Debugging
Please check voltage in the following sequence:
Check voltage!
L1
N
230 V~
Only with “mains”
1.
If the voltage value now complies with the datas at the data sheet, the power consumption of one of the consuming devices
connected to the outputs “E”
, is too high. Reconnect and recheck the particular output
voltage. Check the consuming devices for quantity and faultless function. If the voltage values even after disconnecting
still differ from the declared values, the control panel has to be checked in the factory.
“U”, “B1”, “B2”, “Y”, “OK”, “M” or “B3”
E
-
V=
2.
only with “mains”
at least 21 V
only at “mains”
at least 21 V
S
O
V=
3.
only at “OPEN” or “CLOSE”
24
V (Mains)
6
0,5
21,5 - 26 V (Accu)
B1
_
V=
4.
B2
_
V=
5.
B3
_
V=
6.
at “mains” and “Accu”
at least 20 V (Mains)
at least 18 V (Accu)
7.
OK
_
V=
Please check the fuses if the voltage differed from the
datas of this manual. Disconnect all power consuming
devices and close all closed circuit loops in the control
panel with resistors and diode block.
Attention!!
Mains failure causes a failure indication!
The failure causes an activation of the SHEV system!
S S G O O
Example:
Output actuators
8.
9.
at “mains” and “accu”
at least 21 V (Mains)
at least 18 V (Accu)
in case of failure only
only when SHEV triggered
Y
_
V=
M
_
V=
at “mains” and “akku”
at least 20 V (Mains)
at least 18 V (Accu)
Installation manual ESM-T/X-EV (24 A / 48 A / 72 A)
Page 19/20
SIMON RWA SYSTEME GmbH, Passau
ESM-T/X-EV with power supply
Dublications, also in extracts, are only legal with express authorisation from SIMON RWA SYSTEME GmbH Passau
®