to the stipulated power supply specifications. No joint of wires is allowed.
Upon completion of wire connection, double check it and then connect the power supply.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a
residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed
wiring according to the national rule.
The appliance shall be installed in accordance with national wiring regulations.
5.2 Specifications of power supply
Model
ASE-150AH
ASE-190AH
Power
380-415V~, 3Ph, 50Hz
380-415V~, 3Ph, 50Hz
Switch capacity of the main
power supply / Fuse
70A/50A
70A/50A
Outdoor unit power cable
includes grounded wire
5x16mm
2
5x16mm
2
Connective wire of indoor and
outdoor unit
4x1.0mm
2
4x1.0mm
2
30
Содержание ASE-150AH
Страница 1: ...SERVICE MANUAL ASE 150AH ASE 192AH CONDENSING UNITS...
Страница 2: ......
Страница 3: ...Content General information 2 Outdoor Unit 53 Installation 65 Controller 113 1...
Страница 4: ...General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 3 3 Nomenclature 4 2...
Страница 6: ...Outdoor unit ASE 150AH ASE 192AH 4...
Страница 7: ...Refrigerant circuits 5...
Страница 11: ...ASE 150AH Top view ASE 192AH 2 Dimensions Unit mm 9...
Страница 13: ...ASE 150AH 4 Wiring Diagrams 11...
Страница 14: ...ASE 192AH 12...
Страница 20: ...The distance of the foundation bolt is shown in following picture Unit mm ASE 150AH ASE 192AH 18...
Страница 40: ...Communication error Condenser temperature sensor error Ambient temperature sensor error 38...
Страница 41: ...System low pressure protection Three times low pressure protections within 1 hour 39...
Страница 42: ...System high pressure protection 40...