MultiTox : DGi-TT7-E/O & DG-TT7-S
Page 22 / 60
NOSP 16452-05 (08/2016)
4.3.2.
Connection of the electrical ground braid
Use a shield connection clamp (not supplied) to connect the shielding of the cable to the
electric ground of the housing (see § below).
4.3.3.
Grounding
A M4 screw passes through the body of the enclosure, enabling the electronic ground of the
housing to be connected to the local ground.
It is recommended to use a yellow / green wire with a ring lug (minimum diameter 1.5 mm).
The armour of the power cable is normally connected to the ground of the detector, but it
may depend on site practices.
4.3.4.
3-wires connection(source)
For a standard 3-wires connection, the 20mA current loop must be supplied with 24 V at
terminal L+. To proceed, connect the 3 (V +) and 5 (L +) terminals at the terminal block level
of the device
SOURCE Version
A
0V return
+24VDC
+24VDC
Max 700
Ω
V-
V+
V+
V-
L+
L-
Detector
JP11
C
o
n
n
e
c
t
Shielding to be con-
nected to the enclosure
20 mA loop
+
-
Fire or control system
Содержание MultiTox DG-TT7-S
Страница 1: ...Operating Manual NOSP 16452 05 03 2018 MultiTox Detector MultiTox DGi TT7 E DGi TT7 O DG TT7 S...
Страница 2: ...MultiTox DGi TT7 E O DG TT7 S Page 2 60 NOSP 16452 05 08 2016...
Страница 15: ...MultiTox DGi TT7 E O DG TT7 S Page 15 60 NOSP 16452 05 08 2016 Figure 2 Outline drawing mm...
Страница 39: ...MultiTox DGi TT7 E O DG TT7 S Page 39 60 NOSP 16452 05 08 2016...
Страница 54: ...MultiTox DGi TT7 E O DG TT7 S Page 54 60 NOSP 16452 05 08 2016 13 DECLARATION OF CONFORMITY...
Страница 55: ...MultiTox DGi TT7 E O DG TT7 S Page 55 60 NOSP 16452 05 08 2016...
Страница 56: ...MultiTox DGi TT7 E O DG TT7 S Page 57 60 NOSP 16452 05 08 2016...
Страница 57: ...MultiTox DGi TT7 E O DG TT7 S Page 58 60 NOSP 16452 05 08 2016...
Страница 58: ...MultiTox DGi TT7 E O DG TT7 S Page 59 60 NOSP 16452 05 08 2016...
Страница 59: ......