Operations

The EZ Series

®

 (EZS) control panel uses float switches to 

continuously monitor and control the liquid level in the tank.

Hand Operation

 - Press and hold the “Push to Run” switch if 

stop float is OPEN. If stop float is CLOSED, press “Push to Run” 

switch and the pump will run until stop float opens.

Off Operation

 - Turn control/alarm breaker off to be in Off 

operation. 

Auto Operation

 - In time dose (t-dose) mode the timer 

controls pump ON and OFF time as long as the timer enable 

float is raised. In demand (d-dose) mode, the stop and start floats 

control the pump.

Alarm Count 

- Shown on display as 

  

.



 , counts the 

number of times the alarm is activated. Note: Alarm counter does 

not include testing operations in the total count. High alarm and 

alarm power loss add to count.

Green Control and Alarm Power Indicators 

  -  

Illuminates when control power and alarm power is present. Alarm 

light will flash if alarm power is lost.

Timer Override Float

 - Overrides the OFF time and pump 

will run for full dose ON time. (timed dose only, optional)

Float Error Count

 - Shown on the display as  



.



 . Counts 

the number of times floats are out of sequence. Alarm horn will 

sound and alarm light will flash.

Timer Override Count

 - Shown on the display as  



.



Counts the number of times the timer override float is activated. 

(timed dose only)

Time left in “On” time cycle

 - Shown on the display 

as 



 . Counts down the time left in the “On” cycle. (timed 

dose only)

Time left in “Off” time cycle

 - Shown on the display 

as  



 . Counts down the time left in the “Off” cycle. (timed 

dose only) 

Green Pump Run Indicator(s)

 - Illuminates when 

pump(s) are called to run.

Viewing Panel Settings (Simplex)

With control power supplied to panel:

 

Press menu/enter button to scroll to the desired display screen.

Float Status or Float Error - the display shows   



  or  



    

then float status.  

=closed   

=open

Elapsed Time Count - the display shows   



.

   then alternates 

showing hours (hh) then minutes (:mm).

Cycle Count - the display shows   



.

   then the count.

High Level & Power Fail Alarms - the display shows  



.



 then 

the count.

Float Error Count - the display shows  



.



  then the count.

Auxiliary Alarm Input Counts - the display shows   



   then 

the count.

TIMED DOSE DISPLAY ONLY

Timer Override Count - the display shows  



.



  then the 

count.

ON Time - the display flashes   



  then the ON time in mm:ss.

Off Time - the display flashes   



   then the Off  time in 

hh:mm.

Remaining ON/OFF Times - the display flashes either   



  

or  



  then the time left in the On cycle (mm:ss) or OFF 

cycle (hh:mm).

Programming Panel Setting (Simplex):

With control power supplied to panel:

Press set/change button for 3 seconds to enter program mode.

The display will show   



   time in mm:ss.

Press set/change button to set the pump On time.  Use the 

menu/enter button to select digit desired to change. Use the 

set/change button to change On time.

Press menu/enter button. The display will show   



  time in 

hh:mm. 

Press set/change button to set the pump Off time.  Use the 

menu/enter button to select digit desired to change. Use the  

set/change button to change Off time.

Note:  Setting the  



  times to  



:



  turns off timed dose 

mode and timed dose menu items.  The panel will operate in 

demand mode. 



  time must be set higher than  



:



  for 

demand dose to function.

Press set/change button for 3 seconds to return to the view 

menu. 

Viewing Panel Settings (Duplex)

With control power supplied to panel:

 

Press menu/enter button to scroll to the desired display screen.

Float Status or Float Error - the display shows   



  or  



    

then float status.    

=closed     

=open

Pump 1 Elapsed Time Count - the display shows   



.

   then 

alternates showing hours (hh) then minutes (:mm).

Pump 1 Cycle Count - the display shows   



.

   then the 

count.

Pump 2 Elapsed Time Count - the display shows   



.

   then 

alternates showing hours (hh) then minutes (:mm).

Pump 2 Cycle Count - the display shows   



.

   then the 

count.

High Level & Power Fail Alarms - the display shows  



.



 then 

the count.

Содержание EZS

Страница 1: ...g will be required For outdoor or wet installation we recommend the use of an SJE Rhombus liquid tight junction box with liquid tight connectors to make required con nections You must use conduit sealant to prevent moisture or gases from entering the panel 2 Mount control panel with mounting devices furnished 3 Determine conduit entrance locations on control panel Check local codes and schematic f...

Страница 2: ...mber Failure to do so could result in serious or fatal electrical shock 1 Determine your normal operating level and desired float configuration as illustrated in Figures 2 5 2 Mount float switches at appropriate levels Be sure that floats have free range of motion without touching each other or other equipment in the basin 3 For mounting clamp installation place the cord into the clamp as shown in...

Страница 3: ... status closed open Elapsed Time Count the display shows then alternates showing hours hh then minutes mm Cycle Count the display shows then the count High Level Power Fail Alarms the display shows then the count Float Error Count the display shows then the count Auxiliary Alarm Input Counts the display shows then the count TIMED DOSE DISPLAY ONLY Timer Override Count the display shows then the co...

Страница 4: ...CONSEQUENTIAL DAMAGES AS A RESULT OF A BREACH OF THIS WRITTEN WARRANTY OR ANY IMPLIED WARRANTY SJE Rhombus Five Year Limited Warranty Float Controls 1 Check the floats during their entire range of operation Clean adjust replace and repair damaged floats 2 Measure the float resistance to determine if the float is operating properly To measure float resistance a Isolate the float by disconnecting on...

Отзывы: