Only for cooling and heating unit
Unscrew the fixing nut of the four-way valve coil
and remove the coil. Wrap the four-way valve with
wet cotton and unsolder the 4 weld spots con-
necting the four-way valve to take it out. Welding
process should be as quick as possible and keep
wrapping cotton wet all the time. Be sure not to
burn out the lead-out wire of compressor.
10. Disassemble Four-way Valve
Weld spots
Four-way Valve
11. Disassemble Capillary
Unsolder the weld spots of capillary,valve and
outlet pipe of condenser to remove the capillary.
Prevent welding slag from blocking the capillary.
12. Disassemble Compressor
U n s o l d e r t h e p i p e l i n e c o n n e c t i n g t h e
compressor, and then unscrew the 3 foot-nuts
fixing conpressor to remove it.