2-2
This section describes a procedure that is required only for Revision 1.03.01
firmware in the 4004 panel, and for Revision 1.01.01 firmware in the 4005,
4020, 4100, and 4120 panels. If you are not using either of these revisions, you
can skip this section.
Note:
Notify the Central Station before testing your system (or disable your
DACT). When your system is under Walk Test, numerous events will
be transmitted to the Central Station automatically.
The following procedure is required only for Revision 1.03.01 firmware in the
4004 panel.
1. Follow the installation procedures described in “Installing the 4004-9810
CCDACT Kit” in this chapter, but do not connect the RINGx (RED) wires
from each of the two TELCO cables.
2. Install the DACT programmer cable and have the terminal ready.
3. Power up the 4004 system. The green LED (PWR/COMM) on the DACT
will blink for approximately 11 minutes. During this time, you will not be
able to program the DACT, and the 4004 will display a (C) trouble status if
the panel had not previously been programmed for a DACT or City option.
During this time you must program the 4004 to enable the DACT/City
option, and should make any other panel programming changes. Exit the
4004 programming mode.
4. Watch the DACT LEDs. Once the green and yellow LEDs turn on together,
you will have about 30 seconds to enter the DACT programming mode from
the terminal. Program the DACT as described in the programming section
of this manual. The exception is that you will connect the RINGx (RED)
wires from each of the two TELCO cables before exiting the DACT
programmer.
continued on next page
Revision-Specific Installations
Overview
4004 Installations
firealarmresources.com
Содержание Contact Closure DACT
Страница 2: ...1 2 firealarmresources com ...
Страница 4: ...ii firealarmresources com ...
Страница 10: ...viii firealarmresources com ...
Страница 16: ...1 6 firealarmresources com ...
Страница 54: ...3 1 firealarmresources com ...
Страница 57: ...3 3 W wiring the CCDACT 4004 2 5 4005 2 7 4020 2 9 4100 2 13 4120 2 13 I 3 firealarmresources com ...
Страница 58: ...3 1 firealarmresources com ...
Страница 59: ...3 2 firealarmresources com ...