Page 22 / 56
NOSP16358-03 [04/2016]
Figure 4 : Terminal blocks
Point
JP12 & JP13
Description
1
T2
Relay 2
2
C2
Relay 2
3
T1
Relay 1
4
C1
Relay 1
Point
JP11
Description
1
V-
0 V
2
V+
+24VDC power supply
3
V+
+24VDC power supply loop (connected to point 2)
4
V-
0 V, Connected to point 1
5
L+
20mA Current loop: entry
6
L-
20mA Current loop: output
4.3.2.
Connection of the electrical ground braid
Use a shield connection clamp (not supplied) to connect the shielding of the cable to the
electric ground of the housing (see below).
4.3.3.
Grounding
A M4 screw passes through the body of the enclosure, enabling the electronic ground of the
housing to be connected to the local ground.
It is recommended to use a yellow / green wire with a ring lug (minimum diameter 1.5 mm).
The armour of the power cable is normally connected to the ground of the detector, but it
may depend on site practices.