2-14
Use Table 2-2 along with the applicable interconnection diagrams when wiring
the 4100/4120-0153 CCDACT into your system. (See Figure Reference 1 on
page 2-13.)
Table 2-2. CCDACT - 4100/4120 Wiring
CCDACT WIRE
COLOR
4100/4120
TB1-1
ORANGE
CPU CARD [TB1 - CITY (NO)]
TB1-2
RED
CPU CARD [TB1 - CITY (+)]
TB1-3
BLUE
CPU CARD [TB1 - TBL (NO)]
TB1-4
BLACK
CPU CARD [TB1 - TBL (C)]
TB2-1
RED
POWER I/F CARD [TB3 (+24V)]
TB2-2
BLACK
POWER I/F CARD [TB3 (0V)]
Installing the 4100/4120-0153 CCDACT Kit,
Continued
Interconnection Table