User manual - POWER SUPPLY TRS-09a 

Figure 4.5. Connection of  power supply

Serial   connection  of    power   supply modules  

TRS-09a

  (while   power  output  of  one  module 

drives control input of the next one,  Figure 4.6), allows turn off all modules connected to the 
network at the same time. When power supply of first  

TRS-09a

  module is turned off, then 

following  power supply modules will be turned off sequentially.

 

Figure 4.6. Cascade of  power supply modules 

TRS-09a

.

RS-485 bus should be equipped with termination resistors (100-150 ohm) on 
both ends. The bus must not be ramified, and longer than 1 km.

9

FUSE

L  N

N
L

1 2

A+

B-

terminator
(120 ohm)

ctrl

 ...

Measurement modules of TRS system

TRS- 09a modules

SRS-2/4-Z16-B1a

Содержание TRS-09a

Страница 1: ...6 User manual POWER SUPPLY TRS 09a Designed for TRS system Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes without prior n...

Страница 2: ...n of symbols used in the manual This symbol denotes especially important guidelines concerning the installation and operation of the device Not complying with the guidelines denoted by this symbol may...

Страница 3: ...ched off and disconnected from the power supply prior to starting installation of troubleshooting in the case of malfunction Neighbouring and mating equipment must meet the requirements of appropriate...

Страница 4: ...efficiency max 200 mA Control voltage 7V 12V DC max 2mA Protection level IP 65 ABS casing Housing type Housing material Housing dimensions L x W x D without glands with glands wall mounted ABS 110 x 8...

Страница 5: ...etwork voltage corresponds to the nominal voltage stated on the unit s identification label The load must correspond to the requirements listed in the technical data All installation works must be con...

Страница 6: ...circuit breaker located near the unit In the case of using a monopolar fuse it must be mounted on the phase cable L The power supply network cable diameter must be selected in such a way that in the...

Страница 7: ...ransmission cables together with power supply cables and cables controlling induction loads e g contactors Such cables should cross at a right angle Contactor coils and induction loads should be equip...

Страница 8: ...nes connectors GND GND of supply output and control input Figure 4 4 Connection of TRS 09a module to the network 8 5 8 7 6 4 3 1 2 DATA DATA RS 485 ctrl GND 12V out shield 230V AC J1 J2 LED indicator...

Страница 9: ...network at the same time When power supply of first TRS 09a module is turned off then following power supply modules will be turned off sequentially Figure 4 6 Cascade of power supply modules TRS 09a...

Страница 10: ...rked with this symbol should not be placed in municipal waste Please check local regulations for disposal and electronic products 5 SELECTION OF OPERATION MODE The selection of operation mode can be d...

Страница 11: ...User manual POWER SUPPLY TRS 09a Figure 5 1 Selection of operation mode 11 5 8 7 6 4 3 1 2 J1 J2 Operation mode selection jumpers J1 J2 J1 J2 J1 J2 Stand alone mode Externally controlled mode or...

Страница 12: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Отзывы: