background image

User manual for digital clock SWZ-W610

8. 

       THE MODBUS PRO

  

TOCOL HANDLING

  

Transmission parameters: 1 start bit, 8 data bits, 1 or 2 stop bit (2 bits are send, 1 and 2 bits 

are accepted when receive), no parity control

Baud rate:

selectable from: 1200 to 115200 bits/second

Transmission protocol:

MODBUS RTU compatible

The device parameters and display value are available via RS-485 interface, as HOLDING-

type registers (numeric values are given in U2 code) of Modbus RTU protocol. The registers 

(or groups of the registers) can be read by 03h function, and wrote by 06h (single registers)  or 

10h (group of the registers) accordingly to Modbus RTU specification. Maximum group size for 

03h and 10h functions can not exceeds 16 registers (for single frame).

The device interprets the broadcast messages, but then do not sends the answers. 

8.1. 

  

    LIST OF REGISTERS

  

Register Write

Range

Register description

10h

No

0÷6

Days of the week registry: 

0

 - Sunday, 

1

 - Monday, etc.

11h

Yes

2000÷2099

Year registry

12h

Yes

1÷12

Months registry

13h

Yes

1÷31

Days registry

14h

Yes

0÷23

Hours registry

15h

Yes

0÷59

Minutes registry

16h

Yes

0÷59

Seconds registry

17h

Yes

see descr.

Control registry for time-related settings:

0

 - startup of continued update of registries 10h ÷ 16h by internal 

clock (current time and date),

80h

 - stopping update of registries 10h ÷ 16h by internal clock 

(automatically after writing one of 10h ÷ 16h registries). In this 
status 10h ÷ 16h registries can be written with new values in 
order to update internal clock settings. 

Updating the clock settings with contents of 10h ÷ 16h registries can 
be executed by sending the following commands to the control 
registry:

01h 

- hour update on the basis of (14h ÷ 16h) registries’ contents;

02h 

- date update on the basis of (10h ÷ 13h) registries’ contents;

03h

 - time and date update on the basis of (10h ÷ 16h) registries’ 

contents.
After sending commands 

01h

02h

 or 

03h

 the contents of registries 

automatically return to 0. 

18h

No

-40÷85

Temperature measured by digital thermometer module

20h

1

Yes

0÷199

Device address

21h

No

009Eh

Device identification code

21

i

Содержание SWZ-W610

Страница 1: ...for digital clock type SWZ W610 firmware version 1 01 or higher Read the user s manual carefully before starting to use the unit Producer reserves the right to implement changes without prior notice...

Страница 2: ...ation of DCF77 module 12 7 DEVICE PROGRAMMING 14 7 1 PROGRAMMING MENU 14 7 2 PARAMETERS EDITION 14 7 2 1 Numeric parameters digit change mode 14 7 2 2 Numeric parameters slide change mode 15 7 2 3 Swi...

Страница 3: ...up according to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case of a defect of unit operation there is a risk of a ser...

Страница 4: ...mode only and internal battery preserves proper time counting even if device is turned off from power supply The SWZ W610 is designed to operate in closed rooms where relative humidity is lower than 9...

Страница 5: ...on volatile memory EEPROM type Protection level IP 30 Housing type Housing material Housing dimensions Wall mounted aluminium methyl polimethacrylate 578 x 208 x 102 mm Operating temperature Storage t...

Страница 6: ...y Protecting the power supply clamps against unauthorized persons must be taken into consideration 4 1 UNPACKING After removing the unit from the protective packaging check for transportation damage A...

Страница 7: ...mounted on the phase cable L The power supply network cable diameter must be selected in such a way that in the case of a short circuit of the cable from the side of the unit the cable shall be protec...

Страница 8: ...g induction loads e g contactors Such cables should cross at a right angle Contactor coils and induction loads should be equipped with anti interference protection systems e g RC type Use of screened...

Страница 9: ...Earth terminal is 2 Nm Power supply connection must be made using 3 wire cord After installation power cord gland should be tighten up to prevent cable move Metal housing must be connected with PE gro...

Страница 10: ...ry cloth In the case of more significant contamination use warm water with small amount of detergent to wet the cloth Using any other agents can cause permanent damage to the housing Product marked wi...

Страница 11: ...tal temperature sensor module is connected to THERM input the device can display current temperature near the sensor The display can show only one of these parameters or can change them in sequence wi...

Страница 12: ...f high air flow sunny places and near of artificial light sources like bulbs etc Due to possibility of electromagnetic noise while using long connection wires a temperature sensor should be equipped w...

Страница 13: ...LED is on should be shorter than time while LED is dark The additional test of correct orientation of the aerial is number of received bits see parameter Sync of dCF submenu Aerial should be oriented...

Страница 14: ...ion of ENTER button depend on present menu position if the name of some sub menu is displayed enter this sub menu name of the first parameter or next level sub menu is displayed if the name of some pa...

Страница 15: ...ncel the changes press ESC button shortly after SEt is displayed After that device returns to the menu 7 2 3 Switch parameters LIST type Switch parameters can be described as a sets of values a lists...

Страница 16: ...parameter to 00 causes in permanent displaying of time after switch device to display it dL d this parameter defines the displaying period of current date in format day month year in range from 1 to...

Страница 17: ...eived data the double dot between hour and minutes will start to pulse in asymmetrical mode lighting time much shorter than time of dimming diSP this parameter allows to on off the signalisation of DC...

Страница 18: ...to 199 If the value 0 is set then device responds to frames with address 255 FFh Every SWZ W610 connected to the same serial network should have its own address different from other devices addressed...

Страница 19: ...ble by the one use password To get this password please contact with Marketing Division Single use password can be used only one time after that it is destroyed Entering this password causes in cleari...

Страница 20: ...n 4 digit user password entering if it is different from 0000 thEr MENU ESC rS MENU ESC dEFS ENTER MENU ESC MENU ESC SErv Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud mbAC rESP MENU...

Страница 21: ...Monday etc 11h Yes 2000 2099 Year registry 12h Yes 1 12 Months registry 13h Yes 1 31 Days registry 14h Yes 0 23 Hours registry 15h Yes 0 59 Minutes registry 16h Yes 0 59 Seconds registry 17h Yes see d...

Страница 22: ...eter in Func menu date displaying 0 disabled 1 enabled 39h Yes 0 1 yEAr parameter in Func menu display year while date 0 disabled 1 enabled 3Ah Yes 0 1 thEr parameter in Func menu temperature displayi...

Страница 23: ...ield description ADDR Device address on modbus network FUNC Function code REG H L Starting address address of first register to read write Hi and Lo byte COUNT H L No of registers to read write Hi and...

Страница 24: ...H 07 D5 00 05 00 17 EA BA This write causes by setting the date to 23th of may 2005 Device s answer ADDR FUNC REG H L COUNT H L CRC L H 01 10 00 01 00 03 D1 C8 4 Try to write improper value to registe...

Страница 25: ...ng on 17 yEAr Enable disable of year displaying while date displaying on 17 thEr Enable disable of temperature displaying oFF 17 DCF77 signal receiver configuration dCF menu modE Enable disable of syn...

Страница 26: ...User manual for digital clock SWZ W610 26...

Страница 27: ...User manual for digital clock SWZ W610 27...

Страница 28: ...SIMEX SIMEX Sp z o o ul Wielopole 7 PL 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex com pl e mail info simex com pl...

Отзывы: