Features 

 

Flexible standard combination of addressable 

initiation and 

addressable notification

 

4.3” (109 mm) Diagonal 

color touchscreen

 display: 

 

Convenient and intuitive user interface provides detailed 

system status and individual point information 

 

Supports dual language selection

, including unicode 

character languages 

 

A custom background display appears when operation is 

normal (see page 7 for details)  

Includes a 3 A IDNAC SLC (signaling line circuit) 

output power supply that provides 

enhanced power 

delivery 

to 

addressable

 notification appliances: 

 

constant

 29 VDC source voltage is maintained during 

alarm, even during battery operation, allowing strobes to 

operate at higher voltage with lower current and ensuring 

a consistent current draw and voltage drop margin under 

both primary power and secondary battery standby 

 

Efficiencies include lower strobe currents, wiring 

distances up to 2 to 3 times farther than with conventional 

notification, support for more appliances per IDNAC SLC, 

and smaller gauge wiring. This provides installation and 

maintenance savings. with high assurance that appliances 

will operate as normal during worst case alarm conditions 

 

IDNAC SLCs are compatible with both TrueAlert ES and 

TrueAlert addressable notification appliances, and remote 

4009 IDNAC Repeaters to extend power and wiring 

distance even farther and provide for up to 127 addressable 

notification appliances 

 

Power supply provides battery backup charging of up to 

33 Ah; up to 18 Ah for cabinet mounted batteries and up 

to 33 Ah batteries for mounting in close-nippled remote 

battery cabinet 

Electrically isolated IDNet+ addressable initiating 

device SLC: 

 

Provides built-in short circuit isolation for monitoring 

and control of TrueAlarm analog sensors and IDNet 

communications monitoring and control devices; for use 

with either shielded or unshielded, twisted or untwisted 

single pair wiring; outputs are Class A or Class B 

 

Standard panel SLC provides up to 100 addressable 

points; optional additional loop expansion modules 

provide an additional isolated loop with short circuit 

isolation for the IDNet+ channel; each loop expansion 

module also provides an additional 75 addressable points 

to the IDNet+ channel capacity for a total of up to 250 

addressable points 

Software Feature Summary: 

 

Current and previous panel configuration are both 

maintained in on-board memory to allow easy selection 

of desired revision 

 

An internal Ethernet service port and an internal serial 

service port are available for service computer 

connections to perform configuration updates, 

downloads and uploads; report downloads, and system 

software updates (Ethernet port only); the serial port 

provides the connection for the optional TrueInsight 

Module  

 

 

4007ES Panel Front View 

Software Feature Summary 

(Continued)

 

An internal USB interface allows a compatible portable 

memory device (memory stick/thumb drive) to store job 

revisions, update revised jobs and panel software, and 

save detailed system reports from the panel without 

requiring a service computer  

Optional modules and connections include:  

 

Point or Event DACT assembly that is compatible with 

IP Communicators 

 

Up to two additional IDNet+ addressable device output 

loop connections with short circuit fault protection and 

with 75 additional point capacity each 

 

Front mounted 48 LED annunciator with custom label 

inserts provides 24 Yellow LEDs, 20 Red LEDs, and 

4 Red/Green LEDs; LEDs are programmable for up to 

24 IDC zones of alarm and trouble annunciation or as 

required for custom annunciation requirements 

 

Dual Class A IDNAC Isolator (DCAI) 

 

Remote LED annunciator support via RUI (remote unit 

interface) communications port for use with unshielded, 

twisted pair wiring (UTP) 

 

Eight Point Zone/Relay Modules individually selectable 

as IDC or relay rated 2 A @ 30 VDC (resistive) 

 

Alarm relays and auxiliary relays 

 

City connections, with or without disconnect switch 

 

4003EC Voice Control Panels 

 

4009 Series IDNAC Repeaters 

 

Battery brackets for seismic area protection (see page 2) 

General Mechanical:  

 

Compact red or platinum cabinet for convenient surface 

or semi-flush mounting; rated NEMA 1 and IP30 

4007ES Listings reference: 

 

UL 864, Fire Detection and Control (UOJZ) 

 

ULC S527, Control Units for Fire Alarm Systems 

*   This product has been approved by the California State Fire Marshal (CSFM) pursuant to 

Section 13144.1 of the California Health and Safety Code. See CSFM Listing 

7165-0026:0378 for allowable values and/or conditions concerning material presented in this 

document. NYC Fire Dept COA #6151. Additional listings may be applicable; contact your 

local Simplex product supplier for the latest status. Listings and approvals under Simplex 

Time Recorder Co. are the property of Tyco Fire Protection Products. 

 

 

4007ES Fire Control Panels 

UL, ULC, CSFM Listed;

 

 Fire Detection and Control with Addressable

 

FM, NYC Fire Dept Approved*

 

Initiation and Addressable Notification

 

 

 

S4007-0002-6  11/2015

 

Содержание 4007-9201

Страница 1: ...on board memory to allow easy selection of desired revision An internal Ethernet service port and an internal serial service port are available for service computer connections to perform configuratio...

Страница 2: ...puter or to the USB drive Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring WALKTEST silent or audible system test performs an...

Страница 3: ...in Menu May 27 2015 12 24 PM System Trouble Screen identifies active troubles with custom labels displayed arrows allow navigation through the list Trouble Log Screen allows review of past troubles wi...

Страница 4: ...data sheet S4098 0052 for details TrueAlarm heat sensors can be selected for fixed temperature detection with or without rate of rise detection Utility temperature sensing is also available typically...

Страница 5: ...area zone covered by appliances on the notification appliance circuit NAC making it much more difficult and costly to locate and correct the source of a problem Using the TrueAlert magnet test allows...

Страница 6: ...num Models with BA are available assembled in the USA by adding the suffix BA 6 S4007 0002 6 11 2015 Factory Programming Options Model Description 4007 8810 Factory Programming select 4007 0831 Custom...

Страница 7: ...tion Manual 579 1103 4007ES Hybrid Data Sheet S4007 0001 Detailed Operator s Manual 579 1165 Field Installed Optional Modules Model Description Supv Alarm 4190 8001 TrueInsight Remote Service Gateway...

Страница 8: ...9803 IDNet Loop Expansion Modules maximum of two two are shown 4 IDNAC Power Supply Assembly 5 Location for additional 4007 9801 Zone Relay Module 6 Location for additional 4007 9801 Zone Relay Module...

Страница 9: ...009 IDNet NAC Extender S4009 0002 Battery and Battery Cabinet Reference S2081 0006 4003EC Voice Control Panel S4003 0002 Seismic Battery Brackets Reference S2081 0019 4606 Series Color LCD Touchscreen...

Страница 10: ...f Test TrueAlert addressable appliance not TrueAlert ES addressable appliance Note Additional TrueAlert ES Self Test information is detailed in Operating Instructions 579 1165 shipped with the panel S...