just touches the chamfered retaining wall.
Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/2 hex flat). Cap must be
replaced to prevent leaks.
Never attempt to repair any brazed connections while the system is under pressure. Personal
injury could result.
After the pipes between the indoor unit and the outdoor unit are connected, replenish
compressed nitrogen to perform airtight test.
The airtight test is performed by using the compressed nitrogen, 2.94MPa (30kg/cm
2
G).
Leak test with a bubble type leak detector. Do not use the system refrigerant in the outdoor
unit to purge or leak test.
Tighten the spool of the low pressure valve and high pressure valve before compressing the
nitrogen.
Compress the nitrogen at the air vent of the gas valve.
The low pressure valve and high pressure valve are closed in the process of compressing
the nitrogen.
Do not
use oxygen, flammable gas or toxic gas in the airtight test.
Vacuum
Length of connective pipe
(Single pass)
Procedure of expelling air
Less than 5m
Use refrigerant in the outdoor unit.
5~15m
Use vacuum pump or refrigerant tank.
Note: If the air conditioner is relocated, be sure to use a vacuum pump or refrigerant tank to expel air.
Use the refrigerant in the outdoor unit to expel air.
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover of valves A and B, rotate the square-head
24
Содержание ASE-150AH
Страница 1: ...SERVICE MANUAL ASE 150AH ASE 192AH CONDENSING UNITS...
Страница 2: ......
Страница 3: ...Content General information 2 Outdoor Unit 53 Installation 65 Controller 113 1...
Страница 4: ...General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 3 3 Nomenclature 4 2...
Страница 6: ...Outdoor unit ASE 150AH ASE 192AH 4...
Страница 7: ...Refrigerant circuits 5...
Страница 11: ...ASE 150AH Top view ASE 192AH 2 Dimensions Unit mm 9...
Страница 13: ...ASE 150AH 4 Wiring Diagrams 11...
Страница 14: ...ASE 192AH 12...
Страница 20: ...The distance of the foundation bolt is shown in following picture Unit mm ASE 150AH ASE 192AH 18...
Страница 40: ...Communication error Condenser temperature sensor error Ambient temperature sensor error 38...
Страница 41: ...System low pressure protection Three times low pressure protections within 1 hour 39...
Страница 42: ...System high pressure protection 40...