background image

 

 

S4100-0051-3  9/2012  

Category Implementation 

BACnet Standardized Device Profile  
(Annex L) 

BACnet Smart Sensor (B-SS) 

BACnet Smart Actuator (B-SA) 

BACnet Application Specific Controller (B-ASC) 

BACnet Interoperability Building Blocks 
Supported (Annex K) 

K.1.2 BIBB -Data Sharing -ReadProperty-B (DS-RP-B) 

K.1.8 BIBB -Data Sharing -WriteProperty-B (DS-WP-B) 

K.5.2 BIBB -Device Management -Dynamic Device Binding-B (DM-DDB-B) 

Segmentation Capability 

None 

Standard Object Types Supported 

Device Object 

Analog Input 

Analog Output 

Analog Value 

Binary Input 

Binary Output 

Binary Value 

Multi State Input Output 

Multi State Output 

Multi State Value 

Additional Property Details 

Properties NOT 

supported

BACnet CreateObject 

BACnet DeleteObject 

Any optional properties 

Additional 

Property Details

No additional writeable properties exist 

No proprietary properties exist 

No range restrictions exist 

Data Link Layer Options 

MS/TP master (Clause 9), baud rate up to 76,800 bps 

MS/TP slave (Clause 9), baud rate up to 76,800 bps 

Device Address Binding 

Not supported 

Character Sets Supported 

ANSI X3.4 

ISO 10656 (ICS-4) 

ISO 10656 (UCS-2) 

ISO 8859-1 

IBM/Microsoft DBCS 

Model  

Description 

Required RS-232 Module 

(ordered separately)* 

Additional Data 

Sheet Reference 

Installation 

Instructions 

4100-6069 

BACpac Ethernet Module for 4100ES, 
4100U, 4100/4100+, and 4120 Series fire 
alarm control panels; single slot (2”) module 

4100ES or 

4100U 

4100-6038 

S4100-0031 579-842 

4100, 4100+,

or 4120 

4100-0113 

4010-9915 

BACpac Ethernet Module for 4010ES Series 
fire alarm control panels; single block 
module (4x5) 

4010-9918 

S4010-0004 

(S4010-0006 for 

international 

applications) 

579-1051 

* Note: BACpac modules connect to Port B of these RS-232 modules. 