Unit Installation Instructions
Inspection of Level of Indoor Unit,
Fabrication of Backwater Elbow
Precautions for unfavorable installation:
1.
The preparation of all pipes (connecting pipes and drainage pipes) and cables (connecting lines of
wire controller, indoor unit and outdoor unit) must be ready before the installation, so as to achieve
smooth installation.
2.
Drill an opening on the ceiling. Maybe it is required to support the ceiling to ensure the evenness of it
and avoid the vibration of it. Consult with the user or a construction company for details.
3. In case the strength of ceiling is not enough, use angle iron sections to set up a beam support. Place
the unit at the beam and fix it.
Level Check of the Indoor Unit
After the indoor unit is installed, it is required to check the level of the whole unit. The unit must be placed
horizontally, but the condensate pipe shall be installed obliquely, so as to facilitate the drainage of
condensate.
Air Supply
Air Intake
i
Condensate
Drainpipe
Level Instrument
Enlarged View
Condensate Drainpipe
As the inside of the unit is in
the negative pressure status, it
is required to set up a
backwater elbow. The
requirements is:
A=B
≥
P/10+20(mm)
P is the absolute pressure
inside the unit. The unit of the
pressure is Pa.
Fig. 35
Installation of Rectangular Air Pipe
Air Supply
Air Intake
No. Name
No.
Name
1
Hanger
5
Filter
2
Air Intake
Pipe
6
Main Air
Supply Pipe
3
Canvas Air
Pipe
7
Air Supply
Outlet
4
Air Intake
Ceiling Mount
Air Supply
Air Intake
Fig. 36
2
6