This is where you indicate the number of seconds for the duration of
switch pulse. The value can be set at 0.1 to 25.5 seconds. If you enter 3
seconds, for example, an electric strike is released for 3 seconds before
it locks again.
Limited range
If you select this option, the reader range from the transponder to the
SmartRelay is reduced from 1.5 m to about 0.4 m. This option can be
used when several SmartRelays are in close proximity to one another
and individual transponders are authorised for use on several
SmartRelays, for example.
Logging unauthorised attempted access events
For SREL.ZK and SREL.ADV only: Normally, only authorised transponder
operations are logged. You need to select this option if you also wish to
record attempts to open the door with non-authorised transponders.
Number of extension modules
This where you indicate the number of external modules connected to
the SmartRelay. These modules are connected to the terminals RS-485
C OM, RS-485 A and RS-485 B.
Interface
For SREL.ADV only: You can enter the type of card reader here which
the SmartRelay is to simulate for operation as a serial interface.
The following options are available:
Wiegand, 33 bit
Wiegand, 26 bit
Primion
Siemens
Kaba Benzing
Gantner Legic
Isgus
No audible programming acknowledgement signals
For SREL.ADV only: You should check this field if you do not want
audible programming confirmation signals to be emitted from a
connected buzzer or beeper while you are programming SmartRelay.
External LED/external beeper
For SREL.ADV only: This indicates which external component group is
connected. In flip flop mode, SmartRelay emits a permanent signal
when switched on if there is an external LED; in the case of a beeper, an
audible signal is only emitted when there is a change of status.
SREL1+2
(Manual)
6. Configurations in the software
26 / 38