Wiring the Control Panel

1

Locate conduit entrance at the bottom of the enclosure as 
shown. Check local codes for the number of power circuits 
required. The schematic is located on the inside cover of the 
control panel.

Be sure the incoming voltage is the same as the pump motor

nameplate.
Providing separate pump and control/alarm power sources is

recommended.
Type 4X conduit must be used to maintain a Type 4X rating

of the control panel.

CAUTION!

CAUTION!

Seal the electrical conduit with an approved 
sealing compound to prevent moisture or 
gases from entering into the control panel.

Connect the following wires to the proper terminals:
• 

incoming power for each pump circuit breaker

• 

incoming power for control/alarm

• 

pump 1

• 

pump 2 (duplex only)

• 

C-Level™ sensor

• 

fl oat switches (recommended)

See schematic label on inside cover of the control panel for 
details.

2

Duplex Model Shown

Setup and Operation

Rotate dial and press to select the corresponding pump’s mode indicator or panel settings icon.

3

Verify correct operation of control panel after installation is 
complete.

If redundant off  fl oat is not used, a jumper must be

installed in its place.

2

Alarm System (Indicator Light and Horn)

When an alarm condition occurs, the red light and 
horn will be activated.

If the TEST/SILENCE button is pressed and released, 
the horn will be silenced.  When the alarm condition 
is cleared, the alarm system is reset.

Circuit Breakers

Each pump circuit has a thermal-magnetic circuit 
breaker that provides branch circuit protection and a 
means to disconnect the pump.

Float Test Switches

Push to simulate a fl oat closure condition for each 

input.

Dry Auxiliary Contacts

Normally Open

- Contacts are OPEN under normal 

conditions and CLOSED when alarm condition is 
present. CLOSED during power loss.
Automatically resets once alarm condition is cleared.
Aux contact rating: 120V, 5A

1

2

4

3

NOTE

1

3

4

HAND

OFF

AUTO

1

HAND

OFF

AUTO

2

PUMP 2 

(duplex only)

SETTINGS

Counts and ETMs         - Displays pump run time and counts of pump run and alarms
Timer Settings 

       - Confi gures timers (Timed Dose mode only)   

Level Settings 

       - Confi gures level setpoints        

Alternation (duplex only) - Confi gures alternation mode for duplex panels
Advanced  

       - Confi gure advanced functions and view troubleshooting tools

PUMP 1

HOA

Содержание C-Level

Страница 1: ... conditions please visit www sjerhombus com Products returned must be cleaned sanitized or decontaminated as necessary prior to shipment to ensure that employees will not be exposed to health hazards in handling said material All applicable laws and regulations shall apply High Water Float Redundant Off Float C Level Sensor Parts included Manufactured by SJE Rhombus Detroit Lakes MN USA Control pa...

Страница 2: ...the same conduit as the pump cables E2 Ensure all supply power to the control panel is turned OFF before installing or servicing the C Level sensor float switches or pumps in the tank Failure to do so could result in serious or fatal shock Power from Breaker Off Floats require free range of motion They must not touch each other or any equipment in the pump chamber Timed Dose Float Switch Installat...

Страница 3: ...switches are not mounted and connected correctly the pumps and alarm will not operate properly 3 5 9 cm C Level Sensor Positioning Keep vent above water level hose clamp 4 inch 10 2 cm minimum set level 0 inch 0 cm liquid level measured from approximately this point 1 inch 2 5 cm minimum from bottom of tank or from sludge hose clamp Stow excess tube using a cable tie Caution Do not overtighten and...

Страница 4: ...ttings icon 3 Verify correct operation of control panel after installation is complete If redundant off float is not used a jumper must be installed in its place 2 Alarm System Indicator Light and Horn When an alarm condition occurs the red light and horn will be activated If the TEST SILENCE button is pressed and released the horn will be silenced When the alarm condition is cleared the alarm sys...

Страница 5: ... com Flotador de nivel alto Flotador de apagado redundante Sensor C Level Piezas incluidas Fabricado por SJE Rhombus Detroit Lakes MN USA Es posible solicitar el panel de control con o sin sensor C Level flotadores Sensor C Level Modelos Interruptor de flotador Modelos 3x o 4x Installer Friendly Series Installation and Operation Manual This control panel must be installed and serviced by a license...

Страница 6: ...tación de entrada al panel de control esté APAGADA OFF antes de la instalación o el mantenimiento del sensor C Level de los interruptores de flota dor o de las bombas al interior del tanque No obedecer estas indicaciones podría resultar en choque eléctrico serio o mortal PRECAUCIÓN Corriente proveniente del disyuntor Off Apagado Los flotadores deben tener libre movimiento No pueden tocarse entre s...

Страница 7: ...uptores de flotador no están correctamente montados y conectados las bombas y la alarma no operan bien 9 cm 3 5 Posición del sensor C Level Mantener el tubo de ventilación por encima del nivel de agua abrazadera para manguera 10 2 cm 4 de nivel predeterminado mínimo nivel de líquido a 0 cm 0 medido desde este punto aproximadamente 2 5 cm 1 mínimo desde el fondo del tanque o desde los lodos abrazad...

Страница 8: ...ración correcta del panel de control Si no se utiliza el flotador redundante de apagado en su lugar debe instalarse un puente 2 Sistema de alarma luz indicadora y bocina Cuando se presenta una condición de alarma se activan la luz roja y la bocina o alarma sonora Al pulsar y soltar el botón de prueba silencio Test Silence queda silenciada la alarma sonora o bocina Una vez despeja da la condición d...

Страница 9: ...vec ou sans capteur C Level flotteurs Modèles avec capteur C Level Modèles avec flotteurs 3x ou 4x Installer Friendly Series Installation and Operation Manual This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code NFPA 70 state and local electrical codes UL Type 4X enclosure s are for indoor or outdoor use Technical support service...

Страница 10: ... d alimentation du panneau de contrôle avant d installer ou d entretenir le capteur C Level les interrup teurs à flotteur ou les pompes dans le réser voir Le cas échéant cela pourrait entrainer un risque de choc électrique grave ou mortel ATTENTION Alimentation d entrée au disjoncteur Les flotteurs doivent bouger librement Ils ne doivent pas se toucher entre eux ni avec les équipements qui se trou...

Страница 11: ...teur ATTENTION Si le capteur C Level ou les interrupteurs à flotteur ne sont pas installés et raccordés correctement le système de pompes et l alarme ne fonction neront pas correctement 9 cm 3 5 po Positionnement du capteur C Level Garder l évent au dessus du niveau d eau collier de serrage 10 2 cm 4 po niveau minimal niveau de liquide mesuré à environ 0 cm 0 po depuis ce point 2 5 cm 1 po minimum...

Страница 12: ... paramètres du panneau de commande correspondant 3 Vérifiez que le panneau de contrôle fonctionne correctement après l installation Si le flotteur redondant d arrêt n est pas utilisé un fil de liaison doit être installé à sa place 2 Système d alarme sonnerie et témoin Lorsqu une alarme est déclenchée le témoin rouge s allume et la sonnerie retentit Si vous appuyez relâchez le commutateur TEST SILE...

Отзывы: