background image

 

1.

    Isolate the float by disconnecting one or both of the 

float leads from the float terminals.

2.

   Place one ohmmeter lead on one of the float wires, and 

the other ohmmeter lead on the other float wire.

3.

   Place the ohmmeter dial to read ohms and place on 

the R X 1 scale.  With the float in the “off” position, the 
scale should read infinity (high resistance).  Replace 
the float if you do not get this reading.  With the float 
in the ON position, the scale should read nearly zero 
(very low resistance).  Replace the float if you do not 
get this reading.

NOTE: Readings may vary depending on the length of wire 
and accuracy of the measuring device.

Fuses

Check the continuity of the fuse.  With power OFF, pull the 
fuse out of the fuse block.  With the ohmmeter on the R X 1 
scale, measure resistance.  A reading of infinity indicates a 
blown fuse and must be replaced.  Replace fuse with same 
type, voltage and amp rating.

Indicator Light

If defective, replace all indicator lights with same type.

Alarm Horn

Moving the test/nor-
mal/silence switch to 
the test position or 
activating the alarm 
float should turn on 
the alarm horn. If the 
horn does not sound, 
replace horn with same type.

Alarm Light

Moving the test/normal/silence switch to the test position 
or activating the alarm float should turn on the alarm light.  
If the light does not activate, replace light with same type.

Circuit Breaker (optional)

Check each pole of the circuit breaker for proper resistance 
reading using the following procedure.  

WARNING: Disconnect incoming power to panel.

1.

    Isolate the circuit breaker by disconnecting either line 

side or load side wires.

2.

   Place the ohmmeter leads across the corresponding 

line and load terminals of each pole.

3.

   With the ohmmeter on the R X 1 scale and the breaker 

in the OFF position, the reading should be infinity (very 
high resistance).  With the breaker in the ON position, 
the reading should be nearly zero ohms (very low resis-
tance).  If the readings are not as stated, replace the 
circuit breaker with one of the same ratings.

NOTE: Readings may vary slightly depending on the 
accuracy of the measuring device.

Float Controls

Check the floats during their entire range of operation.  
Clean, adjust, or replace damaged floats.

Checking the float resistance

 - The float resistance can 

be measured to determine if the float is operating correctly 
or is defective.  Use the following procedure to measure 
the float resistance.  

WARNING: Disconnect incoming power to panel.

 

Troubleshooting

For complete terms and conditions, please visit www.sjerhombus.com.

SJE Rhombus

®

 Five-Year Limited Warranty

NOTICE!

Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees 

will not be exposed to health hazards in handling said material.  All applicable laws and regulations shall apply.

Содержание 115

Страница 1: ...perate the pump and high level alarm functions Wide angle pump switch and SJE Double Float applications are illustrated on next page NOTE Options ordered may affect the number of floats and their functions Please reference the schematic provided with the control panel for proper installation Installation of Floats CAUTION If control switch cables are not wired and mounted in the correct order the ...

Страница 2: ... TO STEP 11 FOR INSTALLATION REQUIRING A SPLICE FOLLOW STEPS 6 10 Installation Instructions 6 Determine location for mounting junction box according to local code requirements Do not mount the junction box inside the sump or basin 7 Mount junction box to proper support 8 Run conduit to junction box Drill proper size holes for the type of conduit used Attach connectors to junction box 9 Identify an...

Страница 3: ... the liquid level travels beyond the pump switch or Double Float and reaches the alarm float the audio visual alarm will be activated The alarm horn can be silenced by moving the test normal silence switch to the silence position Alarm System Horn and Indicator When an alarm condition occurs a red light and a horn will be activated If the test normal silence switch is moved to the silence position...

Страница 4: ...ight does not activate replace light with same type Circuit Breaker optional Check each pole of the circuit breaker for proper resistance reading using the following procedure WARNING Disconnect incoming power to panel 1 Isolate the circuit breaker by disconnecting either line side or load side wires 2 Place the ohmmeter leads across the corresponding line and load terminals of each pole 3 With th...

Отзывы: