MultiTox : DGi-TT7-E/O & DG-TT7-S

 

Page 6 / 60

 

NOSP 16452-05    (08/2016)

 

1.

 

PRODUCT DESCRIPTION 

The DGi-TT7-E is designed to monitor poisoning risk induced by the presence of toxic gases 
or vapours (hydrogen sulphide, carbon monoxide, ammonia...).  

The  DGi-TT7-O  is  designed  to  monitor  the  oxygen  concentration  in  %vol  either  for  inerting 
(scales 1 or 5%vol.) or in breathable atmosphere control (Scale 0-25%vol).  

Both versions are equipped with electrochemical cells. 

The DGi-TT7-S is designed to monitor poisoning risk induced by the presence of toxic gases 
or vapours, such as hydrogen sulphide. This version is equipped with semiconductor cells. 

Detectors can be connected to a large range of controllers or PLC. 

These  detectors  may  be  configured  using  the  portable  communication  terminal  (TLU600), 
providing flexibility to the user. 

Thus, calibration and maintenance operations can be undertaken by a single operator. 

MultiTox  are  also  available  for  use  in  an  addressable  network  system  with  distributed 
intelligence  SYNTEL.  For  more  information,  please  refer  to  the  Syntel  module  interface 
operating manual. 

1.1.

 

Application 

The  DGi-TT7  and  DG-TT7  are  suitable  for  indoor  or  outdoor  use  and  offer  a  fast  response 
time. Typical applications include: 

 

 

Storage of toxic products 

 

Monitoring of processes with toxic products 

 

Oxygen detection in inert atmosphere (DG-TT7-O) 

 

Chemical and petrochemical plants 

 

Drilling platforms 

 

Refineries 

 

 

Содержание MultiTox DG-TT7-S

Страница 1: ...Operating Manual NOSP 16452 05 03 2018 MultiTox Detector MultiTox DGi TT7 E DGi TT7 O DG TT7 S...

Страница 2: ...MultiTox DGi TT7 E O DG TT7 S Page 2 60 NOSP 16452 05 08 2016...

Страница 3: ...aintenance of this product The product may not perform as designed if not used or maintained in accordance with the manufacturer s instructions The warranty made by Simtronics with respect to the prod...

Страница 4: ...17 4 3 Electric Connection 20 4 4 Detection cartridge 26 5 Commissioning 27 5 1 Visual inspection 27 5 2 Power up 27 5 3 Operational tests 27 6 Operation 28 6 1 Environmental conditions 28 6 2 Inhibi...

Страница 5: ...and confidentiality 46 10 Warranty 46 11 CERTIFICATIONS AND STANDARDS 47 11 1 Product standards 47 11 2 Approvals 47 11 3 Marking 48 12 Accessories and spare parts 49 12 1 Accessories 49 12 2 Spare p...

Страница 6: ...th semiconductor cells Detectors can be connected to a large range of controllers or PLC These detectors may be configured using the portable communication terminal TLU600 providing flexibility to the...

Страница 7: ...mosphere 1 4 DG TT7 S Le DG TT7 S is a MultiTox detector based on a transducer with semi conductor cells which requires oxygen to function properly It is used mainly for hydrogen sulphide detection in...

Страница 8: ...TLU600 A colour coded cartridge with a label located in the lower part of the detector a green one for the toxic gas detectors with electrochemical cell DGi TT7 E a blue one for the oxygen deficiency...

Страница 9: ...device the cartridges must be stored in their original packaging until commissioning For a long term storage the cartridges will be stored in a dry place between 0 C and 20 C After a long storage per...

Страница 10: ...efer to gas matrix Measurement range Refer to gas matrix Type XV UVIR2 XT IR3 XW UV Detection range A0 Standard range B0 Long range Input Type 0 Not used or flame E Electrochemical S Semi conductor K...

Страница 11: ...T6 S A 20 B 23 C 24 D 25 E 27 F 30 become obsolete to release R association Options M Special version MarED TX6 and TV6 in type A only N Special version with ALRM LED not memorized not in compliance w...

Страница 12: ...ull scale 20 mA 105 full scale 20 8 mA Fault or inhibition 2 mA Version A 0 22mA 4 20mA with several fault levels for PLC and some recent control units 0 full scale 4 mA 100 full scale 20 mA 105 full...

Страница 13: ...densing version DG TT7 S Protection IP66 RFI EMI EN 50270 Heating time 60 sec to 120 sec depending on the version Stabilization time stabilization time 1st implementation or up to 24h after being powe...

Страница 14: ...Safety fraction failure T1 12 mois 91 4 PFD Probability of failure on Demande 2 80x10 3 PFH Probability of failure h 1oo1 6 34x10 7 MTTR Mean Time To Repair Fault on cartridge 16 min Fault on Detector...

Страница 15: ...MultiTox DGi TT7 E O DG TT7 S Page 15 60 NOSP 16452 05 08 2016 Figure 2 Outline drawing mm...

Страница 16: ...pm 10 reading 25 ppm 10 reading 15 ppm 10 reading 50 ppm 5 reading Shelf life months 12 18 24 60 24 36 36 24 24 24 24 24 18 Warming up time or polarisation 10 min 10 min 60 min 10 min 10 min 60 min 10...

Страница 17: ...e height is determined by the density of gas to detect Generally speaking a detector will not be placed in front of an air inlet which brings clean air This height may be adjust to take into account t...

Страница 18: ...ower rings It is possible to set up a suspension cable not supplied between the base and the housing at the lower part with two threaded holes M4 x 6 4 2 2 Cable s inputs as an option Connection cable...

Страница 19: ...nication using the TLU 600 Communication elements are located above the display The orientation enables a communication with an horizontal angle about 35 an vertical up angle about 30 and a vertical d...

Страница 20: ...areas and NF C 15 100 Other cables can be used if they are compliant with the local regulations and standards The table below shows the maximum cable lengths in meter ft based on the wire cross secti...

Страница 21: ...Type C also allows the detector to get a HART output as an option superimposed to the output current The current output format follows the same logic as the one described above but the product code c...

Страница 22: ...round It is recommended to use a yellow green wire with a ring lug minimum diameter 1 5 mm The armour of the power cable is normally connected to the ground of the detector but it may depend on site p...

Страница 23: ...e loop L and L is optically isolated from the detector 4 20mA or 0 22mA input module of the PLC has to power up the current loop with at least 8V at the terminal level for 22 mA This reduces the resis...

Страница 24: ...her and from other parts of the detector The two relays can be activated on one or more states of the detector as shown below Activated on Relay 1 Alarm Relay 2 Fault Comments Alarm Normally Open 4 po...

Страница 25: ...erminal should be performed thanks to 3 wire shielded cables The connection of power supply wires 4 on side A and 4 on side B Two red wires on V 24 V Two white wires on V 0 V Connection of the media w...

Страница 26: ...DGi TT7 E and DGi TT7 O versions these operations can be performed when powered On DG TT7 S version these operations imperatively require power to be off Loosen the locking screw on the side of the n...

Страница 27: ...tichannel detection unit or the Programmable Logic Controller The backlight turns violet The display red appears It displays among other information the INH which indicates the start up inhibition and...

Страница 28: ...me vapored products as silicone Moreover an exposure in area with a low rate of hygrometry for several hours can temporarily damage the sensitivity In order to retain stability of the factory span cal...

Страница 29: ...y as the maintenance inhibition this mode will lead to a purple switch of the backlight 6 3 Signal current loop State 4 20 mA 0 22 mA Display TLU state Line fault 0 0 0 0 Configuration fault 2 0 2 0 D...

Страница 30: ...hich is usually recorded in the display cycle are not provided anymore in order to keep the detection and current alarm level as a priority If the alarm memorization is enabled the backlight remains r...

Страница 31: ...the device IN CASE OF ALARM the display of concentration flashes alternation with AL1 or AL2 depending on the levels IN CASE OF DEFAULT The display shows DEF IN CASE OF INHIBITION The display shows I...

Страница 32: ...s When a device is in communication mode with the TLU its background light flashes It enables the user to ensure he communicates with the requested device The TLU600 menu is composed of 2 access level...

Страница 33: ...tions change depending on the fields displayed above each key Standard functions Scroll function next screen ESC Exit the current menu and return to the previous one CHG Changing displayed value VAL V...

Страница 34: ...This level enables access to the information and the status of the detectors It does not allow the configuration operations or write access Maintenance The access to the parameters and other maintena...

Страница 35: ...f activated alarm levels List of eventual faults press F1 key to scroll through the list Possibility to acknowledge alarms 6 7 3 1 ALRM Alarm screen Allows setting of levels and alarms acknowledgement...

Страница 36: ...enables the acknowledgement of the stored alarms The alarm can be acknowledged only if the alarm condition has disappeared 6 8 1 2 Inhibition End of inhibition The inhibition called permanent inhibit...

Страница 37: ...ck to main screen Use the setting menu and validate the INH command for acknowledgement Press F4 key to stop communication between TLU600 610 and the detector With DG TT7 S versions if the environment...

Страница 38: ...e measurement a 60 minutes clean air recovery is considered as a minimum interval This interval increases up to 90 minutes if the gas exposure has been about 5 minutes and extended to at least 2 hours...

Страница 39: ...MultiTox DGi TT7 E O DG TT7 S Page 39 60 NOSP 16452 05 08 2016...

Страница 40: ...ed with the real concentration 6 8 4 2 Label and zone sub menu This menu allows label and zone s modification After selecting a label or a zone the modification function operates in the same manner Th...

Страница 41: ...detector is in normal operation conditions Test of the relay and current outputs 6 9 1 TEST sub menu 6 9 1 1 Relay menu This menu gives access to activation or deactivation of the relays The detector...

Страница 42: ...HART terminal can read these information and send commands The use of a DD Device Descriptor facilitates the interface Man Device It can be uploaded on our website The HART output is an option It is a...

Страница 43: ...requirements 8 1 1 Preventive maintenance A test is recommended every four months for the DGi TT7 E or DGi TT7 O versions and every six months for the DG TT7 S version Run a calibration if necessary...

Страница 44: ...sor drift the measure is below 10 Non memorized fault Automatic acknowledgement when the measure goes back above 10 Resetting the zero point is necessary CALIB_FAULT Calibration fault Calibration rese...

Страница 45: ...replace the complete detector the easiest way is to take off the main housing from the base of the detector for more details refer to 4 2 1 As the base of the detector remains in place cable glands d...

Страница 46: ...nfidential The information contained in this document cannot be used either partially or wholly nor divulged or reproduced without the prior agreement of SIMTRONICS 10 WARRANTY MultiTox Detectors are...

Страница 47: ...f enclosure d EN 60079 11 IEC 60079 11 Electrical apparatus for potentially explosive atmospheres Equipment protection by intrinsic safety i EN 50270 Electromagnetic compatibility Electrical apparatus...

Страница 48: ...el DGi TT7 DG TT7 Serial Number S N xxxxxxxxx xxxxaamm DGi TT7 Type of certification CE0081 II 2 G Ex d ia IIC T6 Gb 20 C Ta 60 C Certificate number ATEX LCIE 13 ATEX 3024X IECEx LCIE 13 0021X DG TT7...

Страница 49: ...on of detectors AS215 Calibration kit The kit comprises One air cylinder and one pressurized cylinder containing a mixture of air and a gas of titrated concentration A 30 l H flow rate pressure reduci...

Страница 50: ...nut of maintain black on version A AS019 Suspension cable enclosure body Enables to connect the enclsure with the body during the maintenance operations AS052 Tube mounting adapter Enables DM T 6 DMi...

Страница 51: ...er Lubricant for explosion proof seal and thread MOLYKOTE Brand reference P40 Cartridges toxic gas detectors type E DMi ST6 F1F2 EX0 ww F1 F2 to be specified ww to be specified Cartridges toxic gas de...

Страница 52: ...5 Vol 20 Cl2 Chlorine BD 10 Vol 21 CO Carbon monoxide H2S comp BE 20 Vol 22 CO Carbon monoxide BF 50 Vol 23 CO2 Carbon dioxide BG 100 Vol 24 CO2 Carbon dioxide CH4 immune BH 3 Vol 25 COCl2 Phosgene BJ...

Страница 53: ...65 C4H8O Butanal 66 C4H8O Methyl ethyl ketone MEK 67 C4H9O2 Ethyl acetate 68 C5H10O Methyl isopropyl ketone 69 C5H10O2 Propyl acetate 70 C5H12O Isopentanol 71 C5H8 Isoprene 72 C6H10 D limonene 73 C6H...

Страница 54: ...MultiTox DGi TT7 E O DG TT7 S Page 54 60 NOSP 16452 05 08 2016 13 DECLARATION OF CONFORMITY...

Страница 55: ...MultiTox DGi TT7 E O DG TT7 S Page 55 60 NOSP 16452 05 08 2016...

Страница 56: ...MultiTox DGi TT7 E O DG TT7 S Page 57 60 NOSP 16452 05 08 2016...

Страница 57: ...MultiTox DGi TT7 E O DG TT7 S Page 58 60 NOSP 16452 05 08 2016...

Страница 58: ...MultiTox DGi TT7 E O DG TT7 S Page 59 60 NOSP 16452 05 08 2016...