3

Instructions of Unit Installation          Installation of Connecting Pipe 

 

(2) 

Use thermal insulation tape to wrap the pipes from the bottom of the outdoor unit until the 
upper end of the pipe where the pipe enters the wall. When wrapping thermal insulation tape, 
the later circle of tape must cover half of the front circle of tape (Refer to Figure 42).

 

(3) 

Wrapped pipe must be fixed to wall using pipe clamps.

 

 

Caution:

 

(1) 

Do not wrap the protective tape too tight, and otherwise the efficiency of thermal insulation 
may be decreased. Ensure that the condensate drainage flexible tube is separate from the 
bundled pipes.

 

(2) 

After the protective work is completed and the pipes are wrapped, use seal material to block 
the hole in the wall, so as to prevent rain and wind from entering the room.

 

Position and Method of Installing Wire Controller

 

1.  One end of the control wire of the 

wire

 controller is connected with main board of electric box of 

indoor unit inside, it should be tightened by wire clamp, the other end should be connected with the 

wire

 controller (installation sketch map as shown in below). The control wire be used for the 

indoor unit and 

wire

 controller, which is special, the length is 8 meters, 

the material be adopted for the control wire should be metallic substance. The 

wire

 controller 

could not be disassembled and the 

control

 wire be used for the 

wire

 controller should not 

be changed by users optionally, the installation and maintenance should be carried out by the 
professional personnel. 

2.  First select an installation position. According to the size of the 

control wire

 of the wire 

controller, leave a recess or a embedded wire hole to bury the 

control wire

3. 

If the 

control wire

 between the wire controller and the indoor unit is

surface-mounted, use 1# metallic pipe and make matching recess in the wall (refer to Figure 4

3

; If 

concealed installation is adopted, 1# metallic pipe can be used (Refer to Figure 4

4

).

 

4. 

No matter if surface mounting or concealed mounting is selected, it is required to drill 2 holes (in the 
same level) which distance shall be the same as the distance (60mm) of installation holes in the 
bottom plate of the wire controller. Then insert a wood plug into each hole. Fix the bottom plate of the 
wire controller to the wall by using the two holes. Plug the 

control wire

 onto the control panel. 

Lastly install the panel of the wire controller.

 

Caution:

 

During the installation of the bottom plate of the wire controller, pay attention to the direction of the 
bottom plate. The plate’s side with two notches must be at the lower position, and otherwise the panel of 
the wire controller cannot be correctly installed.

 

Содержание ASDU-09A

Страница 1: ...USER S MANUAL ASDU 09A ASDU 12A ASDU 18A ASDU 24A UNI ON OFF SERIES ASDU 36A ASDU 42A ASDU 48A ASDU 60A ducted units ...

Страница 2: ...Thanks for your selection of Sinclair Ducted Air Conditioning Unit Before use please read this instruction manual carefully and keep it properly to ensure correct use of this machine ...

Страница 3: ...sor Setting 16 Installation Dimension of Indoor Unit 20 Installation of Outdoor Unit 22 Precautions on Installation of Indoor Unit and Outdoor Unit 24 Indoor Unit Level Inspection and Air Duct Installation 24 Installation and Test of Condensing Water Pipe and Selection of Connecting Pipe 26 Installation of Connecting Pipe 27 Position and Method of Installing Wire Controller 29 Connection of Cables...

Страница 4: ...oner The appliance shall not be installed in the laundry Before installation please check the power supply for compliance with the ratings on nameplate Check the power safety as well Operating by professinal Before use please check and confirm if the cables drainage pipes and pipelines are correctly connected hence to eliminate the risk of water leakage refrigerant leakage electric shock or fire M...

Страница 5: ...ing status display 4 Energy savingstatus display 5 Set temperature display 6 Ambienttemperature display 7 Fresh air status display not supplied 8 Mode cooling dehumidifying fan heating auto 9 Failure status display 10 Sleep status display 11 Mode key 12 Set temperature increase key 13 Set temperature decrease key 14 Fan speed key fresh air setting 15 Sleep key outdoor environmenttemperature check ...

Страница 6: ...g key to decrease the set temperature whenpressing the keys once the temperature shall increase or decrea se by1 C NOTE key lock function whenthe and key arepressed simultaneously for 5 second the set temperature indicatingarea shall display EE and all keys response shall be shut off press the two keys simultaneously for 5 second again the key lock function shall be relea sed When the wire control...

Страница 7: ...oduce cooling effect but shall only operate under Fan mode When the unit operates under Dehumidifying mode DRY shall be displayed Now the interior fan shall operate in the manner of low speed air supply within a certain range of temperatures The dehumidifying effect of this mode is better than that of the Cooling mode and saves more energy When the unit operates under Heating mode HEAT shall be di...

Страница 8: ...THE LAST KEY INPUT AND THE NORMAL SHUTOFF STATUS INTERFACE SHALL BE DISPLAYED FTER THE ABOVE SETTINGS ARE COMPLETED THE SYSTEM SHALL DISPLAY h3 6 v OW THE SET TEMPERATURE SHALL NOT EXCEED THE TEMPERATURE RANGE OF THE ENERGY SAVING SET TING BEFORE OR EXAMPLE THE LOWER COOLING LIMIT IS SET AS AND THE UPPER COOLING LIMIT IS SET AS FOR THE ENERGY SAVING TEMPERATURE SETTING IN SO THE COOLING TEMPERATUR...

Страница 9: ...L MEANS THE OPERATING STATUS OR SHUTOFF STATUS SHALL NOT BE MEMORIZED 0RESS THE h v KEY TO STORE THE SET VALUE AND EXIT THE SETTING EBUG UNCTION 7HEN THE UNIT IS SHUT OFF PRESS THE h v KEY AND THE h3 0v KEY SIMUL TANEOUSLY TO ACTIVATE THE DEBUG MENU OW THE DISPLAYS h 5 v 0RESS THE h v KEY TO SELECT SETTING ITEM AND USE THE KEY OR THE KEY TO SET ACTUAL VALVE 3ETTING OF MBIENT 4EMP 3ENSOR 5NDER THE ...

Страница 10: ...e F0 Failure of Indoor Room Sensor at Air Intake E1 Compressor High Pressure Protection F1 Failure of Evaporator Temp Sensor E2 Indoor Frost Proof Protection F2 Failure of Condenser Temp Sensor E3 Compressor Low Pressure Protection F3 Failure of Outdoor Ambient Sensor E4 Compressor Exhaust High Temperature Protection F4 Failure of Exhaust Temp Sensor E5 Compressor Overheat F5 Failure of Indoor Roo...

Страница 11: ...ler can be as far as 8 meters Never drop or throw at will the remote controller Never let any liquid enter the remote controller Avoid direct sunshine over the remote controller Do not place the remote controller in an extremely hot place Precautions Press FAN button set fan speed Press TEMP button set suitable TEMP Press MODE but ton to set operation mode Plug in press ON OFF button then air cond...

Страница 12: ...perature key to adjust the set temperature for the room Under the heating mode the unit has the functions of preventing cold air supply and supplying remaining heat After the startup of the compressor the indoor fan shall start operation when the evaporator temperature is larger or equals 35 or after the unit has be started for 45 secon ds so as to avoid supply of cold air shortly after the unit i...

Страница 13: ...f you press the ON OFF key b Press the mode key and select the mode c Press the temperature key and set the temperature as required Fan Mode Operation Connect the unit to power supply Press the ON OFF key Press the MODE key to select FAN mode The unit shall operate under FAN mode Press the FAN key to select from high medium and low speed a After the unit is connected to power supply the air condit...

Страница 14: ...etter codes of all functions The life of batteries is about 1 year Do not mix new and old batteries or mix different types of batteries in usage If the remote controller shall not be used for a long time take out the batteries to avoid liquid leakage and any subsequent failure Load two AAA batteries Accessories ...

Страница 15: ...alized controller weekly timer The weekly timer has the function of invalidating the lower unit The weekly timing fun ction is able to realized four timing ON OFF periods for any unit every day so as to achieve fully automatic operation This WEEKLY TIMER adopts 485 mode to communicate with manual control of every duct type unit and it can control up to 16 units Adopting 2 core twisted pair wire th...

Страница 16: ...s know your requirement before your placing the order for this WEEKLY TIMER will only be prepared when customer orders communication joint with WEEKLY TIMER on manual control had been prepared 1 Press or to select the unit that needed to be control It is available to control several units by Group Control 1 16 or control single unit by Single Control 2 When selected a certain or several units by S...

Страница 17: ...ergy savingstatus display 5 Set temperature display 6 Ambienttemperature display 7 Fresh air status display not supplied 8 Mode cooling dehumidifying fan heating auto 10 Sleep status display 11 Mode key 12 Set temperature increase key 13 Set temperature decrease key 14 Fan speed key fresh air setting 15 Sleep key outdoor environmenttemperature check 16 Timing key 17 ON OFF key Composition of wire ...

Страница 18: ... timer No matter the unit is turned on or turned off press TIMER button enter into Timer setting then use the buttons to select the time As shown In Fig 15 the setting time Fig 16 or cancel setting Fig 17 Then press Timer Button enter into each item setting Wire controller with week timer function No 1 No17 is the same as front instructions of No18 No 19 fig 15 fig 16 SEG SEG 17 ...

Страница 19: ...re are figure blink it can be set up finally press the ON OFF button complete the setting and quit the timer data will be save Fig 18 19 If entered into Timer setting by pressing the Mode button to select the setting item Day Monday to Sunday Hours 0 23 or Minutes 0 59 By pressing buttons to adjust the setting items then press Timer button to confirm or press the Timer button once more to cancel t...

Страница 20: ...ressing buttons to select Week then press the Timer button to confirm at this time dd will display or press Timer button to cancel the selected day at this time dd will not display At last press ON OFF button complete setting and quit Fig 21 19 ...

Страница 21: ...nce of users before going out Refer to the section of wire controller instructions for detailed operation Outdoor Room Sensor Outdoor Side Indoor Side Fig 23 This series of ducted air conditioning unit has two indoor room sensors One is located at the air intake of the indoor unit and the other one is located inside the wire controller User can select one from the two indoor room sensors on the ba...

Страница 22: ...into effect at any time and features very simple operation Refer to the section of wire controller instructions for detailed operation Fresh Air Air Supply Pipe Air Intake Pipe Air Valve Outdoor Fresh Air Indoor Side Before startup the unit please remove all the sealing film on the healthy filter block Fig 24 4 The head of delivery of the condensate drainage pump can reach 1 1m so that the enginee...

Страница 23: ...ons of Indoor Unit Air Intake Drainage Pipe Electric Box G as Pipe Liquid Pipe Air Intake F I Fig 26 B F D C A G H I J Drainage Pipe Gas Pipe Liquid Pipe Electric Box Air Intake E Be suit for ASDU 24A ASDU 36A ASDU 42A ASDU 48A Fig 27 Be suit for ASDU 09A ASDU 12A ASDU 18A 22 ASDU 60A ...

Страница 24: ... a G e p i P Pipe Drainage r e t u O e p i P Diameter Wall Thickness ASDU 09A 3 8 ASDU 12A 856 571 515 790 913 680 750 100 172 220 1 4 1 2 ф 20 1 5 ASDU 18A 932 627 738 894 1012 736 738 125 207 266 1 4 1 2 ф 30 1 5 Dimension Requirement of the Installation Space of Indoor Unit Fig 28 Nut with Washer Nut Spring Washer Be suit for ASDU 09A ASDU 12A ASDU 18A 23 Warning The height of installation for ...

Страница 25: ...l l a t s n i e h T d o o g e v a h t s u m e t i s o s n o i t a l i t n e v t a h t r o o d t u o e h t t i n u n a c e k a t n i d n a exhaust e r u s n E r i a h g u o n e t a h t s i e r e h t d n a e k a t n i r i a e h t r o f e l c a t s b o o n t s u a h x e f o e h t r o o d t u o e r e h t f I t i n u g n i k c o l b e l c a t s b o y n a s i e h t e k a t n i r i a r o t s u a h x e t ...

Страница 26: ...rovide enough space for the service and maintenance 5 The installation site must be far away from heat source leakage of inflammable gas or smoke 6 The indoor unit is of ceiling mount indoor unit is hidden inside the ceiling 7 The indoor and outdoor units the power cable and the connecting electrical lines must be at least 1 meter from any TV set or radio This is to avoid image interference or noi...

Страница 27: ...pport Place the unit at the beam and fix it Level Check of the Indoor Unit After the indoor unit is installed it is required to check the level of the whole unit The unit must be placed horizontally but the condensate pipe shall be installed obliquely so as to facilitate the drainage of condensate Air Supply Air Intake i Condensate Drainpipe Level Instrument Enlarged View Condensate Drainpipe As t...

Страница 28: ... an inclining angel of 5 10 so as to facilitate the drainage of condensate The joints of the Drainage Pipeline must be covered by thermal insulation materials to avoid generation of exterior condensate As shown in Figure 37 2 A Drainage outlet is located at both the left and right sides of the indoor unit After selecting one Drainage outlet the other outlet shall be blocked by rubber plug Bundle t...

Страница 29: ...120g m ASDU 48A ASGE 48A ASDU 24A ASGE 24A ASDU 36A ASGE 36A ASDU 42A ASGE 42A ASDU 09A ASGE 09A ASDU 12A ASGE 12A ASDU 18A ASGE 18A Gas Pipe Liquid Pipe Max Pipe Length m Amount of Additional Refrigerant to be Filled For Extra Length of Pipe Note 1 The standard pipe length is 5m When the length L of the connecting pipe is less than or equals 5m there is no need to add refrigerant If the connectin...

Страница 30: ...ing the fitting pipes 4 Use sponge to wrap the connecting pipe and joint Then use plastic tape to bundle the sponge 5 Remove the bonnets of the liquid valve and the gas valve 6 Use an inner hexagon spanner to turn the spool of the liquid valve for 1 4 circle At the same time use a screwdriver to lift the spool Then there is discharge of gas 7 Refrigerant gas shall appear after the gas is discharge...

Страница 31: ...ng Pipe 1 To avoid generation of condensate on the connecting pipe and avoid leakage the big pipe and the small pipe of the connecting pipe must be covered by thermal insulation materials be bundled by adhesive tape and be isolated from air 2 The joint connecting to the indoor unit must be wrapped by thermal insulation material There shall be no gap between the connecting pipe joint and the wall o...

Страница 32: ...d for the control wire should be metallic substance The wire controller could not be disassembled and the control wire be used for the wire controller should not be changed by users optionally the installation and maintenance should be carried out by the professional personnel 2 First select an installation position According to the size of the control wire of the wire controller leave a recess or...

Страница 33: ... Figure 43 Surface Mounting of Cable Figure 44 Concealed mounting of Cable Figure 45 Schematic Diagram of Installation No Name 1 Wall Surface 2 Bottom Plate of Wire Controller 3 Screw M4X10 4 Panel of Wire Controller Caution 1 The communication distance between the main board and the wire controller is 8 meters 2 The wire controller shall not be installed in a place where there is water drop or la...

Страница 34: ...of the multiple twisted wires 4 Put the screw through the terminal of the multiple twisted wires and fix the terminal at the terminal board Warning If the power supply flexible line or the signal line of the equipment is damaged only use special flexible line to replace it 1 Before connecting lines read the voltages of the relevant parts on the nameplate Then carry out line connection according to...

Страница 35: ... 2 Air conditioning unit with 3 phase power supply 1 Remove the front side panel of the outdoor unit 2 Attach rubber ring to the cable cross hole of the outdoor unit 3 Pass the cable though rubber ring 4 Connect the power cable to the terminal earthing marked L1 L2 L3 N 5 Use cable fastener to bundle and fix the cable Connect wire to the earthed terminal screw on the electric box Connection of Sig...

Страница 36: ...diagram the signal wire between indoor and outdoor unit shall be installed in the shielded bushing Schematic Diagram of Unit Line Connection ASGE 24A ASGE 09A ASGE 12A ASGE 18A ASDU 09A ASDU 18A ASGE 36A ASDU 36A ASGE 42A ASDU 42A ASGE 48A ASDU 48A ASDU 24A utdoor nit ndoor nit 2 5mm 2 utdoor nit ndoor nit 4 5 N 2 N 2 Communication Cords Communication Cords ASDU 12A ASGE 60A ASDU 60A ...

Страница 37: ...indered 4 There is refrigerant leakage 5 The outdoor ambient temperature is lower than 5 6 Control line is abnormal 1 There is obstacle in front of the condenser Note After carrying out the check of the above items and taking relevant measures to solve the problems found but the air conditioning unit still does not function well please stop the operation of the unit immediately and contact the loc...

Страница 38: ... see if the line connection is in good condition Operating by the professional Check if there is any word displaying on the LCD of the wire controller after connecting the unit to power supply Note If there is any abnormal condition ask aftersales personnel to offer guidance 3 Maintenance at the End of the Operational Season 1 When the weather is clear operate the unit under fan mode for half a da...

Страница 39: ...rresponding to standard external static pressure The parameters are subject to change with the improvement of products in which case the values on nameplate shall prevail Appendix Air conditioner nominal working condition and working range Note Indoor side Outdoor side Test condition DB WB DB WB Nominal cooling 27 19 35 24 Nominal heating 20 7 6 Rated cooling 32 23 48 Low temp cooling 21 15 18 Rat...

Страница 40: ...ANT CHARGE Pursuant to Regulation EC 842 2006 on certain fluorinated greenhouse gases in case of extra refrigerant charge it is compulsory to Fill in the label accompanying the unit inserting the factory quantity of refrigerant charge see the technical label the extra refrigerant charge and the total charge Apply the label next to the technical label applied on the unit For the split type air cond...

Страница 41: ...This product must not be disposed together with the domestic waste This product has to be disposed at an authorized place for recycling of electrical and electronic appliances 66175219 ...

Отзывы: