damaged floats 2 Measure the float resistance to determine if the float is operating properly To measure float resistance a Isolate the float by disconnecting on...

Отзывы: