Table 3-1 shows UL-listed receivers that are compatible with the CCDACT.
Table 3-1. CCDACT / Receiver Compatibility
NOTES:
1. 10 and 20 PPS (Pulses Per Second).
2. With 685-8 Line Card.
3. With 9032 Line Card.
4. With 9004 Line Card.
5. With Rec-11 Line Card.
6. These receivers are also Factory Mutual approved.
Before testing the CCDACT to communicate with the central station, make sure
your laptop PC is unplugged from the DACT.
Do not direct-connect the CCDACT to a coin telephone or party line. The line
must be dedicated to the CCDACT and must not have any TELCO features such
as “Call Waiting”, etc.
Continued on next page
Programming the CCDACT,
Continued
Programming(Continued)
RECEIVER
Comm.
Format
Osborne/
Hoffman
Quickalert
Model II
ADEMCO
685
(See Notes
2, 6)
Silent Knight
9000
FBI
CP220FB
(See Notes
5, 6)
RADIONICS
6500
SUR-GARD
MLR2-DG
(See Note 6)
1
3/1 Standard 1800/2300 Hz
(See Note 1)
YES
YES
YES
(See Note 3)
YES
YES
YES
2
3/1 Standard 1900/1400 Hz
(See Note 1)
YES
YES
YES
(See Note 3)
YES
YES
YES
3
4/2 Standard 1800/2300 Hz
(See Note 1)
YES
YES
YES
(See Note 3)
YES
YES
YES
4
4/2 Standard 1900/1400 Hz
(See Note 1)
YES
YES
YES
(See Note 3)
YES
YES
YES
5
SIA
YES
NO
YES
(See Note 4)
NO
NO
YES
6 RADIONICS
BFSK
1800/2300 Hz
YES
YES
YES
(See Note 3)
YES
YES
YES
7 RADIONICS
BFSK
1900/1400 Hz
YES
YES
YES
(See Note 3)
YES
YES
YES
firealarmresources.com
Содержание Contact Closure DACT
Страница 2: ...1 2 firealarmresources com ...
Страница 4: ...ii firealarmresources com ...
Страница 10: ...viii firealarmresources com ...
Страница 16: ...1 6 firealarmresources com ...
Страница 54: ...3 1 firealarmresources com ...
Страница 57: ...3 3 W wiring the CCDACT 4004 2 5 4005 2 7 4020 2 9 4100 2 13 4120 2 13 I 3 firealarmresources com ...
Страница 58: ...3 1 firealarmresources com ...
Страница 59: ...3 2 firealarmresources com ...