5.6 WIP Line Fault
The WIPS2000 must connect to a WTRM2000 termination module. The WIPS9004 must connect to a WTRM9007
termination module. Do not swap them over.
NOTE:
WIP Line fault LEDs will flash (whilst un-acknowledged) when a WIP Line fault is detected in its
corresponding
Zone. For example, a flashing WIP Line Fault LED on Zone 2 will indicate a WIP Line fault
associated with that Zone.
A WIPS Module Fault may be present if one or more WIP Line Fault LEDs are active. The zones in fault will
indicate will indicate which WIP Module may be having issues/problems, as the lines in fault will be connected to
this module.
If a WIP Line Fault is detected, you will need to check the wiring configuration (as above) and ensure the correct
EOL (end of line) resistor has been installed. A WIP Line fault indicator LED will be located on the ECP in its
corresponding Zone, depicting which WIP connection to focus on.
Содержание 4100 Classic
Страница 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Страница 4: ...1 0 Identifying Simplex 4100 Series Faults...
Страница 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Страница 30: ...Page 29 of 60 29 of 60 of 60 of 5 of 1 60 3 0 Identifying Faults on the GCC IMS TrueSite Graphics Network...
Страница 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Страница 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Страница 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Страница 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...
Страница 59: ...Page 59 of 60 6 0 National Contact Directory...