Each Year
After the First
Three Years
The Simplex Day Tank has been designed to require minimum
maintenance. All components have been chosen for a long, reliable
life. The Day Tank is constantly lubricated by the diesel fuel it
transfers. Inspect this tank at least once every year for dam-age,
leakage, or rust on both inside and outside the tank. Promptly
repair or replace any significantly damaged or deteriorated Day
Tank. Two basic intervals of maintenance are required: each year
and after the first 3 years.
1. Water and sediment should be drained from the tank each year.
If normal engine/generator testing does not consume one tank full
of fuel each year the tank should be drained and refilled with fresh
fuel.
2. Remove the inspection port from the Day Tank. The port is
shown in the illustration below. Examine the interior of the Day
Tank. Using an inspection lamp examine all internal Day Tank
components. With tank drained test sending unit operation. Install
a new inspection port gasket and replace the inspection port cover.
3. Press the Test Fill pushbutton and observe pump and motor
performance.
4. Inspect pump/motor alignment and wear. Inspect the pump for
leaks.
5. Re-tighten hose clamps at pump/hose connections. Re-tighten
the pump bracket, motor bracket, and pump/motor coupler
hardware.
6. Inspect all plumbing connections for leaks. Test all options and
fuel level alarms for proper operation.
7. Re-tighten all electrical connections.
After three years of normal use re-oil the Day Tank motor with 10
drops of 5W30 or 10W oil. Do not over oil the motor.