Unit Installation Instructions Installation of Condensate Pipe
Testing of Drainage System
(1)
After the electrical installation is completed, carry out the testing of the drainage system.
(2)
During the test, check if the water correctly flows through the pipelines. Carefully
observe the joints to ensure that there is no leakage. If the unit is to be installed in a new
house, carry out testing before decorating the ceiling.
Selection of Connecting Pipe
Size of Fitting Pipe
(Inch)
Item
Model
Max. Height
Difference
between
Indoor Unit
and Outdoor
Unit m
3/8
1/2
1/4
20
15
30g/m
5/8
3/8
30
15
60g/m
3/4
1/2
50
30
120g/m
ASDU-48A ASGE-48A
ASDU-24A ASGE-24A
ASDU-36A ASGE-36A
ASDU-42A ASGE-42A
ASDU-09A ASGE-09A
ASDU-12A ASGE-12A
ASDU-18A ASGE-18A
Gas Pipe
Liquid
Pipe
Max.
Pipe
Length
(m)
Amount of Additional
Refrigerant to be
Filled (For Extra
Length of Pipe)
Note
:
1
The standard pipe length is 5m. When the length (L) of the connecting pipe is less than or equals 5m,
there is no need to add refrigerant. If the connecting pipe is longer than 5m, it is required to add
refrigerant. In the above table, the amounts of refrigerant to be added for the models are listed for each
additional meter of pipe length.
2. The pipe wall thickness shall be 0.5-1.0 mm and the pipe wall shall be able to withstand the pressure of
6.0 MPa.
3.The longer the connecting pipe, the lower the cooling effect and the heating effect.
28
ASDU-
60
A ASGE-
60
A