34

14. PROTECTIVE FUNCTION

Protective 
function

Description

Note / 
variable

Freeze 
protection

Static (output water 
temperature lower than 5°C)

If the indoor unit is connected to power 
supply, output water temperature 
is monitored. When it is lower then 5°C, 
so circulator and first stage of bivalent 
(2 kW) are switched ON. When temperature 
exceeds 5°C, protection is switched OFF. 
This protection is active also when heating / 
cooling is not switched ON. Protection is solid 
and works only when indoor unit is connected 
to power supply and breaker of technology 
is switched ON. Outdoor unit is not used.

During operation (adjustable 
in service access)

When during heating temperature become 
lower than set temperature (15°C default), 
outdoor unit is shut down. Output water 
heating takes over bivalent source. After 
exceeded output water temperature of 15°C, 
bivalent source continues in heating for 
another 30 minutes. Then heating control 
continues in the usual manner. This protection 
is mostly activated when defrost and water 
flow is insufficient (eventually when is low 
energy accumulated inside 

of 

system).

T freeze 
protect 
- service 
access

Error autoreset 
max. 5 times

Flow control

Flow monitoring by outdoor 
unit power

For compliance declared effectivity 
and ensuring safe operation sufficient water 
flow is necessary. Minimal water flow 
is defined by relationship among outdoor unit 
power and required power of circulator. 
Values of minimal water flow are in graph 

of minimal water flow for different types of 
units on page 32

.

Outdoor unit 
power 
- service 
access

Error autoreset 
max. 5 times

Critical flow monitoring
200 l / hr

If during circulator operation water flow falls 
below 200 l/hr (fixed value), critical error 
is signalized and automatic circulator bleeding 
program is started. Bleeding occurs

 

cyclically,10 seconds stop, 10 seconds 100% 
of power until water flow is restored.

Flow change during defrost 
and cooling

During defrost is water flow automatically 
increased to 100%. When cooling, circulator 
is not controlled proportionally, but always 
running at full capacity 100%.

Water pressure 
control

Heating / cooling water 
pressure control 
(adjustable in service access)

If water pressure falls below defined level, 
critical error is signalized and heat pump 
operating is stoped.

Min. water 
pressure 
- service 
access

Error autoreset 
max. 5 times

Содержание GSH-IRAD

Страница 1: ...USER S MANUAL AIR TO WATER HEAT PUMP GSH IRAD ...

Страница 2: ... Original instructions ...

Страница 3: ...after a certain time For floor heating be aware of delays thermal exchanges in the rooms due to changes in water temperature 3 6 hrs Nastavení Object section Displays mode of heating cooling object temp circulator state object state main switch operation heating cooling DHW section Displays temp of DHW DHW circulator state heating state main switch DHW heating Overview section Displays important t...

Страница 4: ...pe HP However efficiency is worse at this temperature COP decreases Heat pump can be also used for cooling At cooling mode is output water temperature limited to condensing temperature Heat pump is not suitable for cooling with water temperature under condensing temperature e g fancoil Low temperature water causes condensation on inner equipment of indoor unit and thereby the damage Suitable cooli...

Страница 5: ... there is a threat of a serious injury Do not impose air vaporing of the outdoor unit for a long time there is a threat of hypothermia Please follow the conditions set by standards EN 378 4 2008 art 6 5 All parts of the cooling device e g refrigerant oil filter dehydrator insulation material have to be recuperated recycled and or disposed in an ecological way in connection with maintenance repairi...

Страница 6: ...by a compressor and distributed to the condenser indoor unit Inside of plate condenser of indoor unit refrigerant condenses and it transfers the heat into heating medium heating water Thereafter condensed refrigerant goes into expansion valve and the cycle repeats itself 7 INSTALLATION The device has to be mounted by an authorized company otherwise the device can be damaged or an injury can be cau...

Страница 7: ...650 980 395 427 788 1345 572 900 412 378 340 1326 Outdoor unit GSH 70 80ERAD Outdoor unit GSH 110 130ERAD ...

Страница 8: ...is up to 50 C The refrigerant is under pressure There is a threat of a serious injury Do not try to connect the circuit on your own ARNING W 8 CONNECTING OF REFRIGER T A ION CIRCUIT Only authorized service can connect he refrigeration circuit see Installation ...

Страница 9: ...every meter height of the heating system Next it is necessary to bleed the circuit thoroughly The bleeding is done by the bleeding screw of the circuit pump or alternatively on the upper threaded piece of the board exchanger When the circuit pump is switched on the board exchanger shall be bled thoroughly After that its noise is decreased The circuit pump shall run for 10 minutes at least before t...

Страница 10: ...mperature of object bivalent source state and more Main screen summary Used for switch on off Heat pump DHW heating Displays the overview of most important values and allows entry to states and errors screen button More State errors and entry to screen of supplied power measure button More Calorimeter 10 Settings and service of regulator GSH IRAD Unity Color Basic controls For basic controls of th...

Страница 11: ...is interrupted Too low temperature of outdoor air For heating is fully used bivalent source internal electric heater Economic operation Displayed when output water temp is lower than 45 C and the power is lower than 50 DHW heating is blocked by time schedule Antilegionella DHW tank is heated by electric heater because of legionella disinfection e Status icons Meaning of text shortcuts Attenuation ...

Страница 12: ...opped below safe limits 2 Insufficient water flow water flow dropped below safe limits 3 Outdoor unit disorder 4 Low water pressure water pressure dropped below 0 9 Bar 5 Faulty temperature sensor MX communication unit 2 digit 1 2 Faulty output water temperature sensor 3 4 Faulty input water temperature sensor 3 digit 1 2 Faulty pool temperature sensor 3 4 Faulty secondary circuit temperature sens...

Страница 13: ... temperature stability without fluctuations In GSH IRAD heat pump are used two tools for comfort settings of equithermal curve 1 Neo Equitherm Automatic correction write down desired adjustment of heating water temperature without you have to think about which value and how much to change 2 IQ Equitherm Automatic fine tuning of equithermal curve by difference of required and actual temperature of ...

Страница 14: ...on must be set to ON pg 1 Required DHW temperature required DHW temperature recommended 44 48 C Required DHW hysteresis TUV required hysteresis define temperature difference when starts DHW heating DHW el heating delay define time to DHW heating by heat pump after this time is is DHW heated by electric heater and heat pump is used for object heating Disinfection switch ON OFF DHW tank disinfection...

Страница 15: ...me webserver login name Webserver password webserver login password Saved data heat pump operation saved data access is possible only from PC Network settings ethernet network connection settings pg 3 Service access access only for service engineer pg 1 Secondary source enable use of secondary source solid fuel boiler solar panel etc Secondary source tank temp actual temperature in secondary sourc...

Страница 16: ...er IP address of heat pump into your browser address bar The computer must be on the same physical Ethernet network If you want to control heat pump from the Internet network contact your internet provider The default IP address of a heat pump is 192 168 134 176 The username is eneore and password is eneore This address and other settings can be changed in the Settings in the heat pump controller ...

Страница 17: ...ute you have to contact yours heat pump supplier or apply for opening an account by email at info sinclair solutions com Sinclair Route is a paid service After paying a one time fee you will receive user name and password which is needed to insert to heat pump web server settings Settings Network settings IMPORTANT NOTICE That the Sinclair Route service is available is needed to router which is us...

Страница 18: ...r is very soft and could be damaged Before cleaning of exchanger switch off the main circuit breaker in inside unit The inside unit needs minimal maintenance Use a damp cloth for cleaning its top cover and follow caution if the heat pump is running and energized We recommend to do indoor unit maintenance outside the heating season Check an activity of circulator before the heating season Especiall...

Страница 19: ...y accumulated inside of system T freeze protect service access Error autoreset max 5 times Flow control Flow monitoring by outdoor unit power For compliance declared effectivity and ensuring safe operation sufficient water flow is necessary Minimal water flow is defined by relationship among outdoor unit power and required power of circulator Values of minimal water flow are in graph of minimal wa...

Страница 20: ...ard installation is not required to use At installations with often power cut is recommended to set compressor preheat Preheat comp service access Output water temperature limits Limitations of range of water temperature user settings default 20 to 60 C Minimal temperature of output water Maximal temperature of output water service access Compressor restart Compressor protection against frequent s...

Страница 21: ...t Mounting plates DIMENSIONS 650 mm 565 mm 305 mm A A 650 490 27 563 25 60 320 60 03 03 168 309 9 380 380 O 14 R 7 R 7 35 O 6 290 50 137 5 137 5 137 5 137 5 14 57 53 100 100 POSITION IS NOT USED COULD BE USED MIRROR ...

Страница 22: ...r 3 4 Faulty input water temperature sensor 3 digit 1 2 Faulty pool temperature sensor 3 4 Faulty secondary circuit temperature sensor 4 digit 1 2 Faulty outdoor temperature sensor 3 4 Faulty object temperature sensor 5 6 Faulty DHW temperature sensor 7 8 Faulty accumulatice tank temperature sensor First two digits from left indicate critical error in which is heat pump operation stopped or limite...

Страница 23: ......

Страница 24: ...al station is located INFORMATION CONCERNING USED REFRIGERANT MEDIUM This unit is containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personel Type of refrigerant R410A The composition of the cooling medium R410A 50 HFC 32 50 HFC 125 The quantity of the refrigerant please see the unit label The value GWP 2088 GWP Global W...

Отзывы: